background image

DRT1-ID/OD

DRT1-ID/OD

3

Indicators

Indicator

Display

Color

Meaning

MS

Lit

Green

The Unit is normal.

Flashes

No node number has been set.

Lit

Red

The Unit has a fatal error.

Flashes

The Unit has a nonfatal error.

Not lit

No power is supplied to the Unit.

NS

Lit

Green

The communications path is complete.

Flashes

The communications path is incomplete.

Lit

Red

A fatal communications error has occurred.

Flashes

Red

A nonfatal communications error has occurred.

Not lit

The communications power supply is OFF.

0 to 15
(

t )

Lit

Yellow

The corresponding I/O signal is ON.

(see note)

Not lit

The corresponding I/O signal is OFF.

Note:

The DRT1-

D08 does not have indicators 8 to 15.

I/O Terminals

DIP Switch
Used for node number setting, baud rate set-
tings, and holding or clearing outputs for com-
munications error.

Note:

1. Always turn OFF the Unit and the commu-

nications power supply before changing
DIP switch settings.

2. Pin 9 is not used. Always set pin 9 to OFF.

I/O Device Power Supply Terminals
Connected internally to the I/O power supply terminals.

Internal Circuit Power Supply Terminals
Connect a 24-VDC power supply.

I/O Power Supply Terminals
Connect a 24-VDC power supply.

Supply a maximum of 2 A at 24 VDC.

Baud Rate Setting

Node Number Settings

Output
HOLD/
CLEAR Mode

Baud Rate Settings

Pin 8

Pin 7

125,000 bps

OFF

OFF

250,000 bps

OFF

ON

500,000 bps

ON

OFF

Note:

1. Setting both pins 7 and 8 to OFF is not allowed.

2. Pins 7 and 8 are factory-set to OFF.

Output HOLD/CLEAR Mode

Mode

Pin 10

HOLD

ON

CLEAR

OFF

Note:

1. Pin 9 is NC.

2. Pin 10 of the DRT1-ID08 or DRT1-ID16 is not used.

3. Pin 10 is factory-set to OFF.

Summary of Contents for DRT1-ID

Page 1: ...ew terminal 24 VDC 24 VDC DRT1 ID08 Output NPN common DRT1 OD08 Input NPN common 16 DRT1 ID16 Output NPN common DRT1 OD16 Specifications Ratings Input Item DRT1 ID Input current 10 mA max point ON delay time 1 5 ms max OFF delay time 1 5 ms max ON voltage 15 VDC min between each input terminal and V OFF voltage 5 VDC max between each input terminal and V OFF current 1 mA max Insulation method Phot...

Page 2: ...ction 300 m s2 approx 30G Mounting strength No damage when 50 N approx 5 kgf pull load was applied for 10 s in all directions 10 N min approx 1 kgf in the DIN Track direction Terminal strength No damage when 50 N approx 5 kgf pull load was applied for 10 s Screw tightening torque 0 6 to 1 18 N S m 6 2 to 12 kgf S cm Ambient temperature Operating 0 C to 55 C with no icing or condensation Storage 20...

Page 3: ...node number setting baud rate set tings and holding or clearing outputs for com munications error Note 1 Always turn OFF the Unit and the commu nications power supply before changing DIP switch settings 2 Pin 9 is not used Always set pin 9 to OFF I O Device Power Supply Terminals Connected internally to the I O power supply terminals Internal Circuit Power Supply Terminals Connect a 24 VDC power s...

Page 4: ... ON ON OFF OFF 44 ON OFF ON ON OFF OFF 13 OFF OFF ON ON OFF ON 45 ON OFF ON ON OFF ON 14 OFF OFF ON ON ON OFF 46 ON OFF ON ON ON OFF 15 OFF OFF ON ON ON ON 47 ON OFF ON ON ON ON 16 OFF ON OFF OFF OFF OFF 48 ON ON OFF OFF OFF OFF 17 OFF ON OFF OFF OFF ON 49 ON ON OFF OFF OFF ON 18 OFF ON OFF OFF ON OFF 50 ON ON OFF OFF ON OFF 19 OFF ON OFF OFF ON ON 51 ON ON OFF OFF ON ON 20 OFF ON OFF ON OFF OFF 5...

Page 5: ...Note All units are in millimeters unless otherwise indicated DRT1 ID08 DRT1 OD08 Mounting Holes Two 4 2 dia or M4 50 max 40 max 125 max Two 4 2 dia or M4 50 max 40 max 150 max Mounting Holes DRT1 ID16 DRT1 OD16 Fourteen M3 Twenty two M3 ...

Page 6: ...for internal circuitry Communications connector Power supply for internal circuitry Physi cal lay er Physi cal lay er Internal circuit Internal circuit Photo coupler Photo coupler Photo coupler Photo coupler Photo coupler Photo coupler Photo coupler Photo coupler Voltage step down Wiring Input DRT1 ID08 DRT1 ID16 Three wired Sensors NPN Output Two wired Sensors Brown Black Blue Brown Sensor 1 Brow...

Page 7: ...it power supply Shield Blue communications data L Black communications power supply White communications data H Red communications power supply I O power supply Solenoid etc Valve etc Photoelectric sensor or proximity sensor three wired sensor with a built in amplifier Limit switch two wired sensor Shield Blue communications data L Black communications power supply White communications data H Red ...

Page 8: ... Installation Environment Do not install the Unit in the following places Doing so may result in damage to the Unit or cause the Unit to malfunction Places with direct sunlight Places with ambient temperature ranges not within 0 C to 55 C Places with rapid temperature changes resulting in condensation or relative humidity ranges not within 10 to 90 Places with corrosive or inflammable gas Places w...

Reviews: