H7CC-A

@

6

Tachometer Function Ratings

*

An input OFF time of at least 20 ms is required.

Characteristics

*

Refer to the Life-test Curve.

Life-test Curve (Reference Values)

Model

Item

H7CC-A8

@

H7CC-A11

@

H7CC-A

@

H7CC-AW

@

/AU

@

Input mode

No 
tachometer 
functionality 

Selectable from 1 inputs, independent measurements for 2 inputs, differential input for 2 inputs, absolute ratio for 2 inputs, 
and error ratio for 2 inputs.

Pulse measurement 
method

Periodic measurement

Pulse width measurement

Maximum counting 
speed

30 Hz

(minimum pulse width: 16.7 ms)

1-input mode: 
10 kHz 

(minimum pulse width: 0.05 ms)

Other modes: 
5 kHz 

(minimum pulse width: 0.1 ms)

30 Hz

(minimum pulse width: 16.7 ms)

1-input mode: 
10 kHz 

(minimum pulse width: 0.05 ms)

Other modes: 
5 kHz 

(minimum pulse width: 0.1 ms)

Minimum input 
signal width

---

---

30 ms 

*

1-input mode: 0.2 ms
Other modes: 0.4 ms*

Measuring ranges

0.001 to 30.00 Hz

1-input mode: 0.001 to 10 kHz, 
Other modes: 0.01 to 5 kHz 

0.030 to 999999 s

1-input mode: 0.0002 to 999999 s
Other modes: 0.0004 to 999999 s

Sampling period

200 ms min. 

200 ms min. or continuous 
selectable (minimum interval of 
10 ms)

Continuous (minimum interval of 10 ms)

Measuring accuracy

±

0.1% FS 

±

1 digit max. (at 23 

±

5

°

C)

Output mode

Input mode: 
Not 2-input independent measurement: HI-LO, AREA, HI-HI, LO-LO 
2-input independent measurement: HI-HI, LO-LO 

Auto-zero time

0.1 to 999.9s

Startup time

0.0 to 99.9s

Averaging 

Simple averaging/moving averaging selectable, Processing: OFF, 2, 4, 8, or 16 times

Hold input

Minimum input signal width: 20 ms

Insulation resistance

100 M

Ω

 min. (at 500 VDC) between current-carrying terminals and exposed non-current-carrying metal parts, 

and between non-continuous contacts

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and non-current-carrying metal parts
2,000 VAC, 50/60 Hz for 1 min between power supply and input circuit for all models except H7CC-

@

D

@

 (1,500 VAC 

for 24 VAC/12 to 48 VDC)
1,500 VAC (for H7CC-

@

SD

@

), 50/60 Hz for 1 min between control output, power supply, and input circuit (2,000 VAC 

for models other than H7CC-

@

SD

@

)

1,000 VAC, 50/60 Hz for 1 min between non-continuous contacts

Impulse withstand voltage

6.0 kV between power terminals (1.0 kV for models with 24 VAC/12 to 48 VDC)
6.0 kV between current-carrying terminals and exposed non-current-carrying metal parts (1.5 kV for models with 24 
VAC/12 to 48 VDC)

Static immunity

Malfunction: 8 kV
Destruction: 15 kV 

Vibration resistance

Destruction

10 to 55 Hz with 0.75-mm single amplitude each in three directions for 2 h each

Malfunction

10 to 55 Hz with 0.35-mm single amplitude each in three directions for 10 min each

Shock resistance

Destruction

300 m/s

2

 each in three directions

Malfunction

100 m/s

2

 each in three directions

Life expectancy

Mechanical: 10,000,000 operations min. 
Electrical: 100,000 operations min. (3 A at 250 VAC, resistive load, ambient temperature condition: 23

°

C) 

*

Weight

Approx. 120 g (Counter only)

Resistive load

Inductive load

1,000

700

500

300

100

70

50

Load current (A)

0

1

2

3

4

30 VDC (cos

φ

=1)

250 VAC (cos

φ

=1)

No

. of oper

ations (

×

10

3

)

1,000

700

500

300

100

70

50

0

1

2

3

4

30 VDC (L/R=7 ms)

Load current (A)

250 VAC (cos

φ

=1)

No

. of oper

ations (

×

10

3

)

A current of 0.15 A max. can be switched at 125 
VDC (cos

φ

=1) and current of 0.1 A max. can be 

switched if L/R=7 ms. In both cases, a life of 100,000 
operations can be expected.

