Solid-state Timer

 

H3BA-N

Characteristics

Note:

For setting the time-limit of the Timer to a cycle of less than 3 seconds or applying the forced reset, use the H3BA-N in mode D (signal OFF-
delay).

Nomenclature

H3BA-N

H3BA-N8H

Item

H3BA-N

H3BA-N8H

Accuracy of operating time

±

0.3% FS max. (

±

0.3%

±

10 ms in a range of 1.2 s)

Setting error

±

5% FS 

±

0.05 s max.

Reset time

Min. power-opening time:  0.1 s max.
Min. pulse-input time: 

50 ms

Influence of voltage

±

0.5% FS max. (

±

0.5%

±

10 ms in a range of 1.2 s)

Influence of temperature

±

2% FS max. (

±

2%

±

10 ms in a range of 1.2 s)

Insulation resistance

100 M

 min. (at 500 VDC)

Dielectric strength

2,000 VAC, 50/60 Hz for 1 min between current-carrying metal parts and exposed non-current-carrying metal 
parts
2,000 VAC, 50/60 Hz for 1 min between control output terminals and operating circuit
1,000 VAC, 50/60 Hz for 1 min between contacts not located next to each other (750 VAC for H3BA-N8H)

Impulse withstand voltage

1 kV (between power terminals)
2 kV (between current-carrying terminal and exposed non-current-carrying metal parts, 
1.5 kV for 24-VDC models)

Noise immunity

AC models: 

±

1.5 kV (between power terminals), and 

±

600 V (between input terminals), 

square-wave noise by noise simulator (pulse width: 100 ns/1 

µ

s, 1-ns rise)

DC models: 

±

480 V (between power terminals), and 

±

600 V (between input terminals), 

square-wave noise by noise simulator (pulse width: 100 ns/1 

µ

s, 1-ns rise)

Static immunity

Malfunction: 4 kV

Destruction: 8 kV

Vibration resistance

Destruction: 10 to 55 Hz with 0.75-mm single amplitude each in three directions
Malfunction: 10 to 55 Hz with 0.5-mm single amplitude each in three directions

Shock resistance

Destruction: 1,000 m/s

2

 (approx. 100G) each in three directions

Malfunction: 100 m/s

2

 (approx. 10G) each in three directions

Ambient temperature

Operating: –10

°

C to 55

°

C (with no icing)

Storage: –25

°

C to 65

°

C (with no icing)

Ambient humidity

Operating:  35% to 85%

Life expectancy

Mechanical: 20 million operations min. (under no load 

at 1,800 operations/h)

Electrical: 

100,000 operations min. (5 A at 250 VAC, 
resistive load at 1,800 operations/h)

Mechanical: 10 million operations min. (under no 

load at 1,800 operations/h)

Electrical: 

100,000 operations min. (5 A at 250 
VAC, resistive load at 360 operations/h)

Case color

Light gray (Munsell 5Y7/1)

Enclosure ratings

IEC: IP40 (panel surface)

Weight

Approx. 95 g

H3BA

UP

PW

MODE

A

sec

0

1

2

3

0.5

2.5

1

.

5

Power Indicator (Green): 
Lit when Timer operates.

Operating Mode Display Window

Operating Mode Selector: 
Select a mode from 
A, B, B2, C, D, and E 

Scale Range Display 
Windows

Time Unit Selector 
Select a unit from 
sec, min, hrs, and 10h.

Time setting knob (set time)

Output Indicator (Orange): 

Lit when Timer outputs.

Time Range Selector: 

Select one from 

1.2, 3, 12, and 30.

H3BA

UP

PW

MODE

A

sec

0

1

2

3

0.5

2.5

1

.

5

Power Indicator (Green): 
Lit when Timer operates.

Output Type Display Window

Output Type Selector: 
Select a type from A 
and H
A: Time-limit DPDT 
    (default setting)
H: Time-limit SPDT and 
    instantaneous SPDT

Scale Range Display 
Windows

Time Unit Selector 
Select a unit from sec, 
min, hrs, and 10 h.

Time setting knob (set time)

Output Indicator (Orange): 

Lit when Timer outputs.

Time Range Selector: 

Select one from 

1.2, 3, 12, and 30.

Summary of Contents for H3BA-N

Page 1: ...forms to LR and approved by UL and CSA RC Broad Line up of H3B N Series H3B N Multi functional Timer H3BA N H3BA N8H Twin Timer Star delta Timer H3BG N8 H3BG N8H Power OFF delay Timer H3BH N8 H3BH N H3BG N H3BF N H3BA N Note Refer to the H3BF N BG N BH N Datasheet Cat No L094 E1 1 for details 11 pin model 8 pin with instantaneous contact output and time limit output 8 pin with instantaneous contac...

Page 2: ...ontact output Time limit SPDT and switchable SPDT time limit instantaneous 110 VAC 50 60 Hz H3BA N8H 110 VAC 220 VAC 50 60 Hz H3BA N8H 220 VAC 24 VDC H3BA N8H 24 VDC Name specifications Models Flush Mounting Adapters Y92F 30 Y92F 70 Y92F 71 Mounting Tracks 50 cm l 7 3 mm t PFP 50N 1 m l 7 3 mm t PFP 100N 1 m l 16 mm t PFP 100N2 End Plate PFP M Spacer PFP S Protective Cover Y92A 48B Track Mounting ...

Page 3: ...ntaneous Mounting method DIN track mounting surface mounting and flush mounting Approved standards UL508 CSA C22 2 No 14 Conforms to LR currently under application and approval is expected by the end of Feb 2006 Time unit s sec min h hrs 10 h 10 h Setting 1 2 0 05 to 1 2 0 12 to 1 2 1 2 to 12 3 0 3 to 3 3 to 30 12 1 2 to 12 12 to 120 30 3 to 30 30 to 300 Item H3BA N H3BA N8H Rated supply voltage S...

Page 4: ...th 0 75 mm single amplitude each in three directions Malfunction 10 to 55 Hz with 0 5 mm single amplitude each in three directions Shock resistance Destruction 1 000 m s2 approx 100G each in three directions Malfunction 100 m s2 approx 10G each in three directions Ambient temperature Operating 10 C to 55 C with no icing Storage 25 C to 65 C with no icing Ambient humidity Operating 35 to 85 Life ex...

Page 5: ...ut circuit AC DC input Power supply circuit Oscillation circuit Time range unit selectors Counting circuit Output circuit Output type selector Indicator circuit Power ON indicator Output ON indicator H3BA N8H Inputs Start Starts time measurement Reset Interrupts time measurement and resets time measurement value No time measurement is made and control output is OFF while the reset input is ON Gate...

Page 6: ...ht part within the plastic frame of the time setting knob Setting of Time Use the time setting knob to set the desired time Using the Setting Ring Setting a Specific Time Mount the Panel Cover on the Timer set the desired time with the time setting knob and place Time Setting Ring A onto the time setting knob so that the time setting notch of Time Setting Ring A is in the center of the reset lock ...

Page 7: ...relay NO 1 and 3 11 and 9 and output indicator Power indicator t t Basic operation Power Start Output t t t t t t t t t a t Power 2 and 10 Start 2 and 6 Reset 2 and 7 Output relay NC 1 and 4 11 and 8 Output relay NO 1 and 3 11 and 9 and output indicator Power indicator Basic operation Power Start Output t t t t t t t t t a t Power 2 and 10 Start 2 and 6 Reset 2 and 7 Output relay 1 and 4 11 and 8 ...

Page 8: ... t t a t a t Power 2 and 10 Start 2 and 6 Reset 2 and 7 Output relay 1 and 4 11 and 8 NC Output relay NO Output indicator 1 and 3 11 and 9 Power indicator Power Start Output t Basic operation t t t t t a t a Power 2 and 10 Start 2 and 6 Reset 2 and 7 Output relay 1 and 4 11 and 8 NC Output relay NO Output indicator 1 and 3 11 and 9 Power indicator Power Start Gate Reset Output relay ON OFF ON OFF ...

Page 9: ... and 5 1 and 4 Output relay NO 8 and 6 1 and 3 and output indicator Power indicator t t Rt Rt t a Operating mode Timing chart H ON delay with instantaneous output contact Power Output t Basic operation Power 2 and 7 Output relay 8 and 5 NC Power indicator Instantaneous 1 and 4 output relay NC t t Rt Rt t a Instantaneous 1 and 3 output relay NO Output relay 8 and 6 NO output indicator ...

Page 10: ...Y92F 30 Flush Mounting Adapter 48 48 11 pins 15 6 63 7 0 7 39 dia 44 8 44 8 78 13 6 PW UP 48 48 8 pins 15 6 63 7 0 7 39 dia 44 8 44 8 78 13 6 PW UP Time setting ring Panel cover 50 16 5 50 42 dia Panel Cutout Note The mounting panel thickness should be 1 to 5 mm 0 5 R max 45 0 6 0 N 45 0 6 0 58 52 42 48 Panel P3G Back Connecting Socket sold separately PW UP ...

Page 11: ...nce value Flush Mounting Panel 88 58 45 0 15 45 0 15 Panel Cutout Adapter mounting hole Two 4 5 dia 52 to 53 76 0 2 65 to 66 R0 5 max PW UP Panel 43 0 2 58 50 0 2 0 56 68 R0 5 max 45 0 5 0 55 0 5 0 Note The mounting panel thickness should be 1 to 3 2 mm 45 0 2 PW UP 112 2 109 9 2 3 H3BA N P2CF 11 H3BA N8H P2CF 08 101 3 99 2 3 H3BA N Adapter Y92F 30 P3GA 11 91 4 15 H3BA N8H Y92F 30 P3G 08 15 86 4 ...

Page 12: ...M4 40 0 2 Eight M3 5 7 5 sems Two 4 5 dia holes 70 max 50 max 20 3 max 7 8 3 4 5 35 4 4 Two 4 5 dia holes Eleven M3 5 7 5 sems 70 max 50 max 31 2 max 7 8 3 4 5 35 4 4 P3G 08 P3GA 11 Terminal Arrangement Internal Connections Bottom View 45 27 dia 45 4 9 17 45 45 27 dia 25 6 4 5 16 3 6 2 PFP 100N PFP 50N PFP 100N2 L Length 1 m PFP 100N 50 cm PFP 50N 1 m PFP 100N2 4 5 15 25 25 25 25 10 10 L 7 3 0 15 ...

Page 13: ...n three colors Use the most suitable type of Panel Cover with the design of the scaling plate according to the application When setting a given time for the Timer use of the Y92S 27 or Y92S 28 Time Setting Ring facilitates the time setting operation and minimizes possible setting errors by operators The Time Setting Ring and Panel Cover should be used as a pair Hold down Clip PFP M 50 11 5 M4 8 pa...

Page 14: ...al timers are shown as follows The contact symbol of the H3BA N is ex pressed as follows because of its multiple op erating modes The instantaneous contacts of conventional timers are shown as follows Power supply MODE See note A H Note The output contact can be set to either instantaneous or time limit contact using the output type selector located at the upper right corner of the front panel ...

Page 15: ...hen OFF 200 kΩ min Use contacts which can adequately switch 0 1 mA at 5 V No contact Input Connection to NPN open collector output sensor Contact Input No contact Input Connection to a voltage output sensor 12 to 24 VDC sensor power supply Sensor Timer Start reset gate Input 0 V No 2 pin Operates with transistor ON DC power supply Timer Start reset gate Input 0 V No 2 pin Operates with relay ON 12...

Page 16: ...pplied the internal components may be damaged The internal element varistor will be damaged if a voltage of higher than 100 VAC is applied to the 24 VDC line Connect the power supply voltage through a relay or switch in such a way that the voltage reaches a fixed value immediately or the Timer may not be reset or a timer error could result A DC power supply can be connected if its ripple factor is...

Page 17: ... Timer in order to prevent the Timer from malfunction and damage A diode is an example of a surge absorbing element for DC circuits and a surge absorber is an example of a surge absorbing element for AC circuits Do not leave the Timer in time up condition for a month or longer in places with high temperatures otherwise the internal parts such as an electrolytic capacitor of the Timer may be damage...

Page 18: ...ia max multi conductor cable or 3 dia max insulated stranded wire for wiring When the Y92F 40 Y92F 70 or Y92F 71 Flush Mounting Adapter is used just insert the Timer into the square panel hole If the panel coating is too thick and the hooks do not click spread open the hooks appropriately to the left and right after inserting the Timer to the hole Dismounting Surface Mounting with P2CF Panel Mount...

Page 19: ...Solid state Timer H3BA N 19 ...

Page 20: ...LE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards codes or regulations that apply to ...

Reviews: