92
SR Area
Section 4-4
4-4
SR Area
These bits mainly serve as flags related to CPM2C-S operation or contain
present and set values for various functions. The functions of the SR area are
explained in the following table.
Note
“Read-only” words and bits can be read as status in controller PC operation,
but they cannot be written from the ladder program. Bits and words that are
“Not used” are also read-only.
Word(s)
Bit(s)
Function
Read/
write
SR 228,
SR 229
00 to 15
Pulse Output PV 0
Contains the pulse output PV (–16,777,215 to 16,777,215). SR 22915 acts as the sign
bit; a negative number is indicated when SR 22915 is ON.
(The same PV data can be read immediately with PRV(62).)
Only Pulse Output PV 0 is used for ACC(––).
Read-
only
SR 230,
SR 231
00 to 15
Pulse Output PV 1
Contains the pulse output PV (–16,777,215 to 16,777,215). SR 23115 acts as the sign
bit; a negative number is indicated when SR 23115 is ON.
(The same PV data can be read immediately with PRV(62).)
SR 232
to
SR 235
00 to 15
Macro Function Input Area
Contains the input operands for MCRO(99).
(Can be used as work bits when MCRO(99) is not used.)
Read/
write
SR 236
to
SR 239
00 to 15
Macro Function Output Area
Contains the output operands for MCRO(99).
(Can be used as work bits when MCRO(99) is not used.)
SR 240
00 to 15
Interrupt Input 00003 Counter Mode SV
SV when interrupt input 00003 is used in counter mode (4 digits hexadecimal).
(Can be used as work bits when interrupt input 00003 is not used in counter mode.)
SR 241
00 to 15
Interrupt Input 00004 Counter Mode SV
SV when interrupt input 00004 is used in counter mode (4 digits hexadecimal).
(Can be used as work bits when interrupt input 00004 is not used in counter mode.)
SR 242,
SR 243
00 to 15
Not used.
SR 244
00 to 15
Interrupt Input 00003 Counter Mode PV
Counter PV when interrupt input 00003 is used in counter mode (4 digits hexadecimal).
Read-
only
SR 245
00 to 15
Interrupt Input 00004 Counter Mode PV
Counter PV when interrupt input 00004 is used in counter mode (4 digits hexadecimal).
SR 246,
SR 247
00 to 15
Not used.
SR 248,
SR 249
00 to 15
High-speed Counter PV Area
(Can be used as work bits when the high-speed counter is not used.)
Read-
only
SR 250,
SR 251
00 to 15
Not used.
Summary of Contents for CPM2C-S100C
Page 2: ......
Page 3: ...CPM2C S Programmable Controller Operation Manual Revised September 2009 ...
Page 4: ...iv ...
Page 6: ...vi ...
Page 10: ......
Page 14: ...xiv ...
Page 180: ...158 One to one PC Link I O Response Time Section 7 4 ...
Page 222: ...200 Programming Example Section 8 3 ...
Page 250: ......
Page 256: ......
Page 258: ......
Page 260: ...238 Support Software Appendix C ...
Page 268: ......