Summary of Contents for H7CC Series

Page 1: ...t value which makes it easy to understand the status Shortened Body The body depth of all models with screw terminals has been reduced to 59 mm which contributes to thinner control panels Safety and R...

Page 2: ...emory Backup Function Conversion from the H7CN H7AN is supported by enabling the setting of the present value and the output state memory backup H7AN Compatibility Function Conversion from the H7AN is...

Page 3: ...r Batch counter Dual counter Twin counter Tachometer 2 stage Contact output SPST SPDT 100 to 240 VAC H7CC AW Transistor output DSPT H7CC AWS Contact output SPST SPDT 24 VAC 12 to 48 VDC H7CC AWD Trans...

Page 4: ...s 12 Model Classification Connectable Counter Tachometers Remarks Page P2CF 08 Front connecting Socket H7CC 8 13 P2CF 08 E Front connecting Socket Finger safe Type Round crimp terminals cannot be used...

Page 5: ...puts UP DOWN D command input UP DOWN E individual inputs UP DOWN E quadrature inputs Output mode N F C R K 1 P Q A K 2 D and L N F C R K 1 P Q A K 2 D L and H One shot out put time 0 01 to 99 99 s Res...

Page 6: ...arrying terminals and exposed non current carrying metal parts and between non continuous contacts Dielectric strength 2 000 VAC 50 60 Hz for 1 min between current carrying metal parts and non current...

Page 7: ...lue Counting for CP2 input cannot be performed while the reset 2 input is ON Twin counter Resets the CP2 present value Minimum reset signal width Output delay time Relay output Transistor output 1 ms...

Page 8: ...9 10 11 1 2 3 4 5 Reset CP1 CP2 OUT Total Reset 0 V Internal circuit 12 DCV External power supply Sensor 6 7 8 9 10 11 1 2 3 4 5 OUT Reset CP1 CP2 Total Reset 0 V Internal circuit 12 DCV Sensor Exter...

Page 9: ...10 H7CC A 0 V for inputs Reset reset 1 input CP2 input CP1 input Total reset reset 2 input Note Operates with relay ON 6 7 8 9 3 7 5 6 10 H7CC A H7CC A11 4 H7CC A8 1 3 5 4 0 V for inputs Reset reset 1...

Page 10: ...m right to left 1 2 Display Section 3 Reset Indicator yellow 1 Key Protect Indicator yellow 2 Control Output Indicator yellow 4 Total Count Indicator 6 Set Value 1 2 Stage Indicator 8 Set value Sub di...

Page 11: ...ting panel thickness should be 1 to 5 mm 2 To allow easier operation it is recommended that Adapters be mounted so that the gap between sides with hooks is at least 15 mm i e with the panel cutouts se...

Page 12: ...sistive conforming to IP 6 and so even if drops of water penetrate the gaps between the keys there will be no adverse effect on internal circuits If however there is a possibility of oil being present...

Page 13: ...ns Terminal arrangement and internal connections P3GA 11 Bottom View P3GA 08 BOTTOM VIEW 4 70 max 50 max Two 4 5 dia holes Eleven M3 5 7 5 sems screws 7 8 31 2 max 4 5 3 35 4 8 7 6 5 10 11 1 2 9 3 4 4...

Page 14: ...ensions Y92A 48G Y92A 48G UP P C 34 Twelve 6 4 dia holes 47 7 47 7 48 48 27 6 24 6 16 5 47 4 1 35 0 3 7 3 0 15 27 0 15 4 5 15 25 25 10 15 5 10 25 25 1 000 500 The values shown in parentheses are for t...

Page 15: ...b The 5ub parameter is normally not displayed You must set the outm parameter shown below in advance to 6 k 2 d l or h to display it 3 When Using Dual Counter Operation Function setting mode Use UP1 U...

Page 16: ...time OTM1 0 01 s 99 99 s Outputs held Note Displayed only when the output mode is C R K 1 P Q A or K 2 When using as a batch counter One shot output 2 time OTM2 Set the counting speed using the UP1 Ke...

Page 17: ...n ver Output 1 OUT1 inversion OT1I Output 2 OUT2 inversion OT2I Normally Close Normally Open Normally Close Normally Open Normally Close Normally Open Output inversion OT I 99 9 years 10 0 years 0 0 y...

Page 18: ...uts together If contacts are used for input signals set the counting speed to 30 Hz Processing to eliminate chattering is performed for this setting Reset Input Signal Width iflt Set the reset input s...

Page 19: ...applicable to only H7CC W U otst Set the allocation of outputs 1 and 2 OUT1 and OUT2 If output allocation is OFF output 1 OUT1 is allocated to terminals 12 and 13 and output 2 OUT2 is allocated to te...

Page 20: ...n the value changes from 999999 to 0 If the counter continues thereafter the status indicator will light up according to the present value Example 2 When decrementing input is performed The status ind...

Page 21: ...present total count value Present Value Set Value Same as 1 stage preset counter Batch Count Value Shows the number of times the count has been completed for the present value Batch Count Set Value S...

Page 22: ...ibit gate input must be greater than the minimum signal width See note 2 CP1 Prohibit gate input CP2 Count input must be greater than the minimum signal width See note 2 CP1 Prohibit gate input CP2 Co...

Page 23: ...note 2 UP DOWN C Quadrature Input Mode UP DOWN D Command Input Mode must be at least 1 2 the minimum signal width See note 2 must be at least 1 2 the minimum signal width See note 2 UP DOWN E Individu...

Page 24: ...e display continues to increase decrease The outputs are held until reset reset 1 is input UP DOWN A B C UP DOWN D E F Self holding output Self holding output One shot output from OUT1 One shot output...

Page 25: ...operation OUT1 self holding output turns OFF after the OUT2 one shot output time The OUT1 one shot output time is independent of OUT2 UP DOWN A B C UP DOWN D E F Self holding output Self holding outp...

Page 26: ...output turns OFF after the OUT2 one shot output time The OUT1 one shot output time is independent of OUT2 UP DOWN A B C UP DOWN D E F Self holding output Self holding output One shot output from OUT1...

Page 27: ...tart status after the one shot output time has elapsed The outputs repeat one shot operation OUT1 self holding output turns OFF after the OUT2 one shot output time The OUT1 one shot output time is ind...

Page 28: ...se decrease until the overflow or underflow value is reached One shot output only D The display continues to increase decrease until the overflow or underflow value is reached The outputs are ON while...

Page 29: ...rned ON If reset operation is performed while the total count value is displayed the total count value is reset The present value is also reset at this time The counting range of the total counter is...

Page 30: ...Screen displayed in run mode Present value set value 1 2 Present value set value Total count value Present value set value Batch count value batch count set value Dual count value dual count set value...

Page 31: ...g mode the status indicator of the keys that can be set lights up Example In the case of the prescale value PSCL A value from 0 001 to 99 999 can be set and therefore the status indicator of the UP1 K...

Page 32: ...0 999999 999999 1 1 on off 19 99 0 00 ON on off kp 1 kp 2 kp 3 kp 4 kp 5 kp 6 kp 7 Set the output allocation using the UP1 Key DW1 Key From previous page To previous page Key protect level KYPT Set t...

Page 33: ...be set Note The monitor value is only displayed It cannot be set Note The monitor value is only displayed It cannot be set Note The monitor value is only displayed It cannot be set Pulse cycle measure...

Page 34: ...eater than this output will not turn ON Output will turn ON however if a present value overflow occurs FFFFFF Averaging Method avgt A simple average or moving average can be selected for the averaging...

Page 35: ...pulse width measurement With pulse cycle measurement the number of pulse cycles that occur in 1 s is measured With pulse width measurement the ON time for one pulse is measured An input OFF period of...

Page 36: ...ches 1 6 2 6 3 6 50 4 6 5 6 6 6 100 in accordance with the ratio of the measurement value to the comparison value If comparison value 1 2000 and comparison value 2 2300 have been set all status indica...

Page 37: ...comparison value 2 and output is made according to the selected output mode Displayed when the input mode is not 2 inputs Displayed for the 2 input input mode Peak bottom hold value The peak maximum a...

Page 38: ...surement value Comparison value 2 Measurement value Comparison value 2 or Measurement value Comparison value 1 OUT1 OUT2 Measurement value Upper limit Comparison value 2 Lower limit Comparison value 1...

Page 39: ...turn OFF and counting measuring stops 2 Setting changes made in configuration selection mode are enabled when the mode is changed to run mode If the configuration is changed the set value or set valu...

Page 40: ...key protect switch is ON Changing mode to configuration selection mode or function setting mode Level Description Details Changing modes Switching display during operation Reset operation Up Down Key...

Page 41: ...et value or above an RPLC replacement time error can be displayed on the Timer Self diagnostic Function The following displays will appear if an error occurs 1 This includes times when the life of the...

Page 42: ...5 Hz min Averaging not used 200 ms Averaging used 200 multiplied by the averaging setting ms Input pulse of less than 5 Hz Averaging not used Two times the maximum input pulse cycle Using averaging T...

Page 43: ...Shock re sistance Destruction 300m s2 each in three directions three cycles Malfunction 100m s2 each in three directions three cycles Life expectancy Mechanical 10 000 000 operations min Electrical 10...

Page 44: ...0 V Sensor 12 VDC External power supply Internal circuit Count Hold Hold Hold H7CC R11 H7CC R11D 6 7 8 9 10 11 1 2 3 4 5 OUT1 OUT2 0 V Sensor 12 VDC External power supply Internal circuit Internal ci...

Page 45: ...ote Operates when the transistor turns ON No contact input Short circuit level Transistor ON Residual voltage 3 V max Impedance when ON 1 k max The leakage current is approx 12 mA when the impedance i...

Page 46: ...he keys are pressed simultaneously all status indicators start blinking The hold operation is disabled if the keys are released within 1 second To perform the hold operation firmly press and hold both...

Page 47: ...surfaces without hooks are on the sides of the Timers If Counters Tachometers are mounted side by side however water resistance will be lost 60 min 60 min 15 min 45 0 6 0 45 0 6 0 n side by side mount...

Page 48: ...ming to IP 6 and so even if drops of water penetrate the gaps between the keys there will be no adverse effect on internal circuits If however there is a possibility of oil being present on the operat...

Page 49: ...ext page From next page Prescale value PSCL Parameters are set with the operation keys on the front panel Change to Function Setting Mode LO HI LO HI 30 Hz 10 kHz The characters displayed in reverse v...

Page 50: ...idual UP1 to UP3 Keys DW1 to DW3 Keys Set the NPN PNP input mode using the UP1 Key DW1 Key NPN PNP input mode IMOD Peak bottom hold enabled DHLD Enable or disable the peak bottom hold using the UP1 Ke...

Page 51: ...1000 times Output 1 OUT1 inversion OT1I Output 2 OUT2 inversion OT2I 99 9 years 10 0 years 0 0 year Count status display Cumulative run time OT A alarm set value Cumulative run time OT C monitor value...

Page 52: ...asured when the input pulse is received The output will change however when the comparison value is exceeded even if averaging is enabled NPN PNP Input Mode imod Select either NPN input no voltage inp...

Page 53: ...1a on2a The output ON count for notifying the replacement time can be set For details refer to page 57 Output ON Count Monitor Value on c The monitor value is only displayed It cannot be set The outpu...

Page 54: ...1 6 2 6 3 6 50 4 6 5 6 6 6 100 in accordance with the ratio of the measurement value to the comparison value If comparison value 1 2000 and comparison value 2 2300 have been set all status indicators...

Page 55: ...omparison value comparison value 1 and comparison value 2 and an output is made according to the selected output mode 1 Peak bottom hold enabled Peak bottom hold value The peak maximum and bottom mini...

Page 56: ...tor is lit when the key protect switch is ON Changing mode to function setting mode Level Meaning Details Changing mode Switching display during operation Hold operation Up Down Keys KP 1 default sett...

Page 57: ...on1a on2a Set the alarm value for the output ON count The limit can be set between 0 1000 0 times and 9999 1000 9 999 000 times Only the underlined values are set The alarm will be disabled if 0 is s...

Page 58: ...lue Upper limit Measurement value OUT Measurement value Comparison value Lower limit Outputmode setting Operation Upper and lower limit ON condition Measurement value Comparison value 1 or Measurement...

Page 59: ...is ON Note The output will maintain the current status when hold operation is performed Example The H7CC R11W does not have a hold input Output mode setting Operation Lower limit OUT Display value Hol...

Page 60: ...ue Measuring ranges 0 01 to 0 1 s AMD S 1 0 1 to 1 s AMD S 2 1 to 10 s AMD S 3 Output mode Rotation increase detection AMD SU Rotation decrease detection AMD SL Average processing None Input mode Volt...

Page 61: ...beyond its life expectancy its contacts may become fused or there may be a risk of fire Also be sure that the load current does not exceed the rated load current and when using a heater be sure to use...

Page 62: ...Install a switch or circuit breaker that allows the operator to immediately turn OFF the power and label it to clearly indicate its function When the Counter is operated with no voltage input NPN inpu...

Page 63: ...all the product close contact with the heating element Non volatile memory is used as backup memory when the power is interrupted The write life of the non volatile memory is 100 000 writes The non vo...

Page 64: ...ARTERS Chicago IL USA 847 843 7900 800 556 6766 automation omron com Controllers I O Machine Automation Controllers MAC Motion Controllers Programmable Logic Controllers PLC Temperature Controllers Re...

Reviews: