Measure Cold Junction 

+ Sensor error check

Measure Channel 1 

Measure Channel 2 

Measure Channel N 

Unit initialisation 

■ 

DIP switches 

 

8 DIP switches are accessible after removing the 
front terminal block. Switch settings are processed at 
time of power ON, and should not be changed while 
the unit is powered. 

 
Default (ex-factory) setting is all switches ON,  
i.e. all 6 inputs are active and set to K-type 
thermocouple, with filtering at n x 100 Hz. Be sure 
to adjust the settings to your requirements before 
use.

 

 
SW 1, 2 and 3 : Input type selection 

 
Any combination of input types (different numbers of K-type/J-type 
sensors) can be set. 
 

SW 

State 

Input type selection 

OFF 

Input channel 1 is J-type 

ON 

Input channel 1 is K-type 

OFF 

Input channels 2 and 3 are J-type 

ON 

Input channels 2 and 3 are K-type 

OFF 

Input channels 4, 5 and 6 are J-type 

ON 

Input channels 4, 5 and 6 are K-type 

 
 
SW 4 + 5 : Input filtering (valid for all active input channels) 

 
Use filtering if the measured value is affected by the mains frequency or 
other sources of electrical interference. 
 

SW4 SW5 Filtering 

Response 

time 

OFF 

OFF 

n x 10 Hz suppression 

400 ms each input 

OFF 

ON 

n x 50 Hz suppression 

80 ms each input 

ON 

OFF 

n x 60 Hz suppression 

67 ms each input 

ON 

ON 

n x 100 Hz suppression 

40 ms each input 

 
 
SW 6+7+8 : Input activation 

 
To prevent broken wire indication for unused inputs, and to reduce the 
number of input channels occupied in CIO memory, the number of 
required inputs can be set by SW 6+7+8.  
 
Input words are allocated in the PLC’s CIO area as Basic I/O Unit, i.e. 
sequentially starting at the leftmost unit. See CJ1-series Operation 
Manual W393 for details. 
 
Create the I/O table in the PLC after changing the switch settings, to 
register the correct number of input words in the PLC CPU. The unit is 
registered as 48-point, 64-point, or 96-point input unit, depending on the 
number of 16-bit CIO words it occupies. 

 

SW6  SW7  SW8  Active inputs 

Occupied input words 

OFF  OFF  OFF  Not valid, ERC indicator will be ON 
ON  OFF  OFF  1 

3 CIO words (1 used)* 

OFF  ON  OFF  1, 2 

3 CIO words (2 used)* 

ON  ON  OFF  1, 2, 3 

3 CIO words 

OFF  OFF  ON  1, 2, 3, 4 

4 CIO words 

ON  OFF  ON  1, 2, 3, 4, 5 

6 CIO words (5 used)* 

OFF  ON  ON  1, 2, 3, 4, 5, 6 

6 CIO words 

ON  ON  ON  1, 2, 3, 4, 5, 6 

6 CIO words 

 
* In these cases, more CIO words will be occupied than required for the 
active inputs. The remaining occupied CIO words will be filled with 0’s, 
and cannot be used as work bits. 
 

 

■ 

Data representation 

 

Measured temperatures are indicated in °C. Each input value 
occupies one word (16 bits) in the CIO area and is encoded as a 
signed integer, with a resolution of 0.1 °C. 
 
Examples:  #0300 = 

 768 (dec) =  

 76.8 °C 

 

#FF85 = 

-123 (dec) =  

-12.3 °C 

 

Measured values are updated in CIO memory in each I/O refresh cycle.  
The following values are to be interpreted as error codes: 
 

Value Description 

#7AAA 

Calibration data invalid or error detected at start-up, 
e.g. cold junction temperature out of range. 

#7BBB 

Sensor error, broken wire 

#7CCC 

Measured value out of range (over max. Temperature) 

#8CCC 

Measured value out of range (under min. Temperature) 

 
During initialisation after power ON, data of active inputs will be #0000 
until the “Not Ready’ flag turns OFF.

 

 

■ 

‘Not Ready’ flag 

 

During initialisation after power-on, and in case of internal failure, a 
‘Not Ready’ flag will be set in the PLC memory area A050 to A069 
(Basic I/O Unit information area, refer to CJ1 Operation Manual W393 
for details).  
The lower bit of each unit is the Not Ready flag; the error code 
indicated in the remaining bits is relevant for repair purposes only.  
While this flag is ON, the temperature sensor data indicated by the 
unit in the CIO area is invalid. 
 

Address  Bit 

When Bit = ON 

00 

Unit in rack 0, slot 0 is not ready 

A050 

08 

Unit in rack 0, slot 1 is not ready 

00 

Unit in rack 0, slot 2 is not ready 

A051 

… … 
00 

Unit in rack 1, slot 0 is not ready 

A055 

… … 
00 

Unit in rack 3, slot 9 is not ready 

A069 

08 

Unit in rack 3, slot 10 is not ready 

 
 

■ 

Unit cycle time 

 

The internal processing time for all measurements by the unit is 
determined by the number of active channels and the filter type.  
 

 

 
 

The cold junction compensation 
measurement and one sensor error 
check are executed each cycle.  
 
The cold junction measurement 
time depends on the input filter 
setting, whereas the sensor error 

check takes a fixed 40 ms. 
 
Example: 
If 4 inputs are active, and filtering is 
set to n x 50 Hz (response time = 
80 ms): 
 

Each measurement cycle takes 
(4+1) x 80 + 40 ms = 440 ms. 
 
 

 

 

 
 
 
 
 
 
 

 