Limit Value Switch
K3FP-SL-UI
37
Precautions
Refer to pages 38 and 39 for common precautions.
■
Precautions for Correct Use
Indicators
The status indicator (yellow LED) inside the translucent cover shows
when voltage is applied to the contact coil, i.e., that the contact is
switching.
The error indicator (red LED) inside the translucent cover shows the
following error status.
Setting Output Operation Values
The output operation values can be set using the potentiometer for
adjustment inside the translucent cover.
Output Operation
Terminals 3 and 4 are closed and terminals 2 and 3 are open when
the Unit power is OFF.
(1) Pin 8 on DIP Switch S1 Is OFF
(2) Pin 8 on DIP Switch S1 Is ON
Setting Method
1.
Set the input signal, hysteresis, contact operation (delay time),
and contact drive method using the DIP switch.
2.
Mount the Unit to DIN rail and wire it.
3.
Apply a real input signal, enter the input value (output operation
value) for comparative judgment, and adjust using the
potentiometer.
Note:
The output operation can be checked by whether the status
indicator (yellow) is lit or not lit.
Error indicator
status
Error details
Lit
Overrange: 102.5% or more
Flashing
Unit malfunction
Potentiometer for adjustment
0
Input
(%)
50
100
Set value
(Closed)
(Open)
(Open)
(Closed)
Between terminals 3 and 4
Between terminals 2 and 3
Hysteresis
Between terminals 2 and 3
Set value
ON
OFF
0
Input
(%)
50
100
Set value
(Open)
(Closed)
(Closed)
(Open)
Between terminals 3 and 4
Between terminals 2 and 3
Hysteresis
Between terminals 2 and 3
Set value
ON
OFF