103
DSR Message and Response
Chapter 7-4
Response
Normal
Error
7-4-2
Data Write/Broadcast Data Write (Function Code: 10 Hex)
Settings and Response
• To write data to the Inverter, such as control I/O and parameter set value
data, issue the following DSR message.
• Consecutive data of a maximum of 16 words (32 bytes for 16 registers)
can be written per DSR message.
• The register number is allocated to each function item, such as control I/O
and parameter functions. The register number of each parameter is
indicated wherever the parameter is explained in this manual and in
Section 10 List of Parameters. For register numbers other than those of
parameters, refer to
7-7 Register Number Allocations in Detail
Note
1.
A parameter corresponds to one register (one word), so the “number of
registers of write data” indicates the number of parameters to be written
(i.e., the number of consecutive registers beginning with the first register
number).
2.
The “number of bytes of attached data” indicates the number of bytes of
data written to the registers attached from that point onwards. The number
of registers must equal the number of bytes divided by two.
Byte No.
Data
Data example
(Hex)
1 Slave
address
02
2 Function
code
03
3
Number of bytes of attached data
08
4
Data in register No. 0020
MS B
00
5
LSB 65
6
Data in register No. 0021
MSB
00
7
LSB 00
8
Data in register No. 0022
MSB
00
9
LSB 00
10
Data in register No. 0023
MSB
01
11
LSB F4
12 CRC-16
check
AF
13
82
Byte No.
Data
Data example
(Hex)
1 Slave
address
02
2 Function
code
83
3 Error
code
03
4 CRC-16
check
F1
5
31
Summary of Contents for J7 series
Page 12: ...XII...
Page 15: ...1 CHAPTER 1 Overview 1 1 Function 2 1 2 Nomenclature 3...
Page 54: ...40 Outline of Operation Chapter 3 2...
Page 102: ...88 Other Functions Chapter 6 7...
Page 158: ...144 Option Specifications Chapter 9 3...
Page 159: ...145 CHAPTER 10 List of Parameters List of Parameters 146...
Page 172: ...158 List of Parameters Chapter 10...
Page 173: ...159 CHAPTER 11 Using the Inverter for a Motor Using the Inverter for a Motor 160...