Precautions
Correct Use
Available Gases:
No corrosive or flammable gas can be used.
Filter the gas with an appropriate air filter so that the applied gas will
be free of moisture or oil.
Make sure that the pressure applied is within the rated range.
If the silicone diaphragm is damaged, the E8F will not operate prop-
erly. Do not insert a screwdriver or steel wire into the interior of the
pressure-sensitive parts through the pressure leading part.
The E8F has a display error of
±
3% FS
±
1 digit at the time of ON or
OFF point setting at room temperature. If a highly precise pressure
setting is required, use a manometer.
Nullify the ON/OFF output at the time of error detection.
If the use of the E8F requires the IP66 enclosure rating (e.g., wash-
ing the E8F with water), be sure to connect a standard silicone tube
to the atmosphere inlet. The silicone tube must have a 2-mm inner
diameter and 4-mm outer diameter.
Reset Time:
The E8F is ready to operate within 200 ms after the E8F is turned
ON.
Make sure that the Sensor is free from ultrasonic vibration when
mounting the E8F.
Others:
If no linear or error output is used, cut off the black and orange lead
wires and apply insulation tape to the lead wires so that they will not
come in contact with any other terminal.