![Omron E5EN Instruction Manual Download Page 1](http://html1.mh-extra.com/html/omron/e5en/e5en_instruction-manual_742651001.webp)
• Up and Down keys
Use the keys to change the values displayed on
the No.2 display.
Each press of
U
key increments or advances the
values displayed on the No.2 display.
Each press of
D
key decrements or returns the
values displayed on the No.2 display.
• Level key
Use this key to change levels:
• Press the key and the
M
key
together for at least 3 seconds to switch
to protect level.
Operation indicators
• SUB1: Auxiliary output 1 indicator
Lit when the function assigned to auxiliary
output 1 is ON.
• SUB2: Auxiliary output 2 indicator
Lit when the function assigned to auxiliary
output 2 is ON.
• SUB3: Auxiliary output 3 indicator
Lit when the function assigned to auxiliary
output 3 is ON.
• HA: Heater burnout alarm/Heater short
alarm/Heater overcurrent alarm indicator
Lit when a heater burnout alarm, heater
short alarm, or heater overcurrent alarm
has occurred.
• OUT1: Control output 1 indicator
Lit when control output 1 is ON and not
lit when it's OFF.
For a current output, lit except for a 0% output.
• OUT2: Control output 2 indicator
Lit when control output 2 is ON and not
lit when it's OFF.
• STOP: control stop indicator
Lit when event input or “Run/Stop” is stopped
during operation.
During control stop, functions other than control
output are valid.
• CMW: communications writing enable/ disable
indicator
Lit when communications writing is
“enabled” and is out when it is “disabled”.
Conformance to EN/IEC Standards
This is a class A product.
In residential areas it may cause radio
interference, in which case the user may be
required to take adequate measures to
reduce interference.
Conformance to Safety Standards
Reinforced insulation is provided
between input power supply, relay
outputs, and between other terminals.
• Since the voltage output (control output 1) is not electrically insulated from the internal wiring, one or other of the control output terminals must be left unearthed when
using an earthed thermocouple thermometer. (Connection makes measurements unreliable due to sneak currents.) Basic insulation is provided between the voltage
outputs (control output 2) and internal circuits.
• The last character of the lot number “R” indicates that reinforced insulation is provided between input power supply, relay outputs, and between other terminals.
• Consult your OMRON sales representative about using the ES1B Infrared Thermosensor's external power supply for other purposes.
Indicates a potentially hazardous situation which, if
not avoided, is likely to result in minor or moderate
injury or property damage. Read this manual
carefully before using the product.
• No.1 display
Process value or set data symbol
• No.2 display
Set point, set data read-out value or changed
input value
• Mode key
Press this key to change the contents of
the display.
Press this button for 1 s or longer for
reverse scroll.
E5EN
Digital Controller
Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the
performance and functions of the product. Not doing so may occasionally result in unexpected events. Use the
product within specifications.
(1) The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product
in any of the following locations.
• Places directly subject to heat radiated from heating equipment.
• Places subject to splashing liquid or oil atmosphere.
• Places subject to direct sunlight.
• Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).
• Places subject to intense temperature change.
• Places subject to icing and condensation.
• Places subject to vibration and large shocks.
(2) Use/store within the rated temperature and humidity ranges.
Provide forced-cooling if required.
(3) To allow heat to escape, do not block the area around the product.
Do not block the ventilation holes on the product.
(4) Be sure to wire properly with correct polarity of terminals.
(5) Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. To connect bare wires to the
terminal block, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to a cross-
sectional area of 0.205 to 2.081 mm
2
). (The stripping length is 5 to 6 mm.). Up to two wires of same size and
type, or two crimped terminals can be inserted into a single terminal.
(6) Do not wire the terminals which are not used.
(7) Allow as much space as possible between the controller and devices that generate a powerful high-frequency
or surge.
Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring
with the power lines when you are wiring to the terminals.
(8) Use this product within the rated load and power supply.
(9) Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or
relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur.
(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before
starting actual control operations to ensure the correct temperature display.
(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you turn
the controller ON.
(12) A switch or circuit breaker should be provided close to this unit.
