RTD Transducer
K3FP-RS-UI
25
DIP Switch Settings
All DIP switches are turned OFF at shipment.
DIP Switch S1
DIP switch S1 is used to set the connection method, output signal
range, and measurement range start value.
DIP Switch S3
DIP switch S3 is used to select current and voltage outputs for output
signals.
SWITCH
DIP switch S1
ON
●
↑
OFF
❍
↓
1
2
3
4
5
6
7
8
Connection method
2-conductor
❍
❍
2-conductor
●
❍
3-conductor
❍
●
4-conductor
●
●
Output signal range
0 to 20 mA
❍
❍
❍
20 to 0 mA
●
❍
❍
4 to 20 mA
❍
●
❍
20 to 4 mA
●
●
❍
0 to 10 V
❍
❍
●
10 to 0 V
●
❍
●
0 to 5 V
❍
●
●
1 to 5 V
●
●
●
Start temperature
[
°
C]
[
°
F]
0
32
❍
❍
❍
−
10
14
●
❍
❍
−
20
−
4
❍
●
❍
−
30
−
22
●
●
❍
−
40
−
40
❍
❍
●
−
50
−
58
●
❍
●
−
100
−
148
❍
●
●
−
150
−
238
●
●
●
SWITCH DIP switch S3
ON
●
↑
OFF
❍
↓
1
2
Output signal
0 to 20 mA
●
❍
20 to 0 mA
4 to 20 mA
20 to 4 mA
0 to 10 V
❍
●
10 to 0 V
0 to 5 V
1 to 5 V