SELECTING A SCALE RANGE
Use the rotary DIP switch to select the temperature scale range.
The tables below show the switch setting number for each range.
The temperature indication range is the set temperature range
(full scale)
±
10%, unless otherwise noted.
If the set temperature is shifted outside of changing the scale
range, the set temperature is displayed. It is then automatically
changed to the maximum or minimum value of the newly set
temperature scale range.
If the alarm value is shifted outside the temperature scale range
as a result of changing the scale range, it is automatically
changed to the maximum value of the newly set scale range.
Thermocouple Input Type
Thermocouple input models are factory-set to switch position 2
for a temperature range of 0
°
to 400
°
, using a type K
thermocouple.
Switch setting
0
1
2
3
4
5
6
6
7
8
9
Temperature range
0 to 200
0 to 300
0 to 400
0 to 500
0 to 600
0 to 999
0 to 999
0 to 200
0 to 300
0 to 400
0 t0 500
Scale indication
°
C
°
C
°
C/
°
F
°
C/
°
F
°
C/
°
F
°
C/
°
F
°
F
°
C
°
C
°
C/
°
F
°
C/
°
F
Unit of measure
1
°
C or F
Platinum RTD Type
Platinum RTD input models are factory-set to switch position 3
for a temperature range of 0.0
°
to 99.9
°
.
Switch setting
0
1
2
3
4
5
6
7
8
Temperature range
–50 to 50
0.0 to 50.0
–20 to 80
0.0 to 99.9
0 to 200
0 to 300
0 to 400
0 to 600
0 to 800
Scale indication
°
C
°
C
°
C
°
C/
°
F
°
C/
°
F
°
C
°
C/
°
F
°
F
°
F
Unit of measure
1
°
C or F
0.1
°
C or F
1
°
C or F
0.1
°
C or F
1
°
C or F
Note: 1. Do not set the selector switch to position 9. This will cause error message “FFF” or “–––” to be displayed.
2. When changing scale ranges where the unit of measure changes 1
°
to 0.1
°
or vice versa, the set temperature also changes to
reflect the unit of measure. For example, with a set temperature of 100
°
, a change from a scale range with 1
°
resolution to 0.1
°
makes the set temperature 10
°
; with a set temperature of 15
°
, a change in scale range resolution from 0.1
°
to 1
°
makes the set
temperature 150
°
.
Thermistor Input Type
Thermistor input models are factory-set to switch position 0 for a
temperature range of –50
°
to 50C
°
.
Switch setting
0
1
2
3
4
5
6
7
8
9
Temp. range
–50 to 50
0 to 100
50 to
150
100 to
200
150 to
300
–50 to 100
0 to 200
100 to
300
200 to
400
300 to
600
Scale indication
°
C
°
F
Unit of measure
1
°
C or F
Note: 1. The temperature indication range for a setting scale of –50
°
to 50
°
C is –50
°
to 60
°
C. It is the full scale
±
10% with the other set-
ting scale ranges.
2. With a temperature range, such as 50
°
to 150
°
C, exceeds the factory-set range, the indication unit is automatically adjusted to
the minimum value. The set temperature is displayed upon power application.