The switch or circuit breaker should be within easy reach of the operator, and must be marked as a
disconnecting means for this unit.
(13) Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply
shock to the terminals or electronic components. When inserting the interior of the product, do not allow the
electronic components to touch the case.
(14) Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol.
(15) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after
power ON.
(16) The output may turn OFF when shifting to certain levels. Take this into consideration when performing control.
(17) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when
frequently overwriting data during communications or other operations.
(18) Refer to the instruction sheet for installing Option unit (E53-AKB/E53-EN01/E53-EN03).
(19) When disassembling the Temperature Controller for disposal, use suitable tools.
(20) Do not use the Temperature Controller if the front sheet is peeling or torn.
Precautions for Safe Use
2111331-4A
Default setting: 0
: Can be displayed and changed
: Can be displayed
× : Display or shifting to another
level is not possible.
Operation level
Adjustment level
Process value
PV/SP
Others
Level
Set value
0 1
×
2
×
×
3
×
×
For detailed operating instructions, please refer to the E5CN/E5AN/E5EN/E5GN
Digital Controllers User's Manual Basic Type (Cat. No. H156).
Significance of WARNINGs and CAUTIONs
INSTRUCTION MANUAL
Thank you for purchasing the OMRON E5EN Digital Controller.
This manual describes the functions, performance, and
application methods needed for optimum use of the product.
Please observe the following items when using the product.
• This product is designed for use by qualified personnel with a
knowledge of electrical systems.
• Before using the product, thoroughly read and understand this
manual to ensure correct use.
• Keep this manual in a safe location so that it is available for
reference whenever required.
For details about advanced function setting level, monitor/setting item level, or
manual control level, refer to E5CN/E5AN/E5EN/E5GN Digital Controllers User's
Manual Basic Type (Cat. No. H156).
For communications details, refer to E5CN/E5AN/E5EN/E5GN Digital Controllers
Communications Manual Basic Type (Cat. No,. H158).
Suitability for Use
OMRON shall not be responsible for conformity with any standards, codes, or regulations that
apply to the combination of the products in the customer's application or use of the product.
Take all necessary steps to determine the suitability of the product for the systems, machines,
and equipment with which it will be used.
Know and observe all prohibitions of use applicable to this product.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE
OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN
DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY
RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT
OR SYSTEM.See also Product catalog for Warranty and Limitation of Liability.
CAUTION
EN1
• AT in Adjustment level
Designate "
at-2
: 100% AT execute" or "
at-1
: 40%
AT execute" to execute AT and "
off
: AT cancel" to
.
“
at
” flashes
“AT cancel”
Also when AT execution ends, the display
automatically returns to “
off
”.
CAUTION
Do not touch the terminals while power is being supplied.
Doing so may occasionally result in minor injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to
enter the product. Doing so may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from
explosion may occasionally occur.
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric
shock, fire, or malfunction may occasionally occur.
CAUTION - Risk of Fire and Electric Shock
a) This product is UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure that
does not allow fire to escape externally.
b) More than one disconnect switch may be required to de-energize the equipment before servicing.
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always
consider the application conditions and use the output relays within their rated load and electrical life expectancy.
The life expectancy of output relays varies considerably with the output load and switching conditions.
Tighten the terminal screws to between 0.74 and 0.90 N•m. Loose screws may occasionally result in fire.
Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable,
unexpected operation may occasionally result in property damage or accidents.
A malfunction in the Temperature Controller may occasionally make control operations impossible or prevent
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital Controller,
take appropriate safety measures, such as installing a monitoring device on a separate line.
A semiconductor is used in the output section of long-life relays. If excessive noise or surge is impressed on the
output terminals, a short-circuit failure is likely to occur. If the output remains shorted, fire will occur due to
overheating of the heater or other cause.Take measures in the overall system to prevent excessive temperature
increase and to prevent fire from spreading.
U
D
Set value
0
1
2
×
×
×
×
Initial setting
level
Communications
setting level
Advanced function
setting level
Default setting: 1
: Change to
other levels
possible
× : Change to
other levels
not
possible
EN
Safety Precautions
• °C / °F : temperature unit
The temperature unit is displayed
when the displayed value is a
temperature.
