background image

114

Analog Output Module

DRT1-DA02

I/O Interface Converts Binary Data into

Analog Output Data

Two outputs available.
High resolution of 1/6000.
Conversion is possible within a range of --5% to

150% full scale.
High conversion speed of 4 ms/two points.
Handles a wide range of outputs including 1 to 5 V,

0 to 10 V, --10 to 10 V, 4 to 20 mA, and 0 to 20 mA.
Bears the CE marking.

Ordering Information

Classification

I/O points

Model

Analog output Module

2 outputs (Occupies 2 output words of the Master.)

DRT1-DA02

Specifications

Ratings

Output

Item

Type

Voltage output

Current output

Output points

2 points

Output type

1 to 5 V
0 to 10 V
--10 to 10 V

0 to 20 mA
4 to 20 mA

Allowable external output

load resistance

1 K

W

min.

600

W

max.

External output impedance

0.5

W

max.

---

Resolution

1/6000 full scale

Overall accuracy

25

°

C :

±

0.4% full scale

0

°

C to 55

°

C:

±

0.8% full scale

Conversion time

4 ms/2 points

Converted output data

Binary data

--10- to 10-V range: 8BB8 to 0BB8 full scale

Other signal ranges:0000 to 1770 full scale

Insulation resistance

20

MW

min. at 250 VDC (between insulated circuits)

Insulation method

Photocoupler insulation between outputs and communications lines (There is no insulation between

output signals.)

Summary of Contents for DRT1-DA02

Page 1: ... Specifications Ratings Output Item Type Voltage output Current output Output points 2 points Output type 1 to 5 V 0 to 10 V 10 to 10 V 0 to 20 mA 4 to 20 mA Allowable external output load resistance 1 KW min 600 W max External output impedance 0 5 W max Resolution 1 6000 full scale Overall accuracy 25 C 0 4 full scale 0 C to 55 C 0 8 full scale Conversion time 4 ms 2 points Converted output data ...

Page 2: ... DIN track mounting Mounting strength No damage when 50 N approx 5 kgf pull load was applied for 10 s in all directions 10 N min approx 1 kgf in the DIN track direction Terminal strength No damage when 50 N approx 5 kgf pull load was applied for 10 s in all directions Ambient temperature Operating 0 C to 55 C with no icing or condensation Storage 25 C to 65 C with no icing or condensation Ambient ...

Page 3: ...1 DA02 73 max 150 max 50 max 40 max Mounting Holes Two 4 2 dia or M4 Wiring DRT1 DA02 SOURCE 24 VDC Voltage output connection External device External device Current output connection Internal circuit power supply Internal circuit power supply Terminal Arrangement DRT1 DA02 24 VDC 24 VDC 0 0 0 1 1 1 ...

Page 4: ...n cause the Module to malfunction Install surge absorbers or noise filters on nearby equipment that generates noise particularly equipment that has inductive components such as motors transformers solenoids or magnetic coils When using a noise filter in the power supply check the voltage and current and install the noise filter as close as possible to the Module Cat No P10FAX1A 6 00 Specifications...

Reviews: