background image

Operation indicators

• SUB1: Auxiliary output 1 indicator
   Lit when the function assigned to 

auxiliary output 1 is ON. 

• SUB2: Auxiliary output 2 indicator
   Lit when the function assigned to 

auxiliary output 2 is ON.

• SUB3: Auxiliary output 3 indicator
   Lit when the function assigned to 

auxiliary output 3 is ON.

• HA: Heater burnout alarm/Heater short

alarm/Heater overcurrent alarm indicator 

Lit when a heater burnout alarm, heater 
short alarm, or heater overcurrent alarm 
has occurred.

• OUT1: Control output 1 indicator

Lit when control output 1 is ON and not lit 

when it's OFF.

For a current output, lit except for a 0% output. 

• OUT2: Control output 2 indicator

Lit when control output 2 is ON and not lit 

when it's OFF. 

• STOP: control stop indicator

Lit when event input or “Run/Stop ”is stopped 

during operation.

During control stop, functions other than 

control output are valid.

• CMW: communications writing enable/ disable 

indicator

Lit when communications writing is 

“enabled” and is out when it is “disabled”.

•  Insert the controller through the hole in the panel. Push the adapter on from the rear 

and fasten temporarily, removing any gap between the controller, panel and adapter. 

Finally, secure two fixing screws alternately keeping the torque to between 0.29 to 

0.39  N•m.  

•  Make sure that the surrounding temperature does not exceed the allowable operating 

temperature given in the specifications especially when two or more controllers are 

mounted.

.ni

06

45

54

+0.6

0

6.

0

+

0

6.

0

+

0

When waterproofing is required, be sure to mount the 

controller separately. 

Attach the waterproof packing from the terminal side 

and then insert the controller to the panel. 

Recommended panel thickness is 1 to 5 mm.

(48 x number of units - 2.5)

+1

0

54

Individual mounting (mm) Side-by-side mounting (waterproof not possible) (mm)

Indicates a potentially hazardous situation which, if 

not avoided, is likely to result in minor or moderate 

injury or property damage. Read this manual 

carefully before using the product.

Mode key

Press this key to change the 

contents of the display.

Press this button for 1 s or 

longer for reverse scroll.

E5CN-H

Solderless terminal size: M3.5
Terminal cover: E53-COV17
USB-Serial Conversion Cable 
(Sold Separately)(E58-CIFQ1)

5307507- 4D

Default setting : 0

    : Can be displayed and changed
    : Can be displayed
× : Display or shifting to another level 
 

is not possible.

Operation level

Adjustment level

Process value
PV/SP
Others

Level

Set value

0

1

×

2

×
×

3

×
×

For detailed operating instructions, please refer to the E5CN-H/E5AN-H/E5EN-H 
Digital Controllers User's Manual Advaced Type (Cat. No. H157). 
Significance of WARNINGs and CAUTIONs

Instruction Manual

Thank you for purchasing the OMRON E5CN-H Digital Controller.  

This manual describes the functions, performance, 

and application methods needed for optimum use of 

the product.

Please observe the following items when using the product.

• This product is designed for use by qualified personnel with 

  a knowledge of electrical systems.

• Before using the product, thoroughly read and understand 

this manual to ensure correct use.

• Keep this manual in a safe location so that it is available for 

reference whenever required.

OMRON CORPORATION

 ©All Rights Reserved

*1: Upper and lower limits can be set for parameters 1, 4 and 5 to provide for 

different types of alarm. These are indicated by the letter "L" and "H". 

  • The default alarm type is "2"

In the pack:

  *Main unit

  *Watertight packing

  *Adapter

  *Instruction manual

  *Terminal cover (Provided only for models with “-500” 

     suffix only)

Suitability for Use

OMRON shall not be responsible for conformity with any standards, codes, or regulations that 

apply to the combination of the products in the customer's application or use of the product.

Take all necessary steps to determine the suitability of the product for the systems, machines, 

and equipment with which it will be used.

Know and observe all prohibitions of use applicable to this product.

NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE 

OR PROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN 

DESIGNED TO ADDRESS THE RISKS, AND THAT THE OMRON PRODUCT IS PROPERLY 

RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT 

OR SYSTEM.

See also Product catalog for Warranty and Limitation of Liability.

Power supply voltage 

100 to 240 VAC, 50/60 Hz or 

                                                     24 VAC, 50/60 Hz 

/

24 VDC

Operating voltage range 

85 to 110% of the rated voltage

Power consumption                     Approx. 8.5 VA (100 to 240 VAC)

                                                     Approx. 5.5 VA (24 VAC) /

                                                     Approx. 3.5 W (24 VDC)

Indication accuracy 

Thermocouple:

(Ambient temperature: 23°C) 

(±0.1 % of indication value or ±1°C,

                                                    whichever is greater) ±1 digit max.

                                                      Platinum resistance thermometer:

                                                    (±0.1 % of indication value or ±0.5°C,

 

whichever is greater) ±1 digit max.

 Analog 

input:

 

±0.1 % FS ±1 digit max.

Event input 

Output current: approx. 7 mA per contact.

  Contact input 

ON:1 k

Ω

 max., OFF: 100 k

Ω

 min.

  No-contact input 

ON: residual voltage 1.5 V max.,

 

OFF: leakage current 0.1 mA max.

Control output 1 

Relay output  :SPST-NO

 

12 VDC, 21 mA 

 Current output: 4 to 20 mADC, 0 to 20mADC

 Load: 

600 

Ω

 max.

 

Electrical life of relay:

 100,000 

operations

 

(Long-life model: 1 million operations)

Control output 2 

Voltage output (for driving SSR): 12 VDC, 21 mA

Control method 

ON/OFF or 2-PID control

Auxiliary outputs 

Relay outputs: 250 VAC, 

 

3 A (resistive load), Electrical life of relay:

 100,000 

operations

Ambient temperature 

-10 to 55 °C

 (Avoid 

freezing 

or 

condensation)

Ambient humidity 

RH25 to 85%

Storage temperature 

-25 to 65 °C

 (Avoid 

freezing 

or 

condensation)

Altitude Max. 

2,000m

Recommended fuse 

T2A, 250 VAC, time-lag,

 low-breaking 

capacity

Weight 

Approx. 150 g (main unit only)

Degree of protection 

Front panel: IP66

 

Rear case: IP20, Terminal section: IP00

Installation environment 

Installation category II, pollution

 

degree 2 (as per IEC61010-1)

Memory protection 

Non-volatile memory 

 

(Number of write operations: 1,000,000)

*2: Error shown only for "Process value / Set point". Not shown for other status. 

When an error has occurred, the No.1 display shows the error code. Take 

necessary measure according to the error code, referring the table bellow.

CAUTION

CH1

If the input value exceeds the display limit ( -19999 to 32400), though it is within the control 
range, 

[[[[

will be displayed under  -19999 and        

]]]]

 above 32400. Under these conditions, 

control output and alarm output will operate normally.
Refer to E5CN-H/E5AN-H/E5EN -H User's Manual Advanced Type (Cat. No. H157) for details of control range.

Set value

0
1
2

×

×

×
×

Initial setting

level

Communications 

setting level

Advanced function 

setting level

Default setting : 0

    : Change to 

 other 

levels 

 possible

× : Change to 

 other 

levels 

 not 

possible

EN

Safety Precautions

Terminal 

cover

Watertight 

packing

Adapter

°

C /

°

F : temperature unit 

The temperature unit is displayed 

when the displayed value is a 

temperature.
When this parameter is set to“ 

°

C”,

C

” is displayed, and when set to 

°

F”, “

F

 ”is displayed.

This flashes while ST (Self-Tuning) is 

activated. 

         :Protection indicator

Lit when Setting Change Protect is
ON (disables the Up and Down Keys). 

MANU: Manual output indicator

Lit when the Auto/Manual Mode is set 

to Manual Mode. 

Level key

Use this key to change levels:

Press the     key and the      key

together for at least 3 seconds to 
switch to protect level.

Up and Down keys

Use the keys to change the values 

displayed  on the No.2 display.

Each press of      key increments or advances 

the values displayed on the No.2 display.

Each press of     key decrements or returns 

the values displayed on the No.2 display.

No.1 display

Process value or set data symbol

No.2 display

Set point, set data read-out value or 
changed input value 

* The main unit can be removed for maintenance without disconnecting the terminal  wiring.

* Do not remove the terminal block. Doing so may result in failure or malfunction.

* A Setup Tool port is provided on the bottom of the product. Use this port to connect a personal computer to the 

product when using the Setup Tool. E58-CIFQ1 USB-Serial Conversion Cable is required to connect the personal  

computer to the product. (Do not use the product with the USB-Serial Conversion Cable left permanently connected.)

Refer to the instruction manual provided with the USB-Serial Conversion Cable for details on connection methods. 

Turn the power OFF then back ON again. If the 

display remains the same, the controller must be 

repaired. If the display is restored to normal, then 

a probable cause can be external noise affecting 

the control system. Check for external noise.

After the correction of A/D converter error, turn the 

power OFF then back ON again. If the display 

remains the same, the controller must be repaired. 

If the display is restored to normal, then a 

probable cause can be external noise affecting the 

control system. Check for external noise.

No.1 display

Meaning

A/D converter error 

*2

Memory error

Input error

*2

s.err

(S. Err)

e111

(E111)

Action

OFF

Alarm

Control

output

Status at error

OFF

OFF

Operates 

as above the 

upper limit.

OFF

OFF

e333

 (E333)

OMRON EUROPE B.V.

Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands
 Phone 31-2356-81-300
 FAX 31-2356-81-388

OMRON ELECTRONICS LLC

One Commerce Drive Schaumburg, IL 60173-5302 U.S.A   
    Phone 1-847-843-7900
 FAX 1-847-843-7787

OMRON ASIA PACIFIC PTE. LTD.

No. 438A Alexandra Road # 05-05/08 (Lobby 2),
Alexandra Technopark, Singapore 119967
 Phone 65-6835-3011
 FAX 65-6835-2711

Key to Warning Symbols

Dimensions

Names of parts on front panel

Input type

Error display (trouble shooting)

Installation

Specifications

Protection function

Protection function, to prevent unwanted settings, restricts the setting items to be used 
or designates if operation of the key is valid or invalid. 

Operation / Adjustment protection

The following table shows the relationship between settings and protect limits related to 

Operation level and Adjustment level.

Initial setting/Communications protection

This protect level restricts movement to the initial setting level, 

communications setting level and advanced function setting level.

Setting change protection

Setting changes by key operation are restricted. 

OFF

off

: Setting can be changed by key operation 

ON

on

    : Setting cannot be changed by key operation (“       ” will light.) 

(Protect level settings can all be changed.)

Communications Manual  Advanced Type  (Cat. No. H159). 

For details about advanced function setting level,bank setting level,pid setting level
or manual control level,refer to E5CN-H/E5AN-H/E5EN-H Digital Controllers
User's  Manual  Advanced Type (Cat. No. H157).  

For communications details, refer to E5CN-H/E5AN-H/E5EN-H Digital Controllers 

Other functions

Operation menu

Wiring

*

AT in Adjustment level

    Designate "

at-2

: 100% AT execute" or 

    "

at-1

: 40%  AT execute" to execute AT and

 "

off

: AT cancel" 

    to cancel AT.

at

” flashes

“AT cancel”

Also when AT execution ends, the 

display automatically returns to “

off

”.           

at

off

at

at-2

AT (auto-tuning)

“100%AT Execute”

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

*6

in-t

5

in-h

100

in-l

0

dp

0

d-u

c

sl-h

sl-l

cntl

s-hc

stnd

st

on

ptrn

off

cp

20

c-cp

20

orev

or-r

alt1

2

alt2

2

tr-t

off

tr-h

100.0

tr-l

0.0

o1-t

4-20

Alarm 1 Hysteresis

*6

alh1

0.2

Alarm 2 Hysteresis

*6

alh2

0.2

Extraction of Square Root Enable
(Only when analog input is set)

*6

sqr

off

Input Type *3

Scaling Upper Limit
 (only when setting analog input)

Scaling Lower Limit 
(only when setting analog input)

Decimal Point 
(only when setting analog input)

Temperature Unit

SP Upper Limit

SP Lower Limit

PID/ONOFF
In ON/OFF control = 

onof

In 2-PID control = 

pid

Standard or Heating/Cooling
Standard control = 

stnd

Heating and cooling control = 

h-c

(Select standard control or heating

         and cooling control as required) 

Control Period (Heating)
(Unit: Seconds)

Alarm 2 Type: Specified Models Only 

Alarm 1 Type: Specified Models Only 

Control Period (Cooling)
(Unit: Seconds)

°C=

c

°F=

f

(C stands for Celsius, F for Fahrenheit)

ST (Self-Tuning)
ST ON  = 

on

ST OFF = 

off

Direct/Reverse Operation

In Reverse operation (Heating) =

or-r

In Direct operation (Cooling) = 

or-d

*3

*4

*3

*4

*3: Refer to the adjoining tables for details of input types and alarm types. 

