• Up and Down keys 

Use the keys to change the values displayed on 

the No.2 display. 

Each press of 

U

 key increments or advances the 

values displayed on the No.2 display. 

Each press of 

D

 key decrements or returns the 

values displayed on the No.2 display. 

• Level key 
Use this key to change levels: 

• Press the      key and the 

M

 key 

together for at least 3 seconds to switch 
to protect level. 

Operation indicators 
• SUB1: Auxiliary output 1 indicator 
  Lit when the function assigned to auxiliary 

output 1 is ON.  

• SUB2: Auxiliary output 2 indicator 
  Lit when the function assigned to auxiliary 

output 2 is ON. 

• SUB3: Auxiliary output 3 indicator 
  Lit when the function assigned to auxiliary 

output 3 is ON. 

• HA: Heater burnout alarm/Heater short 

alarm/Heater overcurrent alarm indicator 
Lit when a heater burnout alarm, heater 

short alarm, or heater overcurrent alarm 

has occurred.  

• OUT1: Control output 1 indicator 

Lit when control output 1 is ON and not  

lit when it's OFF. 

    For a current output, lit except for a 0% output.  

• OUT2: Control output 2 indicator 

Lit when control output 2 is ON and not  

lit when it's OFF.  

• STOP: control stop indicator 

Lit when event input or “Run/Stop” is stopped 

during operation. 

During control stop, functions other than control 

output are valid. 

• CMW: communications writing enable/ disable 

indicator 

Lit when communications writing is  

“enabled” and is out when it is “disabled”. 

Conformance to EN/IEC Standards

This is a class A product. 

In residential areas it may cause radio 

interference, in which case the user may be 

required to take adequate measures to 

reduce interference.

Conformance to Safety Standards

Reinforced insulation is provided 

between input power supply, relay 

outputs, and between other terminals.

•  Since the voltage output (control output 1) is not electrically insulated from the internal wiring, one or other of the control output terminals must be left unearthed when 

using an earthed thermocouple thermometer. (Connection makes measurements unreliable due to sneak currents.) Basic insulation is provided between the voltage 
outputs (control output 2) and internal circuits. 

•  The last character of the lot number “R” indicates that reinforced insulation is provided between input power supply, relay outputs, and between other terminals.  
•  Consult your OMRON sales representative about using the ES1B Infrared Thermosensor's external power supply for other purposes.  

Indicates a potentially hazardous situation which, if 

not avoided, is likely to result in minor or moderate 

injury or property damage. Read this manual 

carefully before using the product. 

• No.1 display 
Process value or set data symbol 
• No.2 display 
Set point, set data read-out value or changed 
input value  

• Mode key 

Press this key to change the contents of 

the display. 

Press this button for 1 s or longer for 

reverse scroll. 

E5EN 

Digital Controller 

Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the 

performance and functions of the product. Not doing so may occasionally result in unexpected events. Use the 

product within specifications. 

(1)   The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product 

in any of the following locations. 

 

  • Places directly subject to heat radiated from heating equipment. 

 

  • Places subject to splashing liquid or oil atmosphere. 

 

  • Places subject to direct sunlight. 

 

  • Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas). 

 

  • Places subject to intense temperature change. 

 

  • Places subject to icing and condensation. 

 

  • Places subject to vibration and large shocks. 

(2)   Use/store within the rated temperature and humidity ranges. 

 

Provide forced-cooling if required. 

(3)   To allow heat to escape, do not block the area around the product. 

 

Do not block the ventilation holes on the product. 

(4)   Be sure to wire properly with correct polarity of terminals. 

(5)   Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. To connect bare wires to the 

terminal block, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to a cross- 

 

sectional area of 0.205 to 2.081 mm

2

). (The stripping length is 5 to 6 mm.). Up to two wires of same size and 

type, or two crimped terminals can be inserted into a single terminal. 

(6)   Do not wire the terminals which are not used. 

(7)   Allow as much space as possible between the controller and devices that generate a powerful high-frequency 

or surge. 

