10-6 Cleaning and Inspection
This section describes cleaning and inspection procedures that are to be per-
formed as daily maintenance.
10-6-1 Cleaning
Conduct the following periodic cleaning to keep the Controller Link Unit in
optimum condition.
• Wipe the Unit with a dry, soft cloth daily.
• For stains that cannot be removed with a dry cloth, dip the cloth in
medium strength alcohol (2%), wring the cloth tightly, and then wipe down
the Unit.
• If glue, vinyl, or tape is left on the Unit for long periods of time, it will stain.
Remove these items during cleaning.
Not lit
Not lit
Flashing
Not lit
Duplex Communications
Setting Error Flags
(A435)
CPU Bus Unit Setting
Error Flag (A40207)
The was an error in the
standby Controller Link
Unit.
If the RUN indicator still
does not light when the
Unit is mounted on
another PLC, replace it.
Not lit
Lit
Flashing
Not lit
(CPU standby)
The was an error in the
active Controller Link
Unit.
If the ERC indicator
lights when the Unit is
mounted on another
PLC, replace it.
The node address
setting for the active
Controller Link Unit is
out of the allowable
range.
Set the node address of
the active Unit to the
same address as the
standby Unit in the range
1 to 62.
Active Unit
Standby Unit
Status area
(Auxiliary Area)
Probable cause
Probable remedy
RUN
ERC
RUN
ERC
Lit
Not lit
Flashing
Not lit
(No error)
Both the active and
standby Units are oper-
ating normally.
---
Not lit
Not lit
Lit
Not lit
Duplex Communica-
tions Switched Flags
(A436)
There was an error in
the active Controller Link
Unit. (The standby Unit
switched to active mode
and continued communi-
cations.)
Replace the active Con-
troller Link Unit.
Lit
Not lit
Flashing
Lit
Duplex Communica-
tions Standby Unit Error
Flag (A437)
The was an error in the
standby Controller Link
Unit. (The active Unit
continued communica-
tions.)
Replace the standby
Controller Link Unit.
Lit
Not lit
Not lit
Not lit
Duplex Communica-
tions Standby Unit Error
Flag (A437)
The was a watchdog
timer error in the standby
Controller Link Unit.
(The active Unit contin-
ued communications.)
Replace the standby
Controller Link Unit.
Active Unit
Standby Unit
Status area
(Auxiliary Area)
Probable cause
Probable remedy
RUN
ERC
RUN
ERC
Summary of Contents for CS1W-CLK12-V1
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x TABLE OF CONTENTS ...
Page 11: ...xii ...
Page 59: ...42 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 62: ...45 Component Names and Functions Section 3 1 Dimensions Unit mm ...
Page 91: ...74 CVM1 and CV series Optical Ring Controller Link Units Section 4 2 ...
Page 108: ...91 Setting Data Links Section 5 2 Device Information Setting Data Link Tables ...
Page 125: ...108 Checking Data Link Status Section 5 4 ...
Page 181: ...164 Setting Routing Tables Section 7 4 ...
Page 199: ...182 Memory Areas Related to Duplex Operation Section 8 6 ...
Page 275: ...258 Handling Precautions Section 10 7 ...
Page 298: ...281 CS series Optical Bus Controller Link Units Appendix C Dimensions Unit mm 101 35 130 ...
Page 299: ...282 CS series Optical Bus Controller Link Units Appendix C ...