When this parameter is set to “°C”,
“
C
” is displayed, and when set to
“°F”, “
F
” is displayed.
This flashes while ST (Self-Tuning)
is activated.
• : Protection indicator
Lit when Setting Change Protect is
ON (disables the Up and Down
Keys).
• MANU: Manual output indicator
Lit when the Auto/Manual Mode is
set to Manual Mode.
at
off
at
at-2
OMRON EUROPE B.V.
Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
Phone 31-2356-81-300
FAX 31-2356-81-388
OMRON ELECTRONICS LLC
One Commerce Drive Schaumburg, IL 60173-5302 U.S.A
Phone 1-847-843-7900
FAX 1-847-843-7787
OMRON ASIA PACIFIC PTE. LTD.
No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
Phone 65-6835-3011
FAX 65-6835-2711
OMRON Corporation
©All Rights Reserved
• Function key/Auto/Manual key
Press this function key to operate the
function set with the PF Setting.
• No. 3 display
MV, Soak Time Remain, and Multi-SP.
250 VAC, 1 A
(resistive load)
Relay outputs
Auxiliary output
1, 2, 3
• 100 to 240 VAC
• 24 VAC/VDC (no polarity)
-
Input power supply
+
Auxiliary output 2
1
2
3
4
5
13
14
15
6
7
8
9
10
16
17
18
19
Control output 1
+
Analog input
+
-
TC/Pt multi-input
B
+
V
mA
-
Auxiliary output 3
-
22
23
24
25
26
27
28
29
30 20
CT1
CT2
EV1
EV2
CT1/CT2 Control Output 2
+
-
Control Output 2
DO NOT
USE
+
-
External power supply
12 VDC, 20 mA
DO NOT
USE
External Power Supply
DO NOT
USE
B
A
DO NOT
USE
DO NOT
USE
DO NOT
USE
Auxiliary output 1
Event Inputs
21
11
12
A heater burnout alarm, heater short
alarm, heater overcurrent alarm, or
input alarm is output to the output to
which the alarm 1 function is assigned.
Current output
0 to 20 mA DC
Voltage output
(for driving SSR)
12 VDC, 40 mA
Load: 600
Ω
max.
4 to 20 mA DC
Relay output
250 VAC, 5A
(resistive load)
Control output 2
Voltage output
(for driving SSR)
12 VDC, 21 mA
Control output 1
Communications
RS-485
B (+)
11
A (-)
12
DO NOT USE
13
B (+)
21
A (-)
22
RS-232C
SD
11
RD
12
SG
13
21
22
DO NOT USE
DO NOT USE
Long-life relay output
250 VAC, 3 A
(resistive load)
Key to Warning Symbols
Dimensions
Warning Symbols
Installation
Connections
(The applicability of the electric terminals varies with the type of machine.)
Names of parts on front panel
AT (auto-tuning)
Protection function
Protection function, to prevent unwanted settings, restricts the setting items to be used
or designates if operation of the key is valid or invalid.
Operation / Adjustment protection
The following table shows the relationship between settings and protect limits related to
Operation level and Adjustment level.
Initial setting/Communications protection
This protect level restricts movement to the initial setting level,
communications setting level and advanced function setting level.
Setting change protection
Setting changes by key operation are restricted.
OFF “
off
”: Setting can be changed by key operation
ON “
on
” : Setting cannot be changed by key operation (“ ” will light.)
(Protect level settings can all be changed.)
PF key protection
PF Key operation can be enabled or disabled.
OFF “
off
”: PF Key enabled.
ON ”
on
” : PF Key disabled.
Other functions
Operation menu
Wiring
“100%AT Execute”
Power supply voltage
100 to 240 VAC, 50/60 Hz or
24 VAC, 50/60 Hz /
24VDC
Operating voltage range
85 to 110% of the rated voltage
Power consumption
Approx. 10 VA (100 to 240 VAC)
Approx. 5.5 VA (24 VAC)/4 W (24 VDC)
(Approx. 6.5 VA/4.5 W for models
with transfer output)
Indication accuracy
Thermocouple:
(Ambient temperature: 23°C) (±0.3 % of indication value or ±1°C,
whichever is greater) ±1 digit max.
Platinum resistance thermometer:
(±0.2 % of indication value or ±0.8°C,
whichever is greater) ±1 digit max.
Analog input: ±0.2 % FS ±1 digit max.
Event input
Output current: approx. 7 mA per contact.
Contact input
ON:1 k
Ω
max., OFF: 100 k
Ω
min.
No-contact input
ON: residual voltage 1.5 V max.,
OFF: leakage current 0.1 mA max.
Control output 1
Relay output: SPST-NO,
250 VAC, 5 A (resistive load)
Voltage output (for driving SSR):
12 VDC, 40 mA
Current output: 4 to 20 mA DC, 0 to 20 mA DC
Load:
600
Ω
max.
Electrical life of relay:
100,000
operations
Control output 2
Voltage output (for driving SSR):
12 VDC, 21 mA
Relay output: SPST-NO,
250 VAC, 3 A (resistive load)
Electrical life of relay:
1 million operations (Long-life model)
External power supply for
12 VDC±10% at 20 mA
ES1B Control method
ON/OFF or 2-PID control
Auxiliary outputs
Relay outputs: SPST-NO, 250 VAC, 3 A
(resistive load),
Electrical life of relay: 100,000 operations
Ambient temperature
–10 to 55°C
(Avoid freezing or condensation)
Ambient humidity
RH25 to 85%
Storage temperature
–25 to 65°C
(Avoid freezing or condensation)
Altitude
Max. 2,000 m
Recommended fuse
T2A, 250 VAC, time-lag,
low-breaking
capacity
Weight
Approx. 260 g (main unit only)
Degree of protection
Front panel: IP66
Rear case: IP20, Terminal section: IP00
Installation environment
Installation category II, pollution
degree 2 (as per IEC61010-1)
Memory protection
Non-volatile memory
(Number of write operations: 1,000,000)
Transfer output
4 to20mA DC, Load:600
Ω
max.
Specifications
25
26
27
28
EV4
EV3
21
22
23
24
29
30
+
-
Transfer output
DO NOT USE
DO NOT USE
DO NOT USE
4-20 mA DC
(Load: 600
Ω
max.)
OMRON Corporation
Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN
The E5
@
N-
@@@@@@
T
@
is set for a K thermocouple
(input type of 5) by default. If a different sensor is
used, an input error (
s.err
) will occur. Check the
setting of the Input Type parameter.
A급 기기(업무용 방송통신기자재)
이 기기는 업무용(A급) 전자파적합기기로서
판매자 또는 사용자는 이 점을 주의하시기 바라며,
가정외의 지역에서 사용하는 것을 목적으로
합니다.
Adjustment level is for entering set
values and shift values for control.
Temperature Input Shift
(Unit: °C or °F )
Upper Limit Temperature
Input Shift Value
when 2 point input shift
is selected
Lower Limit Temperature
Input Shift Value
when 2 point input shift
is selected
Adjustment Level
Proportional Band
Integral Time
(Unit: secs)
AT Execute/Cancel
100%AT Execute
at-2
40%AT Execute
at-1
*6
*6
*6
*6
*6
*6
l.adj
at
off
Heater Current 1
Value Monitor
(Unit: A) *
7
*6
ct1
0.0
*6
Heater Burnout
Detection 1
(Unit: A) *
7
*6
hb1
0.0
*6
ins
0.0
insh
0.0
insl
0.0
p
8.0
i
233
Derivative Time
(Unit: secs)
*6
d
40
Dead Band
Manual Reset Value
(Unit: %)
Hysteresis
(Cooling)
Soak Time
SP Ramp Set Value
MV Upper Limit
MV Lower Limit
Hysteresis
(Heating)
*6
*6
*6
*6
*6
*6
*6
*6
hys
1.0
chys
1.0
soak
1
sprt
off
ol-h
105.0
ol-l
-5.0
c-db
0.0
of-r
50.0
Cooling Coefficient
*6
c-sc
1.00
Wait Band
*6
wt-b
off
MV Change Rate Limit
*6
orl
0.0
Extraction of Square
Root Low-cut Point
*6
sqrp
0.0
*6
Leakage Current 1
Value Monitor
(Unit: A) *
7
HS Alarm 1
(Unit: A) *
7
lcr1
0.0
Heater Overcurrent
Detection 1
(Unit: A)
oc1
50.0
hs1
50.0
oapt
0
icpt
1
wtpt
off
pfpt
off
PF Key Protect
prlp
0
*6
*6
*6
*6
*6
*6
Extraction of Square Root Enable
(Only when analog input is set)
*6
*6
*6
*6
Alarm 3 Hysteresis
Alarm 1 Hysteresis
Alarm 2 Hysteresis
Operation level should normally
be used during operations.
(No.1display flushes,
then the control stops.)
Operation / Adjustment
Protect
Initial Setting /
Communication
Protect
Setting Change Protect
Move to Protect Level
Restricts which settings can be displayed
or changed, and restricts change by key
operation.
PV/SP
s.err
is displayed when
connected sensor is
different from input type.
(The No.3 display
has been omitted.)
Set Point During
SP Ramp
Alarm Value 1 *
4
A
larm Value Upper Limit 1
*4
Alarm Value Lower Limit 1
*4
Alarm Value 2 *
4
Alarm Value 3 *
4
Alarm Value Upper Limit 2
*4
Program Start
*3: Refer to the adjoining tables for details of input types and alarm types.
*4: Applicable only to models with alarm functions.
*5: Operation is stopped when moved to the initial setting level.
(control/alarm are both stopped.)
*6: The grayed-out setting items may not be displayed according to the models
and setting.
*7: This function is supported only by models with heater burnout detection.
*6
*6
*6
*6
*6
*6
*6
Alarm Value Lower Limit 2
*4
*6
Heater Current 1
Value Monitor
(Unit: A) *
7
*6
Leakage Current 1
Value Monitor
(Unit: A) *
7
*6
Soak Time Remain
*6
When control start =
run
When control stop =
stop
RUN/STOP
*6
*6
Alarm Value Upper Limit 3
*4
*6
Alarm Value Lower Limit 3
*4
*6
Initial setting level enables users to specify their
preferred operating conditions (input type, alarm type,
control method, etc.)
Hold down
for at least
3 seconds
Hold down
for at least
1 second
Hold and
M
keys
down for at least 1 second
Hold and
M
keys
down for at least
3 seconds
POWER ON
Operation stopped.
(Control/alarm are both stopped.)
*5
Press
(less than
1 second)
Individual mounting (mm)
Side-by-side mounting (mm)
• Insert the main unit through the mounting hole in the panel (1-8 mm
thickness). Insert the mounting brackets (supplied) into the fixing
slots located on the top and bottom of the rear case.
• Alternately tighten the top and bottom screws on the mounting
fixtures applying equal pressure a little at a time until the rachet
rotates freely.
• When more than one machine is installed, make sure that the
ambient temperature does not exceed the specified limit.
Waterproofing is impossible
with side-by-side
installation. When
waterproofing is required, fit
watertight packing on the
backside of front panel.