 

Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring 

with the power lines when you are wiring to the terminals. 

(8)   Use this product within the rated load and power supply. 

(9)   Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or 

relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may occur. 

(10)  Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before 

starting actual control operations to ensure the correct temperature display.  

(11)  When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you turn 

the controller ON. 

(12)  A switch or circuit breaker should be provided close to this unit. 

 

The switch or circuit breaker should be within easy reach of the operator, and must be marked as a 

disconnecting means for this unit. 

(13)  Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply 

shock to the terminals or electronic components. When inserting the interior of the product, do not allow the 

electronic components to touch the case.  

(14)  Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol.  

(15)  Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set after 

power ON. 

(16)  The output may turn OFF when shifting to certain levels. Take this into consideration when performing control. 

(17)  The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when 

frequently overwriting data during communications or other operations. 

(18)  Refer to the instruction sheet for installing Option unit (E53-AKB/E53-EN01/E53-EN03). 

(19)  When disassembling the Temperature Controller for disposal, use suitable tools. 

(20)  Do not use the Temperature Controller if the front sheet is peeling or torn. 

Precautions for Safe Use 

2111331-4A

Default setting: 0 

    : Can be displayed and changed 
    : Can be displayed 
×  : Display or shifting to another  
 

level is not possible. 

 
Operation level 
 
Adjustment level 

Process value 
PV/SP 
Others 

Level 

Set value 

0 1 

 
 
 

× 

 
 

× 
× 

 
 

× 
× 

For detailed operating instructions, please refer to the E5CN/E5AN/E5EN/E5GN  
Digital Controllers User's Manual Basic Type (Cat. No. H156).  
Significance of WARNINGs and CAUTIONs 

INSTRUCTION MANUAL 

Thank you for purchasing the OMRON E5EN Digital  Controller.  
This manual describes the functions, performance, and 
application methods needed for optimum use of the product. 
Please observe the following items when using the product. 
• This product is designed for use by qualified personnel with a 

knowledge of electrical systems. 

• Before using the product, thoroughly read and understand this 

manual to ensure correct use. 

• Keep this manual in a safe location so that it is available for 

reference whenever required. 

For details about advanced function setting level, monitor/setting item level, or 

manual control level, refer to E5CN/E5AN/E5EN/E5GN Digital Controllers User's 

Manual Basic Type (Cat. No. H156). 

For communications details, refer to E5CN/E5AN/E5EN/E5GN Digital Controllers 

Communications Manual Basic Type (Cat. No,. H158). 

Suitability for Use

 

OMRON shall not be responsible for conformity with any standards, codes, or regulations that 

apply to the combination of the products in the customer's application or use of the product. 

Take all necessary steps to determine the suitability of the product for the systems, machines, 

and equipment with which it will be used. 

Know and observe all prohibitions of use applicable to this product. 

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE 

OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN 

DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY 

RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT 

OR SYSTEM.See also Product catalog for Warranty and Limitation of Liability. 

CAUTION 

EN1 

• AT in Adjustment level 

Designate "

at-2

: 100% AT execute" or "

at-1

: 40%  

AT execute" to execute AT and "

off

: AT cancel" to

 

at

” flashes 

“AT cancel” 

Also when AT execution ends, the display  
automatically returns to “

off

”. 

CAUTION 

Do not touch the terminals while power is being supplied.  

Doing so may occasionally result in minor injury due to electric shock. 
Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to 

enter the product. Doing so may occasionally result in electric shock, fire, or malfunction. 
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from 

explosion may occasionally occur.  
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric 
shock, fire, or malfunction may occasionally occur.  

CAUTION - Risk of Fire and Electric Shock 

a) This product is UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure that 

does not allow fire to escape externally. 

b) More than one disconnect switch may be required to de-energize the equipment before servicing.  
c) Signal inputs are SELV, limited energy. 
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.  
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always 
consider the application conditions and use the output relays within their rated load and electrical life expectancy. 
The life expectancy of output relays varies considerably with the output load and switching conditions.  
Tighten the terminal screws to between 0.74 and 0.90 N•m. Loose screws may occasionally result in fire.  
Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, 
unexpected operation may occasionally result in property damage or accidents.  
A malfunction in the Temperature Controller may occasionally make control operations impossible or prevent 
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital Controller, 
take appropriate safety measures, such as installing a monitoring device on a separate line.  
A semiconductor is used in the output section of long-life relays. If excessive noise or surge is impressed on the 
output terminals, a short-circuit failure is likely to occur. If the output remains shorted, fire will occur due to 
overheating of the heater or other cause.Take measures in the overall system to prevent excessive temperature 
increase and to prevent fire from spreading. 

Set value 

 



 
 

× 

 
 

× 

 

× 
× 

Initial setting 

level 

Communications  

setting level 

Advanced function  

setting level 

Default setting: 1 

    : Change to  

 

other levels  

 possible 

×  : Change to  

 

other levels  

 not 

possible 

EN 

Safety Precautions 

• °C / °F : temperature unit 

The temperature unit is displayed 

when the displayed value is a 

temperature.
When this parameter is set to “°C”,

C

” is displayed, and when set to 

“°F”, “

F

” is displayed.

This flashes while ST (Self-Tuning) 

is activated. 

•         : Protection indicator

Lit when Setting Change Protect is 

ON (disables the Up and Down 

Keys). 

• MANU: Manual output indicator

Lit when the Auto/Manual Mode is 

set to Manual Mode. 

at 

off 

at 

at-2 

OMRON EUROPE B.V. 

Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands 
 Phone 31-2356-81-300 
 FAX 31-2356-81-388 

OMRON ELECTRONICS LLC 

One Commerce Drive Schaumburg, IL 60173-5302 U.S.A   
    Phone 1-847-843-7900 
 FAX 1-847-843-7787 

OMRON ASIA PACIFIC PTE. LTD. 

No. 438A Alexandra Road # 05-05/08 (Lobby 2), 
Alexandra Technopark, Singapore 119967 
 Phone 65-6835-3011 
 FAX 65-6835-2711 

OMRON Corporation 

 ©All Rights Reserved 

• Function key/Auto/Manual key 
Press this function key to operate the 
function set with the PF Setting. 

• No. 3 display 
MV, Soak Time Remain, and Multi-SP. 

250 VAC, 1 A  
(resistive load) 

Relay outputs 

Auxiliary output  

1, 2, 3 

• 100 to 240 VAC 

• 24 VAC/VDC (no polarity) 

Input power supply 

Auxiliary output 2 

13 

14 

15 

10 

16 

17 

18 

19 

Control output 1 

Analog input 

TC/Pt multi-input 

mA 

Auxiliary output 3 

22 

23 

24 

25 

26 

27 

28 

29 

30 20 

CT1 

CT2 

EV1 

EV2 

CT1/CT2 Control Output 2 

Control Output 2 

DO NOT 

USE 

External power supply 

12 VDC, 20 mA 

DO NOT 

USE 

External Power Supply 

DO NOT 

USE 

DO NOT 

USE 

DO NOT 

USE 

DO NOT 

USE 

Auxiliary output 1 

Event Inputs 

21 

11 

12 

A heater burnout alarm, heater short  
alarm, heater overcurrent alarm, or   
input alarm is output to the output to   
which the alarm 1 function is assigned. 

Current output 

0 to 20 mA DC 

Voltage output  

(for driving SSR) 

12 VDC, 40 mA 

Load: 600 

Ω

max. 

4 to 20 mA DC 

Relay output 

250 VAC, 5A  

(resistive load) 

Control output 2 

Voltage output  

(for driving SSR) 

12 VDC, 21 mA 

Control output 1 

Communications 

RS-485 

B (+) 

11 

A (-) 

12 

DO NOT USE 

13 

B (+) 

21 

A (-) 

22 

RS-232C 

SD 

11 

RD 

12 

SG 

13 

21 

22 

DO NOT USE 

DO NOT USE 

Long-life relay output 

250 VAC, 3 A  

(resistive load) 

Key to Warning Symbols 

Dimensions 

Warning Symbols 

Installation 

Connections 

(The applicability of the electric terminals varies with the type of machine.) 

Names of parts on front panel 

AT (auto-tuning) 

Protection function 

Protection function, to prevent unwanted settings, restricts the setting items to be used  
or designates if operation of the key is valid or invalid.  

Operation / Adjustment protection 

The following table shows the relationship between settings and protect limits related to  

Operation level and Adjustment level. 

Initial setting/Communications protection 

This protect level restricts movement to the initial setting level,  

communications setting level and advanced function setting level. 

Setting change protection 

Setting changes by key operation are restricted.  

OFF “

off

”: Setting can be changed by key operation  

ON “

on

”    : Setting cannot be changed by key operation (“            ” will light.)  

(Protect level settings can all be changed.) 

PF key protection 

PF Key operation can be enabled or disabled. 

OFF “

off

”: PF Key enabled. 

ON   ”

on

”  : PF Key disabled. 

Other functions 

Operation menu 

Wiring 

“100%AT Execute”  

Power supply voltage 

100 to 240 VAC, 50/60 Hz or  

 

24 VAC, 50/60 Hz /  

 24VDC 

Operating voltage range 

85 to 110% of the rated voltage 

Power consumption 

Approx. 10 VA (100 to 240 VAC) 

 

Approx. 5.5 VA (24 VAC)/4 W (24 VDC) 

 

 (Approx. 6.5 VA/4.5 W for models 

 

with transfer output)  

Indication accuracy 

Thermocouple:  

(Ambient temperature: 23°C) (±0.3 % of indication value or ±1°C, 

 

whichever is greater) ±1 digit max.  

 

Platinum resistance thermometer:  

 

(±0.2 % of indication value or ±0.8°C,  

 

whichever is greater) ±1 digit max. 

 

Analog input: ±0.2 % FS ±1 digit max. 

Event input 

Output current: approx. 7 mA per contact. 

  Contact input 

ON:1 k

Ω

 max., OFF: 100 k

Ω

 min. 

  No-contact input 

ON: residual voltage 1.5 V max., 

 

OFF: leakage current 0.1 mA max. 

Control output 1 

Relay output: SPST-NO, 

 

250 VAC, 5 A (resistive load) 

 

Voltage output (for driving SSR):  

 

12 VDC, 40 mA 

 

Current output: 4 to 20 mA DC, 0 to 20 mA DC 

 Load: 

600

Ω

 max. 

 

Electrical life of relay: 

 100,000 

operations 

Control output 2 

Voltage output (for driving SSR):  

 

12 VDC, 21 mA 

 

Relay output: SPST-NO, 

 

250 VAC, 3 A (resistive load) 

 

Electrical life of relay: 

 

1 million operations (Long-life model) 

External power supply for 

12 VDC±10% at 20 mA 

ES1B Control method 

ON/OFF or 2-PID control 

Auxiliary outputs 

Relay outputs: SPST-NO, 250 VAC, 3 A  

 

(resistive load),  

 

Electrical life of relay: 100,000 operations 

Ambient temperature 

–10 to 55°C 

 

(Avoid freezing or condensation) 

Ambient humidity 

RH25 to 85% 

Storage temperature 

–25 to 65°C 

 

(Avoid freezing or condensation) 

Altitude 

Max. 2,000 m 

Recommended fuse 

T2A, 250 VAC, time-lag, 

 low-breaking 

capacity 

Weight 

Approx. 260 g (main unit only) 

Degree of protection 

Front panel: IP66 

 

Rear case: IP20, Terminal section: IP00 

Installation environment 

Installation category II, pollution 

 

degree 2 (as per IEC61010-1) 

Memory protection 

Non-volatile memory 

 

(Number of write operations: 1,000,000) 

Transfer output 

4 to20mA DC,  Load:600

Ω

max. 

Specifications 

25 

26 

27 

28 

EV4 

EV3 

21 

22 

23 

24 

29 

30 

Transfer output 

DO NOT USE 

DO NOT USE 

DO NOT USE 

4-20 mA DC 

(Load: 600

Ω

 max.) 

OMRON Corporation 

Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN 

The E5

@

N-

@@@@@@

T

@

 is set for a K thermocouple 

(input type of 5) by default. If a different sensor is 

used, an input error (

s.err

) will occur. Check the 

setting of the Input Type parameter.

A급 기기(업무용 방송통신기자재)
이 기기는 업무용(A급) 전자파적합기기로서 
판매자 또는 사용자는 이 점을 주의하시기 바라며, 
가정외의 지역에서 사용하는 것을 목적으로 
합니다.

Adjustment level is for entering set 

values and shift values for control. 

Temperature Input Shift 
(Unit: °C   or °F   ) 

Upper Limit Temperature  
Input Shift Value 
when 2 point input shift  
is selected 
Lower Limit Temperature  
Input Shift Value 
when 2 point input shift  
is selected 

Adjustment Level 

Proportional Band 

Integral Time 
(Unit: secs) 

AT Execute/Cancel 

100%AT Execute 

at-2 

40%AT Execute 

at-1 

*6 

*6 

*6 

*6 

*6 

*6 

l.adj 

 

at 

off 

Heater Current 1  
Value Monitor 
(Unit: A) *

*6 

ct1 

0.0 

*6 

Heater Burnout  
Detection 1 
(Unit: A) *

7

  

*6 

hb1 

0.0 

*6 

ins 

0.0 

insh 

0.0 

insl 

0.0 

8.0 

233 

Derivative Time 
(Unit: secs) 

*6 

40 

Dead Band 

Manual Reset Value 
(Unit: %) 

Hysteresis  
(Cooling) 

Soak Time 

SP Ramp Set Value 

MV Upper Limit 

MV Lower Limit 

Hysteresis  
(Heating) 

*6 

*6 

*6 

*6 

*6 

*6 

*6 

*6 

hys 

1.0 

chys 

1.0 

soak 

sprt 

off 

ol-h 

105.0 

ol-l 

-5.0 

c-db 

0.0 

of-r 

50.0 

Cooling Coefficient 

*6 

c-sc 

1.00 

Wait Band 

*6 

wt-b 

off 

MV Change Rate Limit 

*6 

orl 

0.0 

Extraction of Square  
Root Low-cut Point 

*6 

sqrp 

0.0 

*6 

Leakage Current 1  
Value Monitor 
(Unit: A) *

HS Alarm 1 
(Unit: A) *

lcr1 

0.0 

Heater Overcurrent  
Detection 1   
 (Unit: A) 

oc1 

50.0 

hs1 

50.0 

oapt 

icpt 

wtpt 

off 

pfpt 

off 

PF Key Protect 

prlp 

*6 

*6 

*6 

*6 

*6 

*6 

Extraction of Square Root Enable 
(Only when analog input is set) 

*6 

*6 

*6 

*6 

Alarm 3 Hysteresis 

Alarm 1 Hysteresis 

Alarm 2 Hysteresis 

Operation level should normally 
be used during operations.  

(No.1display flushes,  
then the control stops.) 

Operation / Adjustment 
Protect 

Initial Setting /  

Communication 

Protect 

Setting Change Protect 

Move to Protect Level 

Restricts which settings can be displayed 
or changed, and restricts change by key 
operation. 

PV/SP 

s.err

 is displayed when  

connected sensor is  

different from input type. 

(The No.3 display  
has been omitted.) 

Set Point During  
SP Ramp 

Alarm Value 1 *

A

larm Value Upper Limit 1 

*4 

Alarm Value Lower Limit 1 

*4 

Alarm Value 2  *

Alarm Value 3  *

   Alarm Value Upper Limit 2

  

*4 

Program Start 

*3: Refer to the adjoining tables for details of input types and alarm types.  
*4: Applicable only to models with alarm functions. 
*5: Operation is stopped when moved to the initial setting level. 
     (control/alarm are both stopped.) 
*6: The grayed-out setting items may not be displayed according to the models 

and setting. 

