background image

 

 

Model 

CJ1W-TS561  

Thermocouple input unit

 

 

 

INSTRUCTION SHEET 

 

 

Thank you for purchasing an OMRON product. Read this 
instruction sheet thoroughly and familiarise yourself with the 
functions and characteristics of the product before using it.

  

To ensure safe and correct use of this Unit, also read the 
Operation- and Programming Manuals for your CJ1 PLC system.

  

 

Keep this instruction sheet for future reference.

 

 

OMRON MANUFACTURING OF THE NETHERLANDS B.V. 

 OMRON Corporation 2004 

All Rights Reserved 

 
 

■ 

General Specifications 

 

Unit classification  

CJ-series Basic I/O Unit  

Compatible Racks 

CJ-series CPU Rack or  
CJ-series Expansion Rack 

Max. number of 
Units 

10 Units/Rack max.  
(This requires a CJ1G or CJ1H CPU) 

CPU Unit data area 
for inputs  

Basic I/O area CIO0000 – 0999  
(3, 4 or 6 words allocated in IO Table) 

Insulation resistance 
 

20 M

 min. (at 500 V DC) between 

input terminals and PLC I/O bus. 

Dielectric Strength 

500 V AC, 50/60 Hz for 1 min. (detection 
current: 1 mA), between Input terminals 
and PLC I/O bus. 

Internal current 
consumption 

220 mA max., 5 V DC,  
from the PLC I/O bus. 

Dimensions  

31 x 90 x 65 mm (W x H x D) 

Weight 

150 g max. 

Other  
 

Other general specifications conform to 
the CJ-series general specifications. 
See Operation Manual W393. 

 
 

■ 

Characteristics 

■ 

Unit Description 

 

Thermocouple input  

K-type or J-type (IEC 60584) 

Number of inputs 

1 to 6 

Measurement range 

K-type:  -200.0 to +1300.0 °C  
J-type:   -100.0 to +850.0 °C 

Indication resolution  

0.1 °C 

Cold junction 
compensation  
- Accuracy 

Internal measurement of terminal 
temperature, once in each scan cycle. 
± 2.0 °C in a stable temperature 
environment (no direct heat or airflow).  

Temperature value 
Data representation 

16-bit signed integer in units of 0.1 °C: 
#F830 = -200.0 °C, #32C8 = +1300.0 °C 

Indication accuracy * 
over full operational 
range (0 – 55 °C 
ambient temperature) 

± 0.5 % of indicated value or ± 0.7 °C 
(whichever is larger) ± 1 digit max. 
±2.0 °C ± 1 digit max. using a K-type 
thermocouple below –100 °C. 

Input response time  
(per active input) 

  40  ms  (100 Hz suppression) 
  67  ms  (60 Hz suppression) 
  80   ms  (50 Hz suppression) 
 400   ms  (50+60 Hz suppression) 

Input update cycle 
time (all active inputs) 

[number of active 1] x [input 
response time] + 40 ms 

I/O refresh time 
(influence on PLC 
cycle time) 

1-3 inputs   (48pt mode):  0.008 ms 
4    inputs   (64pt mode):  0.011 ms 
5-6 inputs  (96pt mode):  0.016 ms 

 
The CJ1W-TS561 is a 6-channel input unit for K-type and J-type 
thermocouples. It can be installed in any CJ1-series PLC system.  
It is classified as a basic I/O unit, occupying 48, 64 or 96 I/O points, 
depending on the number of activated inputs. 
Always verify that the maximum I/O capacity of the CJ1 CPU is 
sufficient for the number of required I/O points. 
 

■ 

Nomenclature 

 

Unit status indicators

 

• 

RUN (green) 

• 

ERC (red) 

 

Sensor error indicators

 

• 

1 - 6  

(red) 

 

Removable Terminal Block

 

• 

Connections for Thermocouples 1 - 6 

• 

CJ1W-TS561: screw terminal 

• 

CJ1W-TS561 (SL): screwless terminal 

  

DIP switches  
(remove terminal block for access) 

• 

Select input types (K-type/J-type) 

• 

Select filter functions 

• 

Select number of active inputs (1-6) 

 
Terminal Block latch

 

• 

Slide down to remove 

• 

Slide up to lock 

 
* Indication accuracy is guaranteed with the supplied terminal block. 
Do not replace the supplied terminal block by a different model (e.g. 
screw type by screwless type or vice versa).  
 

■ 

LED indicators 

 

Name State Description 

OFF 

Fatal error or no power supply. 

• 

Check the host PLC’s CPU status, and the 
status of other I/O units. If all other units 
function normally, replace the Unit. 

RUN 
(Green) 

ON 

Unit functions normally. 

OFF 

No fatal errors. 

ERC 
(Red) 

ON 

Incorrect DIP switch setting 
Fatal error in the Unit. 

• 

Check the CPU unit for error codes. 

• 

Re-start the PLC system. 

• 

If the ERC LED is still lit, replace the unit. 

OFF 

• 

Measurement of the corresponding channel is 
within range, or 

• 

Channel has been deactivated by DIP switch 
settings 

ON 

• 

Measured temperature out-of-range, or 

• 

Thermocouple broken wire 

Sensor 
Error 
1 – 6 
(Red) 

All ON  Calibration data not found or incorrect. The Unit 

should be returned to OMRON for calibration. 

 
 

■ 

Wiring 

• 

Keep the thermocouple wiring as short as possible to avoid 
electrical interference. Shielded wiring is recommended. 

• 

When extending input wiring, always use compensation wires 
appropriate for the thermocouple type. 

• 

For activated but unused inputs, short-circuit the + and - 
terminals, to prevent unstable readout on the other inputs. 

• 

Keep the input wiring away from power lines including AC power 
supply lines and high-power lines. Do not run the I/O lines in the 
same duct or conduit as power lines. 

• 

The input circuits are galvanically isolated from the PLC’s I/O bus, 
but there is no galvanic isolation between individual inputs. 

• 

Always ground the        terminal on the Power Supply Unit of the 
PLC. In case of shielded sensor wiring, connect the shields to the 
same grounding point as the PLC. 

 