Checking Operation

Overvoltages

Gradually increase the input from 80% of the set value.

The input will equal the operating value when the input 

exceeds the set value and the alarm indicator starts flashing. 

Operation can be checked by the relay outputs that will start 

after the operating time has passed.

Undervoltage

Gradually decrease the input from 120% of the set value and 

check the operation using the same method as for 

overvoltage.

Example: Overvoltage Operating Mode and an Operating Time of 5 s

Note:

K8AK-VS

@

 output relays are normally operative.

Connection Diagram

How to Measure the Operating Time

Overvoltage

Change the input suddenly from 0% to 120% of the set value 

and measure the time until the Unit operates.

Undervoltage

Change the input suddenly from 120% to 0% of the set value 

and measure the time until the Unit operates.

Questions and Answers

Q

Q

Set value

Input voltage

Alarm indicator

Relay output

Flashing

Lit

5 s

200 VAC

0 to 300 V

V

A1
A2

±

C 200 V

Variable 

autotransformer

Input terminals

Power supply

Cycle counter

Q

Q

Summary of Contents for K8AK-VS

Page 1: ...r to page 30 for commonly asked questions For the most recent information on models that have been certified for safety standards refer to your OMRON website Setting range Control power supply voltage...

Page 2: ...tive load 5 A at 250 VAC 5 A at 30 VDC Maximum contact voltage 250 VAC or 30 VDC Max switching current 5 A Maximum switching capacity 1 250 VA 150 W Mechanical life 10 million operations min Electrica...

Page 3: ...t 10564 CSA CAN CSA C22 2 No 14 CCC GB14048 5 Insulation resistance 20 M min Between external terminals and case Between power supply terminals and input terminals Between power supply terminals and o...

Page 4: ...nerated during the instable period when the power is first turned on There is no relay output during timer operation Note There is no polarity when a DC current input is used T1 T Set value Input Powe...

Page 5: ...dicator Terminal block See notes 1 and 2 Terminal block See notes 1 and 2 Item Meaning Power indicator PWR Green Lit when power is being supplied Relay status indicator RY Yellow Lit when relay is ope...

Page 6: ...ng method relay drive method and operating mode are set using the DIP switch located on the bottom of the Unit Model Setting range Wiring connection K8AK VS2 1 to 10 V AC DC V1 COM 3 to 30 V AC DC V2...

Page 7: ...the input have reached the same level Use this as a guide to set the hysteresis Example Maximum Setting of 600 VAC VDC Voltage Set Value SV of 50 and Overvoltage Operation Operation will be at 300 V a...

Page 8: ...hod as for overvoltage Example Overvoltage Operating Mode and an Operating Time of 5 s Note K8AK VS output relays are normally operative Connection Diagram How to Measure the Operating Time Overvoltag...

Page 9: ...s 2 Use and store the product in a location where the ambient temperature and humidity are within the specified ranges If applicable provide forced cooling 3 Mount the product in the correct direction...

Page 10: ...will be large if the K8AK AS K8AK AW K8AK VS or K8AK VW is used for thyristor or inverter control The K8AK PH K8AK PA K8AK PM K8AK PW or K8DS PH cannot be used on the secondary side of an inverter To...

Page 11: ...nt or addition to the above warranty See http www omron247 com or contact your Omron representative for pub lished information 14 Limitation on Liability Etc OMRON COMPANIES SHALL NOT BE LIABLE FOR SP...

Page 12: ...rasil 55 11 2101 6300 www omron com br OMRON ARGENTINA SALES OFFICE Cono Sur 54 11 4783 5300 OMRON CHILE SALES OFFICE Santiago 56 9 9917 3920 OTHER OMRON LATIN AMERICA SALES 54 11 4783 5300 OMRON INDU...

Reviews: