![background image](http://html1.mh-extra.com/html/omron/cj2h-cpu6-series/cj2h-cpu6-series_replacement-manual_742076037.webp)
28
< TTL I/O Unit >
C200H-series Unit
Corresponding CJ-series Unit
Description
Difference
C200H-MD501
CJ1W-MD231
I/O Unit with connector for 16
inputs and 16 outputs.
*The CJ-series Unit does not
support dynamic outputs.
Change the wiring for static
outputs.
*We recommend you to
replace this Unit with
CJ1W-MD563 (32 inputs/32
outputs) for TTL I/O.
1) Connector
2) Output method
(Dynamic or static mode
→
Static mode only)
3) Internal current consumption
(5 VDC: 180 mA
→
130 mA)
Based on specifications in static output mode
< Output circuit >
4) No. of circuits (8 points/common x 2 circuits
→
16 points/common x 1 circuit)
5
)
Output circuit specifications
Output voltage range
(5 VDC
→
12 to 24 VDC)
Residual voltage (0.4 V -> 1.5 V)
ON response time (0.2 ms
→
0.1 ms)
OFF response time (0.3 ms
→
0.8 ms)
< Input circuit >
6) No. of circuits (8 points/common x 2 circuits
→
16 points/common x 1 circuit)
7) Input circuit specifications
Input voltage (5 VDC
→
24 VDC)
Input impedance (1.1
kΩ
→
3.3
kΩ)
ON voltage (3 VDC
→
14.4 VDC)
OFF voltage (1 VDC
→
5 VDC)
5 VDC/16 inputs (3.5 mA),
5 VDC/16 outputs (35 mA,
Sinking), Connector
(Special I/O)
24 VDC/16 inputs (7 mA),
12 to 24VDC/16 outputs
(0.5 A, Sinking), Connector
Summary of Contents for CJ2H-CPU6 Series