5-2 Settings
Com
m
u
n
ication
Unit
5
5-
2-5 Un
it F
unct
ions
The following table lists the EtherCAT Communication Unit’s functions.
Functionality to registers the configuration of the connected SmartSlice I/O Units in a table within the
Communication Unit. This table can then be used to compare the registered table with the information
of the Master.
ON (during power up) = Compare
The registered I/O table will be compared automatically with the actual configuration each time the
power of the EtherCAT Communication Unit is turned ON.
The red blinking TS LED indicates a verification error. A verification error will occur if a registered I/O
Unit is not available or an unregistered I/O Unit is detected.
The verification error will prevent the Communication Unit to change from init to pre-operational.
For communication state details refer to "2-5 Communication State Transitions" in page 2 - 7.
Reference
A mismatch (verification error) with the registered table is indicated at the EtherCAT
Communication Unit’s TS indicator (flashing red).
5-2-5
Unit Functions
Function name
Summary
Setting method
Table
reg
i
s
tration
Reads the configuration of the SmartSlice I/O Units
connected to the Communication Unit and registers that
information in a table
More info: 5-2-6 Table Registration Function (1 | REGS)
DIP switch ‘1 REGS’
Back
up
Records the parameter data of all connected I/O Units in the
Communication Unit
More info: 5-2-7 Backup Function (4 | BACK)
DIP switch ‘4 BACK’
A
utomatic
D
ownload and
R
estore
Automatically downloads the backed-up parameter data to
the appropriate Unit
More info: 5-2-8 Automatic Device Restore Function (3 |
ADR)
DIP switch ‘3 ADR’
5-2-6
Table Registration Function (1 | REGS)
There are the same number of
Units, but the I/O data size does
not match, so a verification error
occurs and this I/O Unit does not
participate in communications.
#1
#2
#3
#4
Pin 1 ON when power
was turned ON.
Registration table
The actual configuration is compared to the registered table.
Units that do not match the registered table do not participate
in I/O communications. I/O communications start with the other
I/O Units.
Four
contact
inputs
Four
contact
inputs
Two
relay
outputs
Two
relay
outputs
EtherCAT
Communications
Unit
Summary of Contents for GRT1-ECT SmartSlice
Page 3: ...GRT1 series EtherCAT Communication Unit Operation Manual Revised March 2012 ...
Page 18: ...15 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 30: ...1 EtherCAT Network 1 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 38: ...2 EtherCAT Communication details 2 8 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 52: ...4 GRT1 ECT Details 4 10 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 76: ...6 GRT1 ECT Troubleshooting 6 12 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 136: ...A4 Appendix Object Dictionary A4 16 GRT1 series EtherCAT Communication Unit Operation Manual ...
Page 140: ...Revision 2 GRT1 ECT series EtherCAT Slave Unit User s Manual ...