24-hour/Weekly Time Switch

H2F

Up to 96 ON/OFF Cycles from DIN-sized 
(72 x 72 mm) Timer

• Easy setting with color-coded programming tabs.

• Choose from 24-hour or 1-week models with either SPST-NO or 

SPDT control outputs.

• Minute dial assures accurate settings.

• Models with memory protection available.

• Control outputs can be manually turned ON/OFF.

• Designed for surface, flush, or track mounting.

Model Number Structure

Model Number Legend

1. Operation cycle

D:

24-hour

W:

1-week

2. Motor type

None: Synchronous motor

M:

Quartz motor

3. Mounting method

None: Flush mounting

F:

Surface mounting, DIN track mounting

4. Output type

None: SPST-NO

C:

SPDT

1 2 3 4

H2F-

@@@@

Summary of Contents for H2F -

Page 1: ...ntrol outputs Minute dial assures accurate settings Models with memory protection available Control outputs can be manually turned ON OFF Designed for surface flush or track mounting Model Number Structure Model Number Legend 1 Operation cycle D 24 hour W 1 week 2 Motor type None Synchronous motor M Quartz motor 3 Mounting method None Flush mounting F Surface mounting DIN track mounting 4 Output t...

Page 2: ...tz motor with memory protection Flush SPST NO H2F D H2F DM H2F WM SPDT H2F DC H2F DMC H2F WMC Surface track SPST NO H2F DF H2F DMF H2F WMF SPDT H2F DFC H2F DMFC H2F WMFC Extra Programming Tabs 1 pair for each ON OFF See note 1 Y92S 21 Rechargeable Battery See note 2 Y92S 42 Operation period Minimum division Minimum set time Maximum set time 24 hour 15 min 15 min 23 h 45 min 1 week 1 h 2 h 166 h Op...

Page 3: ...ax Memory protection against power failure 180 h min See note 3 Insulation resistance 100 MΩ min at 500 VDC Dielectric strength 2 000 VAC 50 60 Hz for 1 min between current carrying terminals and non current carrying metal parts 1 000 VAC 50 60 Hz for 1 min between non continuous contacts Vibration resistance Destruction 16 7 Hz 2 mm single amplitude Malfunction 10 to 55 Hz 0 25 mm single amplitud...

Page 4: ...to the load 2 Do not exceed the following torque when tightening the screws Specified torque 0 8 N m Maximum torque 0 98 N m 3 When connecting leads to the terminal block use the same wire size for all leads If different wire sizes are used the thinner leads may come off during operation 4 Recommended lead wires AWG18 to AWG24 cross section 0 205 to 0 823 mm2 solid or twisted wire 5 When using cri...

Page 5: ...ated Mounting Dimensions Surface Mounting H2F DF DMF WMF Track Mounting H2F DFC DMFC WMFC Mounting Holes M3 5 6 29 Two M3 holes Screw size M3 x 45 included Flush Mounting H2F D DM WM DC DMC WMC Panel Cutout Recommended panel thickness 1 to 3 2 mm Note The mounting adapter and screws are included 65 5 ...

Page 6: ...Time Setting To set the time turn the center knob clockwise to the correct time Turning it counterclockwise or turning it with your fingers hooked on the setting bracket may cause a malfunction With 24 hour models set the hour to the arrow on the upper left cor ner of the front panel and the minute to the arrow on the center knob With 1 week models set the day of the week to the arrow on the upper...

Page 7: ...F Be sure to load the Battery before using the H2F If the Battery is not loaded the H2F will not work properly Be sure to load the Battery with the correct polarity The polarity is indicated in the battery box After loading the Battery be sure to place the cover on the battery box The Battery is fully charged before shipment The Battery may lose its charge while the Battery is stored Therefore the...

Page 8: ...of the terminals or the back panel while power is being supplied Doing so may result in electric shock Be sure to mount the terminal cover after wiring Before changing times or other settings while power is being supplied either turn OFF the power on the load side or set the output ON OFF switch to OFF and confirm the safety of the system Unexpected operation may occasionally result Tighten the te...