*7: This function is supported only by models with heater burnout detection. 

*6 

*6 

*6 

*6 

*6 

*6 

*6 

Alarm Value Lower Limit 2 

*4 

*6 

Heater Current 1  
Value Monitor 
(Unit: A) *

*6 

Leakage Current 1  
Value Monitor 
(Unit: A) *

*6 

Soak Time Remain 

*6 

When control start = 

run 

When control stop = 

stop 

RUN/STOP 

*6 

*6 

Alarm Value Upper Limit 3 

*4 

*6 

Alarm Value Lower Limit 3 

*4 

*6 

Initial setting level enables users to specify their 

preferred operating conditions (input type, alarm type, 

control method, etc.) 

Hold     down 

for at least 

3 seconds 

Hold     down 

for at least 

1 second 

Hold      and 

M

 keys 

down for at least 1 second 

Hold       and 

M

 keys 

down for at least 

3 seconds 

POWER  ON 

Operation stopped. 

(Control/alarm are both stopped.) 

*5 

Press      

(less than  

 1 second) 

Individual mounting (mm) 

Side-by-side mounting (mm) 

• Insert the main unit through the mounting hole in the panel (1-8 mm 

thickness). Insert the mounting brackets (supplied) into the fixing 

slots located on the top and bottom of the rear case. 

• Alternately tighten the top and bottom screws on the mounting 

fixtures applying equal pressure a little at a time until the rachet 

rotates freely. 

• When more than one machine is installed, make sure that the 

ambient temperature does not exceed the specified limit. 

Waterproofing is impossible 

with side-by-side 

installation. When 

waterproofing is required, fit 

watertight packing on the 

backside of front panel. 

120 min 

45 

92 

+ 0.6 

   0 

+ 0.8     0 

(48 x number of units–2.5)  + 1  

   0 

92 

+ 0.8     0 

Input Type *

Scaling Upper Limit 
 (only when setting analog input) 

Scaling Lower Limit  
(only when setting analog input) 

Decimal Point  
(only when setting analog input) 

Temperature Unit 

SP Upper Limit 

SP Lower Limit 

PID ON/OFF 
In ON/OFF control = 

onof 

In 2-PID control = 

pid 

Standard or Heating/Cooling 
Standard control = 

stnd 

Heating and cooling control = 

h-c 

(Select standard control or heating 
         and cooling control as required)  

Control Period (Heating) 
(Unit: Seconds) 

Alarm 2 Type: Specified models only  

Alarm 1 Type: Specified models only  

Control Period (Cooling) 
(Unit: Seconds) 

°C= 

°F= 

(C stands for Celsius, F for Fahrenheit) 

ST (Self-tuning) 
ST ON  = 

on 

ST OFF = 

off 

Direct/Reverse Operation 

In Reverse operation (Heating) =

 

or-r 

In Direct operation (Cooling) =  

   

or-d 

*3 
*4 

*3 
*4 

*6 

*6 

*6 

*6 

*6 

*6 

*6 

*6 

Transfer Output Type 

Transfer Output Upper Limit 

Transfer Output Lower Limit 

Linear Current Output 

Program Pattern 

Alarm 3 Type: Specified models only  

*3 
*4 

in-t 

in-h 

100 

in-l 

dp 

d-u 

sl-h 

1300 

sl-l 

-200 

cntl 

onof 

s-hc 

stnd 

st 

on 

ptrn 

off 

cp 

20 

c-cp 

20 

orev 

or-r 

alt1 

25 

sp-m 

ct1 

0.0 

lcr1 

0.0 

prst 

rset 

sktr 

r-s 

run 

al-1 

al1h 

al1l 

al-2 

al2h 

al2l 

al-3 

al3h 

al3l 

Only the value set to the “

ins

: Temperature Input Shift” parameter is 

applied to the entire temperature input range. When the process value is 

200 °C, the process value is treated as 201.2 °C after input shift if the 

input shift value is set to 1.2 °C. 