*4: Applicable only to models with alarm functions.

*5: Operation is stopped when moved to the initial setting level.
 

(control/alarm are both stopped.)

*6: The grayed-out setting items may not be displayed according to the models and setting.

Transfer Output Type

Transfer Output Upper Limit

Transfer Output Lower Limit

Linear Current Output

Only the value set to the 

ins

: temperature input shift parameter is 

applied to the entire temperature input range. When the process 

value is 200

°

C, the process value is treated as 201.2

°

C after input 

shift if the input shift value is set to 1.2

°

C.

The process value is treated as 198.8

°

C after input shift if the input 

shift value 

is set to -1.2°C.

Program Pattern

Initial setting level enables users to specify their preferred

operating conditions 

 (input type, alarm type, control method, etc.)

Hold     down

for at least

1 second

POWER  ON

Operation stopped.

(Control/alarm are both stopped.)

*5

Settings shown above is the parameters displayed for the models without options. 

(Options include heater burnout detection, communications, event inputs, and 

control output 2.) 

Initial Setting Level

Adjustment Level

Connections

(The applicability of the electric terminals varies with the type of machine.)

Auxiliary output

(Relay outputs)

+

-

A

B

B

-

+

+

-

V

Auxiliary output

1

Input power supply

ut

Control outpu

1

Auxiliary output 

(Relay outputs)

250VAC 3A 

(resistive load)

Auxiliary output2

• 100-240V AC Type

• 24V AC/DC Type (no polarity)

DO NOT

USE

+

-

mA

DO NOT

USE

DO NOT

USE

11

12

13

14

15

B(+)

A(-)

RS-485

DO NOT

USE

Communications

(RS-485)

and

Control output 2

((

))

+

-

11

12

13

14

15

DO NOT

USE

Transfer output

+

-

transfer

 output

+

-

11

12

13

14

15

EV1

EV2

Event Inputs and

+

-

11

12

13

14

15

CT2

CT1

B(+)

A(-)

RS-485

Communications

(RS-485)

and

2 CTs

((

11

12

13

14

15

CT2

CT1

Control output 2

and 2 CTs 

+

-

11

12

13

14

15

EV1

EV2

Event Inputs and

Control output 2

p

+

-

11

12

13

14

15

Communications

(RS-232C)

and CT

RS-232C

SD

RD

SG

CT1

A heater burnout alarm, Heater Short 
alarm, heater overcurrent alarm, or input 
alarm is output to the output to which the 

alarm 1 function is assigned.

Relay output

250VAC 3A

 (resistive load)

Voltage output

(for driving SSR)

12VDC 21mA

Current output

0-20mADC

Load 600

Ω

  max

.

Linear voltage output

0-10VDC

4-20mADC

Load: 1 k

Ω

 min.

Control output 1

Control output 2

trol outpu

 12VDC,21 mA

DC,21 m

ppp

Control output 222

ntrol outpu

 12VDC,21 mA

A

VDC,21 m

ppp

Control output 2

rol output

12VDC,21 mA

DC,21 m

ppp

*1

*1

*1

 *The default is“5”.

  *

s.err

 will be displayed when a platinum resistance thermometer is mistakenly connected while 

input type is not set for it. To clear the 

s.err

 display, correct the wiring and cycle the power supply.

Alarms

-200.0 to  850.0(°C)
-199.9 to  500.0(°C)
    0.0 to  100.0(°C)
-199.9 to  500.0(°C)
    0.0 to  100.0(°C)
-200.0 to 1300.0(°C)
 -20.0 to  500.0(°C)
-100.0 to  850.0(°C)
 -20.0 to  400.0(°C)
-200.0 to  400.0(°C)
-199.9 to  400.0(°C)
-200.0 to  600.0(°C)
-100.0 to  850.0(°C)
-200.0 to  400.0(°C)
-199.9 to  400.0(°C)
-200.0 to 1300.0(°C)
    0.0 to 1700.0(°C)
    0.0 to 1700.0(°C)
  100.0 to 1800.0(°C)
    0.0 to 2300.0(°C)
    0.0 to 1300.0 (°C)
 -50.00 to 200.00(°C)
 -50.00 to 200.00(°C)
 -50.00 to 200.00(°C)
 -50.00 to 200.00(°C)

/ -300.0 to 1500.0  (°F)
/ -199.9 to  900.0 (°F)
/     0.0 to  210.0 (°F)
/ -199.9 to  900.0 (°F)
/    0.0 to  210.0 (°F)
/-300.0 to 2300.0 (°F)
/    0.0 to  900.0 (°F)
/-100.0 to 1500.0 (°F)
/    0.0 to  750.0 (°F)
/-300.0 to  700.0 (°F)
/-199.9 to  700.0 (°F)
/-300.0 to 1100.0 (°F)
/-100.0 to 1500.0 (°F)
/-300.0 to  700.0 (°F)
/-199.9 to  700.0 (°F)
/-300.0 to 2300.0 (°F)
/    0.0 to 3000.0 (°F)
/    0.0 to 3000.0 (°F)
/  300.0 to 3200.0 (°F)
/    0.0 to 3200.0 (°F)
/    0.0 to 2300.0 (°F)
/ -50.00 to 200.00(°F)
/ -50.00 to 200.00(°F)
/ -50.00 to 200.00(°F)
/ -50.00 to 200.00(°F)

K

J

T

E

L

U

N
R
S
B
W

PL

II

K

J

T

Pt100

4 to 20mA
0 to 20mA

1 to 5V
0 to 5V

0 to 10V

0
1
2
3
4
5
6
7
8
9

10

11
12
13
14
15
16
17
18
19
20
21
22

23
24

25
26
27
28
29

One of the following ranges is used depending on scaling.

  :

 -19999 to 32400

 -1999.9 to 3240.0

 -199.99 to 324.00

 -19.999 to 32.400

Input type

Platinum

resistance

thermometer

Input

Pt100

JPt100

Thermocouple

Platinum

resistance

thermometer

Current input

Voltage input

Setting

Input Setting range

RSP absolute value upper limit

RSP absolute value lower limit

Vary with "L", "H" values

Vary with "L", "H" values

Vary with "L", "H" values

X

ON

OFF

SP

X

ON

OFF

SP

ON

OFF

SP

X

X

ON

OFF

SP

L H

ON

OFF

SP

X

ON

OFF

SP

X

ON

OFF

SP

X

ON

OFF

0

ON

OFF

X

0

X

ON

OFF

0

X

ON

OFF

0

ON

OFF

X

0

X

ON

OFF

0

L H

ON

OFF

SP

L H

ON

OFF

SP

SP

X

ON

OFF

SP

ON

OFF

X

ON

OFF

X

0

14

15

X

ON

OFF

0

X

ON

OFF

0

ON

OFF

X

0

ON

OFF

X

0

ON

OFF

X

0

1

0

2

3

4

5

6

7

8

9

10

11

12

13

Alarm output function

Positive alarm value (X) Negative alarm value (X)

Alarm type

Setting

No alarm function

Deviation upper/lower limit

standby sequence ON

Absolute value upper limit

Absolute value lower limit

Absolute value upper limit

standby sequence ON

Absolute value lower limit

standby sequence ON

LBA (only for alarm 1)

Deviation lower limit 

standby sequence ON

Deviation upper limit

standby sequence ON

Deviation upper/lower range

Deviation upper limit

Deviation upper/lower limit

Deviation lower limit

Output off

PV change rate alarm

pid

Move to Advanced Function Setting Level

*6

amov

0

Moving to the next level is 
possible when the password 
(-169) is input. 

init

off

Manual Reset Value

(Unit: %)

Hysteresis
(Cooling)

Soak Time

SP Ramp Set Value

MV Upper Limit

MV Lower Limit

Hysteresis
(Heating)

*6

*6

*6

*6

*6

*6

*6

hys

1.0

chys

1.0

soak

1

sprt

off

ol-h

105.0

ol-l

-5.0

of-r

50.0

Wait Band

*6

wt-b

off

MV Change Rate Limit

*6

orl

0.0

Extraction of Square 
Root Low-cut Point

*6

sqrp

0.0

Adjustment level is for entering set 

values and shift values for control.

