114
Analog Output Module
DRT1-DA02
I/O Interface Converts Binary Data into
Analog Output Data
Two outputs available.
High resolution of 1/6000.
Conversion is possible within a range of --5% to
150% full scale.
High conversion speed of 4 ms/two points.
Handles a wide range of outputs including 1 to 5 V,
0 to 10 V, --10 to 10 V, 4 to 20 mA, and 0 to 20 mA.
Bears the CE marking.
Ordering Information
Classification
I/O points
Model
Analog output Module
2 outputs (Occupies 2 output words of the Master.)
DRT1-DA02
Specifications
Ratings
Output
Item
Type
Voltage output
Current output
Output points
2 points
Output type
1 to 5 V
0 to 10 V
--10 to 10 V
0 to 20 mA
4 to 20 mA
Allowable external output
load resistance
1 K
W
min.
600
W
max.
External output impedance
0.5
W
max.
---
Resolution
1/6000 full scale
Overall accuracy
25
°
C :
±
0.4% full scale
0
°
C to 55
°
C:
±
0.8% full scale
Conversion time
4 ms/2 points
Converted output data
Binary data
--10- to 10-V range: 8BB8 to 0BB8 full scale
Other signal ranges:0000 to 1770 full scale
Insulation resistance
20
MW
min. at 250 VDC (between insulated circuits)
Insulation method
Photocoupler insulation between outputs and communications lines (There is no insulation between
output signals.)