The process value is treated as 198.8 °C after input shift if the input shift 

value is set to –1.2 °C. 

*2: Error shown only for "Process value / Set point". Not shown for other status.  

If the input value exceeds the display limit (-1999 to 9999), though it is within the control 
range, 

[[[[ 

will be displayed under -1999 and 

]]]]

 above 9999. Under these conditions, 

control output and alarm output will operate normally.Refer to E5CN/E5AN/E5EN/E5GN 
Digital Controllers User's Manual Basic Type (Cat. No. H156) for details of control range. 

Check the setting of the Input Type parameter, 

check the input wiring, and check for broken or 

shorts in the temperature sensor.   

Turn the power OFF then back ON again. If the 

display remains the same, the controller must be 

repaired. If the display is restored to normal, then 

a probable cause can be external noise affecting 

the control system. Check for external noise. 

After the correction of A/D converter error, turn the 

power OFF then back ON again. If the display 

remains the same, the controller must be repaired. 

If the display is restored to normal, then a 

probable cause can be external noise affecting the 

control system. Check for external noise. 

No.1 display 

Meaning 

A/D converter error  

*2 

Memory error 

Input error 

*2 

s.err

 

(S. Err) 

e111 

(E111) 

Action 

OFF 

Alarm 

Control 

output 

Status at error 

OFF 

OFF 

Operates  

as above the  

upper limit. 

OFF 

OFF 

e333

 (E333) 

ON 

OFF 

SP 

ON 

OFF 

SP 

ON 

OFF 

SP 

ON 

OFF 

SP 

L H 

ON 

OFF 

SP 

ON 

OFF 

SP 

ON 

OFF 

SP 

ON 

OFF 

ON 

OFF 

ON 

OFF 

ON 

OFF 

ON 

OFF 

ON 

OFF 

ON 

OFF 

L H 

ON 

OFF 

SP 

L  H 

ON 

OFF 

SP 

SP 

ON 

OFF 

SP 

ON 

OFF 

ON 

OFF 

Alarm output function 

Positive alarm value (X)  Negative alarm value (X) 

Alarm type 

Setting 

No alarm function 

Deviation upper/lower limit 

standby sequence ON 

Absolute value upper limit 

Absolute value lower limit 

Absolute value upper limit 

standby sequence ON 

Absolute value lower limit 

standby sequence ON 

LBA (only for alarm 1) 

Deviation lower limit  

standby sequence ON 

Deviation upper limit 

standby sequence ON 

Deviation upper/lower range 

Deviation upper limit 

Deviation upper/lower limit 

Deviation lower limit 

Output off 

Vary with "L", "H" values 

Vary with "L", "H" values 

Vary with "L", "H" values 

-200 to 850 (°C) 
-199.9 to 500.0 (°C) 
0.0 to 100.0 (°C) 
-199.9 to 500.0 (°C) 
0.0 to 100.0 (°C) 
-200 to 1300 (°C) 
-20.0 to 500.0 (°C) 
-100 to 850 (°C) 
-20.0 to 400.0 (°C) 
-200 to 400 (°C) 
-199.9 to 400.0 (°C) 
-200 to 600 (°C) 
-100 to 850 (°C) 
-200 to 400 (°C) 
-199.9 to 400.0 (°C) 
-200 to 1300 (°C) 
0 to 1700 (°C) 
0 to 1700 (°C) 
100 to 1800 (°C) 
0 to 90 (°C) 
0 to 120 (°C) 
0 to 165 (°C) 
0 to 260 (°C) 

