![Omron E5CS Manual Download Page 4](http://html.mh-extra.com/html/omron/e5cs/e5cs_manual_744346004.webp)
E5CS-X
E5CS-X
40
Connections
100 to 240 VAC, 50/60 Hz
20 mA, 12 VDC
Alarm output
Thermistor input type
Platinum RTD input type
Thermocouple input type
Contact output type
Voltage output type
Operation
J
SETTINGS BEFORE APPLYING POWER
Note:
Always turn off the power supply to the temperature control-
ler before changing any switch settings.
Before applying power to the temperature controller, set the
following selector switches to specify the temperature range,
functions and alarm mode.
J
ACCESS TO INTERNAL SWITCHES AND
SELECTORS
Push the tab on the underside of the front panel as you draw out
the internal mechanism from the housing. The temperature range
selector, and the alarm mode selector must all be set. A
protection switch can also be set to protect settings. The
following diagrams show the locations of these switches on the
internal mechanism.
Alarm mode selector switch
Protection switch
Right side view
Control mode selector switch
Left side view
Temperature range selector switch
Select the desired temperature range by using the temperature
range selector switch (rotary DIP type). The other rotary DIP
switch is used to select one of eight alarm functions. Be sure the
set temperature and alarm values are within the new range.
Otherwise, the temperature controller automatically shifts these
values to the maximum or minimum of the newly-set temperature
range.
The protection switch may be used in conjunction with the front
panel “hidden key” to prevent unauthorized changes to
temperature settings. The switch is ON when it is pushed inwards
in the direction of the white arrow.
The function selector switch is a 8-pin in-line DIP switch on the
other side of the internal mechanism. Use it to select ON/OFF or
PID control action, proportional period, control output, input shift
function, temperature sensor input standard and scale indication
for dual-scale temperature ranges.