G-30
Pushbutton Switch
A16
Installation
■
Panel Mounting
After mounting the Pushbutton Unit (i.e., the Pushbutton and the
Case) to the panel, snap in the Switch Unit (i.e., the Switch and the
Lamp) from the back of the panel.
Mounting to the Panel
Insert the Pushbutton Unit into the front of the panel, and fix the lock
ring and mounting nut from the terminal side.
Make sure that the lock ring is aligned with the thread of the Case
and the edge of the lock ring is touching the panel.
Tighten the mounting nuts to a torque of 0.29 to 0.49 N
⋅
m.
The maximum tightening torque is 0.49 N
⋅
m.
Mounting the Switch Unit
Snap on the Switch Unit to the Pushbutton Unit.
Make sure that the Switch Unit has the correct orientation when
snapping it onto the Case. Align the • mark on the Case with the
groove between the case guards on the NC terminal side of the
Switch Unit in the way shown below, and push the Switch Unit into
the Case until it clicks into place. Confirm that the Switch Unit is
securely in place before using.
Mounting the Switch Unit for Voltage Reduction Types
1.
The mounting panel thickness must be 0.5 to 3.2 mm.
2.
The mounting ring must be tightened to a torque 0.29 to 0.49 N
⋅
m.
3.
The mounting hole must be cut out in the way described previously. The dimension A is the length required for removing the Switch when it is
in the mounted state. If Switches are mounted side-by-side separated by less than the specified distance, it may not be possible to remove the
Switch.
4.
Be sure to mount the Case to the Switch with the correct orientation. Mount with the • mark on the Case facing in the same direction as the
side of the Switch with the direction arrow or the word TOP.
Case
Panel
Mounting nut
Lock ring
Edge
Thread
NC terminal
•
mark
Groove between
case guards
Case
•
mark
Switch
Direction arrow
Case
Switch
TOP mark
•
mark