Temperature Input Shift
(Unit: °C or  °F)

Upper Limit Temperature 

Input Shift Value

when 2 point input shift 

is selected

Lower Limit Temperature 

Input Shift Value

when 2 point input shift 

is selected

Adjustment Level

Proportional Band

Integral Time
(Unit: secs)

AT Execute / Cancel

100%AT Execute 

at-2

40%AT Execute

at-1

l.adj

at

off

ins

0.0

insh

0.0

insl

0.0

p

8.0

i

233.0

Derivative Time
(Unit: secs)

d

40.0

Dead Band

c-db

0.0

Cooling Coefficient

c-sc

1.00

*6

*6

*6

*6

*6

*6

*6

*6

*6

d.bnk

0

d.pid

1

Bank Setting Level

PID Setting Level

Press

(less than 

 1 second)

Press

(less than 

 1 second)

Display PID 
Selection

Display Bank
Selection

Press

(less than 

 1 second)

Press

(less than 

 1 second)

Operation Level

Hold     and 

M

 keys

down for at least

3 seconds

Hold    and 

M

 keys

down for at least 

1 second

*6

*6

*6

*6

*6

*6

*6

*6

25.0

0.0

sp-m

0.0

prst

rset

*6

sktr

0

*6

r-s

run

al-1

0.0

al1h

0.0

al1l

0.0

al-2

0.0

al2h

0.0

al2l

0.0

*6

b

a

n

k

0

PV/SP

s.err

 is displayed when 

connected sensor is 

different from input type.

Bank No.

Set Point During 

SP Ramp

Program Start

Soak Time Remain

When control start  =

run

When control stop = 

stop

RUN/STOP

Alarm Value 1 *4

Alarm Value Upper Limit 1

*4

Alarm Value Lower Limit 1

*4

Alarm Value 2 *4

Alarm Value Upper Limit 2 

*4

Alarm Value Lower Limit 2

*4

Operation level should normally 

be used during operations. 

oapt

0

icpt

0

wtpt

off

prlp

0

Protect Level

Operation / Adjustment
Protect

Initial Setting / 

Communication Protect

Setting Change Protect

Password to Move 
to Protect Level

Restricts which settings can be displayed 
or changed, and restricts change by key 
operation.

Advanced Function 

Setting Level

Parameter
Initialization

Hold     down

for at least

1 second

(No.1display flushes, 
then the control stops.)

Hold     down

for at least

3 seconds

1300.0

-200.0

Transfer output

48

58

6

44.8

48.8

1.5

78

91

25.0

0.0

Dimensions (mm)

CAUTION

Do not touch the terminals while power is being supplied. 

Doing so may occasionally result in minor injury due to electric shock.
Do not allow pieces of metal, wire clippings, or fine metallic shavings or filings from installation to 

enter the product. Doing so may occasionally result in electric shock, fire, or malfunction.
Do not use the product where subject to flammable or explosive gas. Otherwise, minor injury from 

explosion may occasionally occur. 
Never disassemble, modify, or repair the product or touch any of the internal parts. Minor electric 

shock, fire, or malfunction may occasionally occur. 

CAUTION - Risk of Fire and Electric Shock

a) This product is UL listed as Open Type Process Control Equipment. It must be mounted in an enclosure that 

does not allow fire to escape externally.

b) More than one disconnect switch may be required to de-energize the equipment before servicing. 
c) Signal inputs are SELV, limited energy.
d) Caution: To reduce the risk of fire or electric shock, do not interconnect the outputs of different Class 2 circuits.
If the output relays are used past their life expectancy, contact fusing or burning may occasionally occur. Always 
consider the application conditions and use the output relays within their rated load and electrical life expectancy. 
The life expectancy of output relays varies considerably with the output load and switching conditions. 
Tighten the terminal screws to between 0.74 and 0.90 N•m. Loose screws may occasionally result in fire. 
Set the parameters of the product so that they are suitable for the system being controlled. If they are not suitable, 
unexpected operation may occasionally result in property damage or accidents. 
A malfunction in the  Digital Controller may occasionally make control operations impossible or prevent 
alarm outputs, resulting in property damage. To maintain safety in the event of malfunction of the Digital 
Controller, take appropriate safety measures, such as installing a monitoring device on a separate line. 

Warning Symbols

Digital Controller

 

Linear voltage output   0-10VDC

  

 

Load: 1 k   min.

Ω

Transfer output

 4 to 20 mA DC, Load : 600

Ω

max. 

(Load: 600

Ω

 max.)

4-20 mADC

Control output 2

l output 2

12VDC,21 mA

C,21 mA

pppp

(Load: 600

Ω

 max.)

4-20 mADC

transfer

 output

 Voltage 

output 

(for 

driving 

SSR): 

250VAC, 3A(resistive load)

OMRON Corporation

Shiokoji Horikawa, Shimogyo-ku, Kyoto 600-8530 JAPAN

The E5

@

N-H is set for a K thermocouple (input 

type of 5) by default. If a different sensor is used, 

an input error (

s.err

) will occur. Check the setting 

of the Input Type parameter.

