192
Exchanging Data with the CPU Unit
Section 5-5
Set Values and Stored Values
Note
1.
When using a CJ1W-DA08C, these output signal range settings are invalid
and the contents will be ignored. The output signal range for the CJ1W-
DA08C is fixed at 4 to 20 mA.
2.
The output signal ranges 1 to 5 V and 4 to 20 mA are switched using the
output terminal connections. For details, refer to
. (The CJ1W-
DA08V supports only voltage outputs.)
3.
The values output for the signal ranges will be 0 V for the range of
±
10 V,
and the minimum value for the other ranges. For details, refer to
.
Item
Contents
Page
Output
Use setting
0:
Not used.
1:
Used.
Output signal range
(See note 1.)
00:
–10 to 10 V
01:
0 to 10 V
10:
1 to 5 V/4 to 20 mA (See note 2.)
11:
0 to 5 V
Output status when stopped
00:
CLR
Outputs 0 or minimum value of each range.
(See note 3.)
01:
HOLD
Holds output just before stopping.
02:
MAX
Outputs maximum value of range.
Conversion time/resolution
setting
00:
Conversion time: 1 ms; resolution: 4,000
01:
Conversion time: 250
µ
s; resolution: 8,000
Operation mode setting
00:
Normal mode
01:
Adjustment mode
Scaling settings
Any value other than 0 within range of
±
32,000 (8300 hex to 7D00 hex)
as long as the upper limit is not equal to the lower limit.
Summary of Contents for CJ1W-AD041-V1
Page 3: ...iv...
Page 5: ...vi...
Page 9: ...x TABLE OF CONTENTS...
Page 15: ...xvi...
Page 99: ...76 Handling Errors and Alarms Section 2 8...
Page 191: ...168 Handling Errors and Alarms Section 4 8...
Page 243: ...220 Handling Errors and Alarms Section 5 8...
Page 381: ...358 Handling Errors and Alarms Section 7 10...
Page 385: ...362 Dimensions Appendix A...
Page 395: ...372 Sample Programs Appendix B...
Page 396: ...373 Appendix C Data Memory Coding Sheets...
Page 417: ...394 Data Memory Coding Sheets Appendix C...
Page 425: ......