K3MA-J

Setting Example

Initial Settings

The settings for the following example are shown here.

Example: Tank pressure display

Here, the pressure inside the tank is to be displayed in units of 0.1
kPa.

Pressure Sensor

Measuring range: 0 to 980 kPa, output 4 to 20 mA

1.

Set the K3MA-J input type to the 4 to 20 mA input range.
Parameter: 

in-t

 (input type), Setting value: 

4-20

2.

Set the display values for the corresponding input values.
Set the scaling as shown below for the following correspondence:
input 4 mA-->display 0.0, input 20 mA-->display 980.0
Parameter

Setting value

inp.1

 (scaling input value 1)

4.00

dsp.1

 (scaling display value 1)

00000

inp.2

 (scaling input value 2)

20.00

dsp.2

 (scaling display value 2)

09800

dp

 (decimal point position)

%%%%.%

Note:

The decimal point position here refers to the position in the
number after scaling. When setting the scaling display value, it
is necessary to consider the number of digits to be displayed
past the decimal point.

Troubleshooting

When an error occurs, error details will be displayed on the main indicator. Confirm the error from the main indicator and take the appropriate coun-
termeasures.

 

 

 

 

0 to 9

8

0 kPa 

4 to 20 mA 

Press

u

re Sensor

K3MA-J-A2 24

V

AC/

V

DC 

Max 
Min 

SV 

MAX/MIN LEVEL  MODE  SHIFT 

UP 

(

)

(

)

(

)

(

)

Display 

v

al

u

e

DISPLAY 2

DISPLAY 1

I

N

PUT 1

I

N

PUT 2

Inp

u

v

al

u

e

Level 

display

Main indicator

Error contents

Countermeasures

Not lit

e111

RAM memory error

Repair is necessary.
Consult your OMRON sales representative.

5

e111

EEPROM memory error

When this error is displayed, press the Level Key for 3 sec-
onds, and the settings will be restored to the factory set-
tings.
If the error cannot be recovered, repair is necessary. Con-
sult your OMRON sales representative.

Not lit

Flashes 

s.err

You will see this indication when turning ON the 
product the first time after purchase. This is be-
cause the input signal value is 0 mA at that time 
even though the range is factory set to 4 to 20 mA.
For the K3MA-J-A2, the relay output will be OFF. 

At the initial setting level, set the input type and other pa-
rameters according to your application.

Input error

Promptly change the input voltage/current to a value that 
falls within the measurement range. 
If the error cannot be recovered, repair is necessary. Con-
sult your OMRON sales representative.

Not lit

Flashes 

99999

The scaling display value exceeds 99999.

Promptly change the input to a value that falls within the 
specified range.

The scaling value may be inappropriate. Review the scal-
ing value at the initial setting level.

Not lit

Flashes 

The scaling display value is lower than 

19999. 

Promptly change the input to a value that falls within the 
specified range.

The scaling value may be inappropriate. Review the scal-
ing value at the initial setting level.

19999

-

In the interest of product improvement, specifications are subject to change without notice.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.

Summary of Contents for K3MA-J 100-240VAC

Page 1: ...CE marking Model Number Structure Model Number Legend 1 Input Type J DC voltage current 2 Comparative Output Model None No output A2 2 relay contact outputs SPST NO 3 Supply Voltage 100 240VAC 100 to...

Page 2: ...on resistance Vibration 10 to 55 Hz Acceleration 50 m s2 5 min each in X Y and Z directions for 10 sweeps Shock resistance 150 m s2 100 m s2 for relay contact outputs 3 times each on 3 axes 6 directio...

Page 3: ...red OUT type change upper limit lower limit upper lower limit Average processing simple average Output Relays 2 SPST NO Delay in comparative outputs 750 ms max Degree of protection Front panel NEMA4X...

Page 4: ...ge input For current input OUT1 OUT2 COM COM Current input Terminal No Name Description Operation power Connects the operation power supply Analog input Connects the voltage or current analog input Ou...

Page 5: ...ng value Meaning Parameter Setting value Meaning inp 1 19999 to 99999 Input value for dsp 1 dp Display four digits after decimal point dsp 1 19999 to 99999 Input value for inp 1 Display three digits a...

Page 6: ...set value The three types of output operations shown above can be combined as desired The following are examples of possible combinations T lights to indicate that the parameter is valid for teaching...

Page 7: ...or from red to green according to the status of the comparison criterion Display Auto return Time This function automatically returns the display to the operation level s current value if no keys are...

Page 8: ...ge the level 6 Mode Key Used to allow the main indicator to indicate parameters sequentially 7 Shift Key Used to enable a set value to be changed When changing a set value this key is used to move alo...

Page 9: ...packing is provided with the Controller Wiring Precautions Use crimp terminals Tighten the terminal screws to a torque of approximately 0 5 N m To avoid the influence of noise route signal lines and...

Page 10: ...e the forced zero The Z indicator will turn OFF If forced zero protection is turned ON in the protect level the Up Key cannot be used to set a forced zero Forced zero protection is ON in the default s...

Page 11: ...etting level 1234 5 Power ON Operation level Protect level Initial setting level Advanced function setting level Time set by user See note 1 s min 1 s min 1 s min Flashing stops if key is released Con...

Page 12: ...UT2 upper limit value OUT2 lower limit value OUT2 value Some parameters are not displayed for certain models The K3MA J will stop measurement if the level is changed to the initial setting level or ad...

Page 13: ...d function setting level Enter password 0169 Parameter initialization Average processing OUT1 hysteresis OUT2 hysteresis Models with the compar ative output function MODE MODE MODE MODE MODE MODE MODE...

Page 14: ...tting change lockout Forced zero shift lockout Parameter Setting Operation level Current value display Set value display oapt 0 Allowed Allowed 1 Allowed Allowed 2 Allowed Prohibited Parameter Setting...

Page 15: ...Repair is necessary Consult your OMRON sales representative 5 e111 EEPROM memory error When this error is displayed press the Level Key for 3 sec onds and the settings will be restored to the factory...

Page 16: ...ther in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted Suitability of Use Omron Companies shall not be responsible for conformity...

Page 17: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information Omron K3MA J A2 24VAC VDC K3MA J 24VAC VDC...

Reviews: