1 - 11
1 Outline
K6PM-TH Thermal Condition Monitoring Device User’s Manual (H231)
1-
4 Part Na
mes an
d F
u
n
ction
s
1
1
-4-1
Main U
nit
Indicator Specifications
(K)
Indicators
Indicates the product status or network status by LEDs.
• "MS": Module Status. Displays the status of the Main Unit. It is
green when it is normal.
• "NS": Network Status. Displays the state of the communications. It
lights or flashes green when it is normal.
For details, refer to
(L)
CH
Indicates the K6PM-TH sensor number. 1 to 31.
(M)
°
e
Temperature unit
Displays the temperature unit. °C or °F.
*1. The display is as follows when the arrival prediction function is enabled.
• The predicted arrival temperature exceeds threshold 1, and the current temperature or differential tem-
perature does not exceed the threshold: Flashes yellow
• Regardless of whether the predicted arrival temperature exceeds threshold 1, the current temperature or
differential temperature exceeds threshold 1: Lit in yellow
• Regardless of whether the current temperature or differential temperature exceeds threshold 1, the pre-
dicted arrival temperature exceeds threshold 2: Flashes red
• Regardless of whether the predicted arrival temperature exceeds the threshold, the current temperature
or differential temperature exceeds threshold 2: Lit in red
Symbol
Name
Color
Status
Operating condition
MS
Product
status
indication
(Module
Status}
Green
Lit.
Normal status
Flashes at 1-s
intervals.
BOOTP server connection error state
Red
Lit.
One of the following fatal errors (Main Unit internal error)
• Internal CPU error
• Internal memory error
Flashes at 1-s
intervals.
One of the following conditions
• K6PM-TH sensor communications error
• The detection of the K6PM-TH sensor angle deviation
• Sensor type error
• Temperature measurement range exceeded
• Running time error
--
Not lit.
No power supply
NS
Network
status
indication
(Network
Status)
Green
Lit.
Tag data link or message connection established
Flashes at 1-s
intervals.
No tag data link or message connection established
Red
Lit.
IP address duplication status
Flashes at 1-s
intervals.
The connection has timed out
--
Not lit.
No power supply, or IP address not set
Symbol
Name
Function
Summary of Contents for K6PM-TH
Page 56: ...2 Installation and Wiring 2 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 76: ...3 Initial Setting 3 20 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 156: ...7 Troubleshooting 7 8 K6PM TH Thermal Condition Monitoring Device User s Manual H231...
Page 195: ...I 1 I K6PM TH Thermal Condition Monitoring Device User s Manual H231 Index...
Page 197: ......