•  A heater burnout alarm, heater short alarm, heater overcurrent alarm, or input alarm is output to the output to which the alarm 1 functi on is assigned.

•  Since the voltage output (control output) is not electrically insulated from the internal wiring, one or other of the control output terminals must be left 

unearthed when using an earthed thermocouple thermometer. (Connection makes measurements unreliable due to sneak currents.)

•  The last character of the lot number “R” indicates that reinforced insulation is provided between input power supply, relay outputs, and between other 

terminals. 

Conformance to EN/IEC Standards

This is a class A product. 

In residential areas it may cause radio 

interference, in which case the user may 

be required to take adequate measures 

to reduce interference.

Conformance to Safety Standards

Reinforced insulation is 

provided between input power 

supply, relay outputs, and 

between other terminals.

Check the wiring before turning ON the power supply. 

Check the setting of the Input Type parameter, 

check the input wiring, and check for broken or 

shorts in the temperature sensor.  

Be sure to observe the following precautions to prevent operation failure, malfunction, or adverse affects on the 

performance and functions of the product. Not doing so may occasionally result in unexpected events.

Use the product within specifications.

(1)  The product is designed for indoor use only. Do not use the product outdoors. Do not use or store the product 

in any of the following locations.

 

 •Places subject to splashing liquid or oil atmosphere.

 

 •Places subject to direct sunlight.

 

 •Places subject to dust or corrosive gas (in particular, sulfide gas and ammonia gas).

 

 •Places subject to intense temperature change.

 

 •Places subject to icing and condensation.

 

 •Places subject to vibration and large shocks.

(2)  Use/store within the rated temperature and humidity ranges.

 

Provide forced-cooling if required.

(3)  To allow heat to escape, do not block the area around the product.

 

Do not block the ventilation holes on the product.

(4)  Be sure to wire properly with correct polarity of terminals.

(5)  Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wiring. To connect bare wires to the 

terminal block, use copper braided or solid wires with a gage of AWG24 to AWG14 (equal to cross- sectional 

area of 0.205 to 2.081 mm

2

). (The stripping length is 5 to 6 mm.) Up to two wires of same size and type, or 

two crimped terminals can be inserted into a single terminal.

(6)  Do not wire the terminals which are not used.

(7)  Allow as much space as possible between the controller and devices that generate a powerful high- 

frequency or surge.

 

Separate the high-voltage or large-current power lines from other lines, and avoid parallel or common wiring 

with the power lines when you are wiring to the terminals.

(8)  Use this product within the rated load and power supply.

(9)  Make sure that the rated voltage is attained within two seconds of turning ON the power using a switch or 

relay contact. If the voltage is applied gradually, the power may not be reset or output malfunctions may 

occur.

(10) Make sure that the Digital Controller has 30 minutes or more to warm up after turning ON the power before 

starting actual control operations to ensure the correct temperature display. 

(11) When executing self-tuning, turn the load and the unit ON simultaneously, or turn the load ON before you 

turn the controller ON.

(12) A switch or circuit breaker should be provided close to this unit.

 

The switch or circuit breaker should be within easy reach of the operator, and must be marked as a 

disconnecting means for this unit.

(13) Always turn OFF the power supply before pulling out the interior of the product, and never touch nor apply 

shock to the terminals or electronic components. When inserting the interior of the product, do not allow the 

electronic components to touch the case. 

(14) Do not use paint thinner or similar chemical to clean with. Use standard grade alcohol. 

(15) Design system (control panel, etc) considering the 2 second of delay that the controller’s output to be set 

after power ON.

(16) The output may turn OFF when shifting to certain levels. Take this into consideration when performing 

control.

(17) Refer to the instruction sheet for installing Option unit (E53CNH03N / E53-CNHBN / E53-CN03N / 

E53-CNBN / E53-CNHH03N / E53-CNQ03N / E53-CNQHN / E53-CNPBN / E53-CNPHN / E53-CNQBN / 

E53-CNQHHN).

(18) The number of non-volatile memory write operations is limited. Therefore, use RAM write mode when 

frequently overwriting data during communications or other operations.

(19) When disassembling the Temperature Controller for disposal, use suitable tools.

(20) Do not use the Temperature Controller if the front sheet is peeling or torn.

Precautions for Safe Use