51
Connecting the Communications Connector
Section 2-4
2-4
Connecting the Communications Connector
Colored stickers are provided on the communications connector that match
the colors of the lines to be inserted. Check that the colors of the lines and
stickers match when wiring the connectors. The colors are as follows:
Refer to the
DeviceNet Operation Manual
(Cat. No. W267) for details on com-
munications specifications and wiring.
IMPORTANT
• When connecting the communications connector to the DST1, tighten the
screws on the communications connector to 0.25 to 0.3 N
⋅
m.
• OMRON’s S8
@@
Power Supplies are recommended for communications
power.
• Be sure to separate communications cables from high-voltage and power
lines.
• Use DeviceNet-compliant Thick Cables or Thin Cables for the communi-
cations cables. Do not use flat cables.
Note
• The internal power for the DST1-series Safety I/O Terminals is supplied
from the communications power supply (V+, V
−
).
Color
Signal
Red
Power cable positive side (V+)
White
High side of communications data (CAN_H)
-
Shield
Blue
Low side of communications data (CAN_L)
Black
Power cable negative side (V
−
)
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...