background image

10

Mini Motor Contactor 

J7KNA

Cable cross-section

all connectors

solid

mm² 0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

flexible

mm² 0.75 - 2.5

0.75 - 2.5

0.75 - 2.5

flexible with multicore cable end

mm² 0.5 - 1.5

0.5 - 1.5

0.5 - 2.5

Clamps per pole

2

2

2

solid or stranded

AWG 18 - 14

18 - 14

18 - 14

*1) version „VS“
*2) Suitable at 690V for: earthed-neutral systems, overvoltage category I to IV, pollution degree 3 (standard-industry): U

imp

 = 8kV.

Data for other conditions on request.

*3) With reduced control voltage range 0.9 up to 1.0 x U

s

 and with reduced thermal rated current I

th

 to I

e

/AC15

*4) Summary switching time = release time + arc duration
*5) Release time of NC make time of NO increase when suppressor units for voltage peak protection are used 

(Varistor, RC-units, Diode units).

Mini Motor Contactors 

Data according to IEC 947-5-1, VDE 0660, EN 60947-5-1

Auxiliary Contacts

Type

J7KNA-09...
J7KNA-12...

J7KNA-09...D(VS)

*1

J7KNA-12...D(VS)

J73KN-A...

Mini Contactors for North America

Data according to UL508

Main Contacts (cULus)

Type

J7KNA-09...

J7KNA-12...

J73KN-A...

Rated operational current "General Use"

A

15

20

10

Rated operational power of three-phase motors

115V

hp

2

-

at 60Hz (3ph) 

200V

hp

3

3

-

230V

hp

3

3

-

460V

hp

5

-

575V

hp

10

-

Rated operational power of of AC motors

115V

hp

½

¾

-

at 60Hz (1ph)

200V

hp

1

-

230V

hp

2

-

Fuses  

A

30

30

-

Suitable for use on a capability of delivering not more than

rms

(SCCR)

A

5000

5000

-

V

600

600

-

Rated voltage

V AC 600

600

600

Auxiliary Contacts (cULus)

heavy pilot duty

AC

A600

A600

A600

standard pilot duty

DC

Q600

Q600

Q600

Summary of Contents for J7KNA -

Page 1: ...AC24V 50 60Hz 48 AC48V 50Hz 60 AC60V 50Hz 110 AC110 115V 50Hz AC120 125V 60Hz 180 AC180 210V 50Hz AC200 240V 60Hz 230 AC220 230V 50Hz AC240V 60Hz 240 AC230V 240V 50Hz 400 AC380 400V 50Hz AC440V 60Hz...

Page 2: ...4 4 9 20 J7TKN A J7KNA 09 4 10 0 19 Ratings Rated Current Aux Contacts Type Pack Weight AC2 AC3 AC3 AC1 380V 400V 415V kW 500V kW 660V 690V kW 400V A 690V A NO NC Suitable Overload Relay 1 1 For detai...

Page 3: ...A 11 1 1 1 1 Contacts according to DIN EN 50005 J73KN A 02 0 2 0 2 J73KN A 40 4 0 4 0 J73KN A 22 2 2 2 2 J73KN A 04 0 4 0 4 Wiring Diagrams Auxiliary Contact Blocks Contactor with Auxiliary Contact Co...

Page 4: ...5 5 5 12 20 1 J7TKN A J7KNA 12 01 R 1 0 32 Ratings Rated Current Aux Contacts Type Pack Weight AC2 AC3 AC3 AC1 380V 400V 415V kW 500V kW 660V 690V kW 400V A 690V A NO NC Suitable Overload Relay 1 1 F...

Page 5: ...ide Distinc Number according to DIN EN 50012 Contactor K1 Type NO NC Contactor K2 Type NO NC 3 pole With Screw Terminals 01 J73KN AM 11V 1 1 J73KN AM 11X 1 1 Wiring Diagrams Contacts suitable for Elec...

Page 6: ...6 16 Rated operational power of three phase resistive loads 230V kW 6 3 6 3 50 60Hz cos 1 240V kW 6 7 6 7 400V kW 11 11 415V kW 11 5 11 5 Minimum cross section of conductor at load with Ie Ith mm 2 5...

Page 7: ...0 Short circuit protection for contactors without thermal overload relay Coordination type 1 according to IEC 947 4 1 Contact welding without hazard of persons max fuse size gL gG A 40 40 Coordination...

Page 8: ...0 15 0 25 Resistance to shock according to IEC 68 2 27 Shock time 20ms sine wave AC operated NO g 5 5 NC g 5 5 DC operated NO g 8 8 NC g 6 6 1 Suitable at 690V for earthed neutral systems overvoltage...

Page 9: ...0 4 0 4 0 4 220V A 0 1 0 1 0 1 Maximum ambient temperature Operation open C 40 to 60 90 3 enclosed C 40 to 40 Storage C 40 to 90 Short circuit protection short circuit current 1kA contact welding not...

Page 10: ...e when suppressor units for voltage peak protection are used Varistor RC units Diode units Mini Motor Contactors Data according to IEC 947 5 1 VDE 0660 EN 60947 5 1 Auxiliary Contacts Type J7KNA 09 J7...

Page 11: ...ontactor J7KNA 11 Dimensions AC and DC operated with screw terminals Auxiliary Contact Blocks J7KNA 09 J7KNA 12 J73KN A Reversing Contactors J7KNA 09 01 R J7KNA 12 01 R J7KNA 09 01 R J7TKN A J7KNA 12...

Page 12: ...rest of product improvement specifications are subject to change without notice ALL DIMENSIONS SHOWN ARE IN MILLIMETERS To convert millimeters into inches multiply by 0 03937 To convert grams into oun...