/-300 to 1500 (°F) 
/-199.9 to 900.0 (°F) 
/0.0 to 210.0 (°F) 
/-199.9 to 900.0 (°F) 
/0.0 to 210.0 (°F) 
/-300 to 2300 (°F) 
/0.0 to 900.0 (°F) 
/-100 to 1500 (°F) 
/0.0 to 750.0 (°F) 
/-300 to 700 (°F) 
/-199.9 to 700.0 (°F) 
/-300 to 1100 (°F) 
/-100 to 1500 (°F) 
/-300 to 700 (°F) 
/-199.9 to 700.0 (°F) 
/-300 to 2300 (°F) 
/0 to 3000 (°F) 
/0 to 3000 (°F) 
/300 to 3200 (°F) 
/0 to 190 (°F) 
/0 to 240 (°F) 
/0 to 320 (°F) 
/0 to 500 (°F) 

Setting range 

Input type 

Platinum 

resistance 

thermometer 

Input 

 

Pt100 

JPt100 

Thermocouple 

 
 
 
 
 
 
 
 
 
 
 

Infrared 

Thermosensor 

ES1B 

 

Analog input 

 

Thermocouple 

 

 

 



 




 

   Use the following ranges for scaling:  
   -1999 to 9999,-199.9 to 999.9 

  0 to 2300 (°C)            /0 to 3200 (°F) 
  0 to 1300 (°C)            /0 to 2300 (°F) 

 10 -70   

   60 -120°C 
 115 -165°C 
 140 -260°C 

 0 to 50mV 

 

PL 

II 

Setting 










10 
11 
12 
13 
14 
15 
16 
17 
18 
19 
20 
21 
22 
23 

 

24 
25 

Use the following ranges for scaling: -1999 
 to 9999, -199.9 to 999.9, -19.99 to 99.99, 
-1.999 to 9.999 

Analog  

input type 

Setting range 

Input type 

Current input 

Voltage input 

Input 

4 to 20mA 
0 to 20mA 

1 to 5V 
0 to 5V 

0 to 10V 

 • The default is 

0

Setting 





  *The default is“5”. 
  *

s.err

 will be displayed when a platinum resistance thermometer is mistakenly connected while input 

type is not set for it. To clear the 

s.err

 display, correct the wiring and cycle the power supply. 

When an error has occurred, the No.1 display shows the error code. Take 
necessary measure according to the error code, referring the table below. 

*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for 

different types of alarm. These are indicated by the letter "L" and "H".  

 • The default alarm type is "2" 

10 

11 

12 

13 

*1 

*1 

*1 

Thermocouple/platinum-resistance thermometer (multi-input) 

PV Change Rate Alarm 

Input Type 

Alarms 

Error display (troubleshooting) 

Initial Setting Level 

Operation Level 

Protect Level 

Adjustment Level 

alh1 

0.2 

alt2 

alh2 

0.2 

alt3 

alh3 

0.2 

tr-t 

off 

tr-h 

100.0 

tr-l 

0.0 

o1-t 

4-20 

sqr 

off 

The setting data for the E5EN-

@

3HT/L is shown here as an example.

Check the wiring before turning ON the power supply.  

Dimensions (mm) 

Mounting 

bracket 

Solderless terminal size: M3.5 

Terminal cover: 

(Model: E53-COV16) 

USB-Serial Conversion Cable  

(Sold Separately) 

(E58-CIFQ1) 

In the pack: 

 • Main unit 

 • Watertight packing 

 • Two mounting brackets 

 • Instruction manual 

 • Terminal cover 

    (Provided only for models  

    with "-500" suffix.) 

* The internal mechanisms can be drawn out for maintenance without removing terminal wiring. 

* Do not remove the terminal block. Doing so may result in failure or malfunction. 

* A Setup Tool port is provided on the bottom of the product. Use this port to connect a personal computer to the 

product when using the Setup Tool. E58-CIFQ1 USB-Serial Conversion Cable is required to connect the personal 

computer to the product. (Do not use the product with the USB-Serial Conversion Cable left permanently 

connected.) 

  Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods. 

Watertight  

packing 

Terminal  

cover 

96 

48 

112 

79.2 

78 

91 

44 