G-166
Safety Sensors / Components
Characteristics
Note: 1.
The degree of protection shown above is based on the test method specified in EN60947-5-1. Be sure to confirm in advance the sealing
performance under the actual operating environment and conditions.
Although the switch box is protected from dust, oil, or water penetration, do not use the D4GS-N in places where dust, oil, water, or chem-
icals may penetrate through the key hole on the head, otherwise Switch damage or malfunctioning may occur.
2.
The durability is for an ambient temperature of 5°C to 35°C and an ambient humidity of 40% to 70%.
3.
When the ambient temperature is 35°C or higher, do not apply 1 A at 125 VAC to more than one circuit.
4.
These figures are minimum requirements for safe operation.
5.
The value given for minimum applicable load is a reference value for micro-loads. The value will vary depending on factors such as the
switching frequency, the ambient environment, and the reliability level. Be sure to confirm correct operation with the actual load before
application.
Degree of protection (see note 1)
Body: IP67 (EN60947-5-1) (Operation Key insertion face: IP00)
Durability (see note 2)
Mechanical:1,000,000 times min.
Electrical:100,000 times min. (1-A resistive load at 125 VAC) (see note 3)
Operating speed
0.1 to 0.5 m/s
Contact gap
2 x 2 mm min.
Operating frequency
30 operations/minute
Direct opening force (see note 4)
60 N min.
Direct opening travel (see note 4)
10 mm min.
Insulation resistance
100 M
Ω
min. (at 500 VDC) between terminals of the same polarities, between terminals
of different polarities, and between each terminal and non-current carrying metal parts
Minimum applicable load (see note 5)
4 mA at 24 VDC
Contact resistance
300 m
Ω
max. (Initial value with 1-m cable)
Dielectric strength
Between terminals of same polarities: Uimp 2.5 kV (EN60947-5-1)
Between terminals of different polarities: Uimp 4 kV (EN60947-5-1)
Between each terminal and non-current carrying metal parts: Uimp 6 kV (EN60947-5-1)
Conditional short-circuit current
100 A (EN60947-5-1)
Pollution degree (operating environment)
3 (EN60947-5-1)
Conventional free air thermal current (I
th
)
2.5 A (EN60947-5-1)
Protection against electric shock
Class II (double insulation) (IEC60536)
Vibration resistance
Malfunction:10 to 55 Hz, 0.35-mm single amplitude
Shock resistance
Malfunction:300 m/s
2
min.
Ambient temperature
Operating:-30°C to 70°C (with no icing)
Ambient humidity
Operating:95% max.
Cable
UL2464 No. 22 AWG, finishing O.D.: 7.2 mm
Weight
Approx. 120 g (D4GS-N1R, with 1-m cable)