43
5
BU
1002
SWG / BU
3002
SWG
(3) Calculate the initial value of the backup time for the total capacity of the connected devices from the
graph below.
●
Graph of backup time (graph of initial values for products that have not been used)
●
The smaller the capacity of connected devices becomes, the longer the backup time becomes.
120
110
100
90
80
70
60
50
40
30
20
10
0
0
100
200
300
400
500 600
700
800
900 1000 1100 1200 1300 1400 1500
1600 1700 1800 1900 2000 2100
Backup time
(20°
C, initial value)
BU1002SWG
BU3002SWG
(Minutes)
Power consumption
of connected devices(W)
* These backup times are for reference only. Times may vary according to battery life and external environmental
conditions (temperature, etc.).
Time unit: Minutes
Model
20W
50W
100W
200W
300W
400W
500W
700W 1000W 1400W
BU1002SWG
180
120
60
35
20
15
10
5
-
-
Model
200W 400W 600W 800W 1000W 1200W 1400W 1600W 1800W 2000W 2100W
BU3002SWG
92
46
30
20
15
12
10
8
7
5.5
5