53
Installation
Section 3-2
3-2-3
CS1D PLCs
Up to 3 pairs (i.e., active Unit and standby Unit) of CS-series Controller Link
Units used in duplex operation and one CS-series Controller Link Unit not
used in duplex operation can be mounted to a CS1D Duplex Backplane or an
Expansion Backplane supporting online replacement. In other words, Units
using up to 4 unit numbers can be mounted. Controller Link Units cannot be
installed on an C200H Expansion I/O Rack or a SYSMAC BUS Slave Rack.
Note
1.
Duplex operation is possible only with the CS1W-CLK12-V1 and CS1W-
CLK52-V1.
2.
Tighten the screws on the Backplane to a torque of 0.9 N • m.
Tighten the fixed screws on the CPU Unit to a torque of 0.4 N • m.
When installing several CS-series CPU Bus Units at the same time, a total of
16 CS-series CPU Bus Units maximum (not including Controller Link Units in
standby mode) may be installed.
For details on the CS1D System, refer to the CS-series Duplex System Oper-
ation Manual (W405).
Note
1.
A pair of Controller Link Units used in duplex operation can be mounted in
non-adjacent slots or on different Racks. Be sure, however, to connect
them directly with a cable.
2.
In the CS1D System, online replacement is possible using a Programming
Console. If the Controller Link Units are used in token-bus mode, however,
there is a possibility of the network splitting.
P
S
P
S
D
P
L
C
P
U
C
P
U
*1
P
S
P
S
P
S
CS1D CPU Rack
The Unit can be mounted in any of the 5
slots shown in the diagram on the left.
*1: This slot is empty for
Simplex Systems.
5 slots
Duplex Backplane
CS1D-BC052
CS1D Expansion Backplane
The Unit can be mounted in any of
the 9 slots shown in the diagram on
the left (8 slots for Long-distance
Expansion racks).
Expansion Backplane
supporting online replacement
CS1D-BI092
9 slots
C200H Expansion I/O Backplane
C200H Expansion I/O Backplane
Controller Link Units cannot be
mounted to Expansion I/O slots.
Units corresponding to up to 4
unit numbers can be mounted.
Possible configurations include
the following:
1. Controller Link Units used
in duplex operation can be
mounted to 6 slots (3 lots
for active Units and 3 slots
for standby Units) and a
Controller Link Unit not
used in duplex operation
can be mounted in 1 slot.
2. Controller Link Units not
used in duplex operation
can be mounted to 4 slots.
PS: Power Supply Unit
CPU: CPU Unit
DPL: Duplex Unit (CS1D-DPL01)
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...