120 min
45
92
+ 0.6
0
+ 0.8 0
(48 x number of units–2.5) + 1
0
92
+ 0.8 0
Input Type *
3
Scaling Upper Limit
(only when setting analog input)
Scaling Lower Limit
(only when setting analog input)
Decimal Point
(only when setting analog input)
Temperature Unit
SP Upper Limit
SP Lower Limit
PID ON/OFF
In ON/OFF control =
onof
In 2-PID control =
pid
Standard or Heating/Cooling
Standard control =
stnd
Heating and cooling control =
h-c
(Select standard control or heating
and cooling control as required)
Control Period (Heating)
(Unit: Seconds)
Alarm 2 Type: Specified models only
Alarm 1 Type: Specified models only
Control Period (Cooling)
(Unit: Seconds)
°C=
c
°F=
f
(C stands for Celsius, F for Fahrenheit)
ST (Self-tuning)
ST ON =
on
ST OFF =
off
Direct/Reverse Operation
In Reverse operation (Heating) =
or-r
In Direct operation (Cooling) =
or-d
*3
*4
*3
*4
*6
*6
*6
*6
*6
*6
*6
*6
Transfer Output Type
Transfer Output Upper Limit
Transfer Output Lower Limit
Linear Current Output
Program Pattern
Alarm 3 Type: Specified models only
*3
*4
in-t
5
in-h
100
in-l
0
dp
0
d-u
c
sl-h
1300
sl-l
-200
cntl
onof
s-hc
stnd
st
on
ptrn
off
cp
20
c-cp
20
orev
or-r
alt1
2
25
0
sp-m
0
ct1
0.0
lcr1
0.0
prst
rset
sktr
0
r-s
run
al-1
0
al1h
0
al1l
0
al-2
0
al2h
0
al2l
0
al-3
0
al3h
0
al3l
0
Only the value set to the “
ins
: Temperature Input Shift” parameter is
applied to the entire temperature input range. When the process value is
200 °C, the process value is treated as 201.2 °C after input shift if the
input shift value is set to 1.2 °C.
The process value is treated as 198.8 °C after input shift if the input shift
value is set to –1.2 °C.
*2: Error shown only for "Process value / Set point". Not shown for other status.
If the input value exceeds the display limit (-1999 to 9999), though it is within the control
range,
[[[[
will be displayed under -1999 and
]]]]
above 9999. Under these conditions,
control output and alarm output will operate normally.Refer to E5CN/E5AN/E5EN/E5GN
Digital Controllers User's Manual Basic Type (Cat. No. H156) for details of control range.
Check the setting of the Input Type parameter,
check the input wiring, and check for broken or
shorts in the temperature sensor.
Turn the power OFF then back ON again. If the
display remains the same, the controller must be
repaired. If the display is restored to normal, then
a probable cause can be external noise affecting
the control system. Check for external noise.
After the correction of A/D converter error, turn the
power OFF then back ON again. If the display
remains the same, the controller must be repaired.
If the display is restored to normal, then a
probable cause can be external noise affecting the
control system. Check for external noise.
No.1 display
Meaning
A/D converter error
*2
Memory error
Input error
*2
s.err
(S. Err)
e111
(E111)
Action
OFF
Alarm
Control
output
Status at error
OFF
OFF
Operates
as above the
upper limit.
OFF
OFF
e333
(E333)
X
ON
OFF
SP
X
ON
OFF
SP
ON
OFF
SP
X
X
ON
OFF
SP
L H
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
SP
X
ON
OFF
0
ON
OFF
X
0
X
ON
OFF
0
X
ON
OFF
0
ON
OFF
X
0
X
ON
OFF
0
ON
OFF
X
0
L H
ON
OFF
SP
L H
ON
OFF
SP
SP
X
ON
OFF
SP
ON
OFF
X
ON
OFF
X
0
Alarm output function
Positive alarm value (X) Negative alarm value (X)
Alarm type
Setting
No alarm function
Deviation upper/lower limit
standby sequence ON
Absolute value upper limit
Absolute value lower limit
Absolute value upper limit
standby sequence ON
Absolute value lower limit
standby sequence ON
LBA (only for alarm 1)
Deviation lower limit
standby sequence ON
Deviation upper limit
standby sequence ON
Deviation upper/lower range
Deviation upper limit
Deviation upper/lower limit
Deviation lower limit
Output off
Vary with "L", "H" values
Vary with "L", "H" values
Vary with "L", "H" values
-200 to 850 (°C)
-199.9 to 500.0 (°C)
0.0 to 100.0 (°C)
-199.9 to 500.0 (°C)
0.0 to 100.0 (°C)
-200 to 1300 (°C)
-20.0 to 500.0 (°C)
-100 to 850 (°C)
-20.0 to 400.0 (°C)
-200 to 400 (°C)
-199.9 to 400.0 (°C)
-200 to 600 (°C)
-100 to 850 (°C)
-200 to 400 (°C)
-199.9 to 400.0 (°C)
-200 to 1300 (°C)
0 to 1700 (°C)
0 to 1700 (°C)
100 to 1800 (°C)
0 to 90 (°C)
0 to 120 (°C)
0 to 165 (°C)
0 to 260 (°C)
/-300 to 1500 (°F)
/-199.9 to 900.0 (°F)
/0.0 to 210.0 (°F)
/-199.9 to 900.0 (°F)
/0.0 to 210.0 (°F)
/-300 to 2300 (°F)
/0.0 to 900.0 (°F)
/-100 to 1500 (°F)
/0.0 to 750.0 (°F)
/-300 to 700 (°F)
/-199.9 to 700.0 (°F)
/-300 to 1100 (°F)
/-100 to 1500 (°F)
/-300 to 700 (°F)
/-199.9 to 700.0 (°F)
/-300 to 2300 (°F)
/0 to 3000 (°F)
/0 to 3000 (°F)
/300 to 3200 (°F)
/0 to 190 (°F)
/0 to 240 (°F)
/0 to 320 (°F)
/0 to 500 (°F)
Setting range
Input type
Platinum
resistance
thermometer
Input
Pt100
JPt100
Thermocouple
Infrared
Thermosensor
ES1B
Analog input
Thermocouple
K
J
T
E
L
U
N
R
S
B
Use the following ranges for scaling:
-1999 to 9999,-199.9 to 999.9
0 to 2300 (°C) /0 to 3200 (°F)
0 to 1300 (°C) /0 to 2300 (°F)
10 -70
60 -120°C
115 -165°C
140 -260°C
0 to 50mV
W
PL
II
Setting
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
Use the following ranges for scaling: -1999
to 9999, -199.9 to 999.9, -19.99 to 99.99,
-1.999 to 9.999
Analog
input type
Setting range
Input type
Current input
Voltage input
Input
4 to 20mA
0 to 20mA
1 to 5V
0 to 5V
0 to 10V
• The default is
“
0
”
.
Setting
0
1
2
3
4
*The default is“5”.
*
s.err
will be displayed when a platinum resistance thermometer is mistakenly connected while input
type is not set for it. To clear the
s.err
display, correct the wiring and cycle the power supply.
When an error has occurred, the No.1 display shows the error code. Take
necessary measure according to the error code, referring the table below.
*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for
different types of alarm. These are indicated by the letter "L" and "H".
• The default alarm type is "2"
1
0
2
3
4
5
6
7
8
9
10
11
12
13
*1
*1
*1
Thermocouple/platinum-resistance thermometer (multi-input)
PV Change Rate Alarm
Input Type
Alarms
Error display (troubleshooting)
Initial Setting Level
Operation Level
Protect Level
Adjustment Level
alh1
0.2
alt2
2
alh2
0.2
alt3
2
alh3
0.2
tr-t
off
tr-h
100.0
tr-l
0.0
o1-t
4-20
sqr
off
The setting data for the E5EN-
@
3HT/L is shown here as an example.
Check the wiring before turning ON the power supply.
Dimensions (mm)
Mounting
bracket
Solderless terminal size: M3.5
Terminal cover:
(Model: E53-COV16)
USB-Serial Conversion Cable
(Sold Separately)
(E58-CIFQ1)
In the pack:
• Main unit
• Watertight packing
• Two mounting brackets
• Instruction manual
• Terminal cover
(Provided only for models
with "-500" suffix.)
* The internal mechanisms can be drawn out for maintenance without removing terminal wiring.
* Do not remove the terminal block. Doing so may result in failure or malfunction.
* A Setup Tool port is provided on the bottom of the product. Use this port to connect a personal computer to the
product when using the Setup Tool. E58-CIFQ1 USB-Serial Conversion Cable is required to connect the personal
computer to the product. (Do not use the product with the USB-Serial Conversion Cable left permanently
connected.)
Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods.
Watertight
packing
Terminal
cover
96
48
6
112
79.2
78
2
91
44