background image

G7SA

G7SA

137

Precautions

Safety Relays

A Safety Relay is a Relay with which a safety circuit can be config-
ured.

Wiring

Use one of the following wires to connect to the P7SA-10F/10F-
ND/14F/14F-ND.

Stranded wire:

0.75 to 1.5 mm

2

Solid wire:

1.0 to 1.5 mm

2

Tighten each screw of the P7SA-10F/10F-ND/14F/14F-ND to a
torque of 0.98 N 

S

 m securely.

Wire the terminals correctly with no mistakes in coil polarity, other-
wise the G7SA will not operate.

Cleaning

The G7SA is not of enclosed construction. Therefore, do not wash
the G7SA with water or detergent.

Forcibly Guided Contacts (from EN50205)

If an NO contact becomes welded, all NC contacts will maintain a
minimum distance of 0.5 mm when the coil is not energized. Like-
wise if an NC contact becomes welded, all NO contacts will maintain
a minimum distance of 0.5 mm when the coil is energized.

ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.

To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.