Error Processing 

At the occurrence of an error: 

  the corresponding error code is transferred to device 

variables  
     *_ErrCode1
 and *_ErrCode2 

  the corresponding error code is stored inside the SSI Unit 

  the Global Error device variable *_GlblErr is turned ON 

  the ERC LED indicator or ERH LED indicator is turned ON 

 
The  following  errors  codes  can  be  reported  in  device  variables 
*_ErrCode1 and *_ErrCode2 

*_ErrCode 1 

*_ErrCode2 

Description 

0300 

Offset (see 
configuration 
device 
variable table 
above) 

The setting for the Device 
Variable is out of range. Use the 
*_ErrCode2 offset to identify the 
Device Variable. 

0310 

Offset (see 
configuration 
device 
variable table 
above) 

The setting for the Device 
Variable has an invalid BCD-
code (The range of a valid BCD-
code for a digit is 0-9. If one or 
more digits are within range A – 
F, an invalid BCD-code is 
specified). Use the *_ErrCode2 
offset to identify the Device 
Variable. 

Countermeasure:  Configuration  errors  can  be  cleared  by  correcting 
the  faulty  settings  in  device  variables  and  transferring  the  new 
configuration data to the Unit. To transfer the configuration data: 

 

Turn the power of the NJ system ON, or 

 

Restart the Unit  

 
 

*_ErrCode 1 

*_ErrCode2 

Description 

 

0490 

CH 

No. 

00 

Parity error in SSI channel CH No. 

Countermeasure:  Check  if  the  unit  is  configured  to  check  for  the 
correct type of parity (even or odd). Check the SSI-encoder. 

*_ErrCode 1 

*_ErrCode2 

Description 

0490 

CH 

No. 

01 

SSI-encoder  channel  CH  No.  not 
ready 

Countermeasure: This error appears in case the data line is low right 
before the communication with the encoder connected to channel CH 
No.
  is  started.  Check  the  cabling  between  the  unit  and  the  SSI-
encoder. Check the SSI-encoder. 

*_ErrCode 1 

*_ErrCode2 

Description 

0490 

CH 

No. 

02 

SSI-encoder  channel CH  No. time-
out 

Countermeasure:  This  error  appears  in  case  the  data  line  is  and 
stays  low  after  the  mono-flop  time  has  expired  on  channel  CH  No. 
Check if the unit is configured for the correct encoder settings. Check 
the  cabling  between  the  unit  and  the  SSI-encoder.  Check  the  SSI-
encoder. 

*_ErrCode 1 

*_ErrCode2 

Description 

0002 

Time-out in 

ms (hex) 

A  cyclic  refresh  time-out  error  was 
generated caused by a PLC system 
error or you have chosen to disable 
the  Cyclic  Refresh  of  the  SSI  Unit 
in  the  NJ-series  CPU  Unit.  This 
error  will  be  cleared  as  soon  as 
Cyclic  Refresh  or  IORF  will  take 
place. 

000E 

0000 

An  error  has  occurred  on  the  I/O 
Bus  causing  the  SSI  Unit  to  be  in 
an undefined state.  

Countermeasure:  Turn  ON  the  power  supply  again  or  restart  the 
system. If the error persists then replace the NJ CPU. 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 