E-16

Conductive Level Controller 

61F-GPN-BT/-BC

Specifications

Ratings

Note: 1.

The 61F may not operate at resistance settings close to zero. Adjust the sensitivity to match actual usage conditions.

2.

The figure for wiring distance above is for when 600-V 3-core cabtyre cable with a cross-sectional area of 0.75 mm

2

 is used.

Characteristics

Note:

The dielectric strength is measured between power terminals
and electrode terminals, power terminals and output terminals,
and between electrode terminals and output terminals.

Connections

Automatic Drainage Operation

Note:

 The part within the dotted-line box is for the 61F-GPN-BC (relay-output type) only.

Automatic Water Supply Operation

Short terminals 7 and 8 for automatic water supply operation. (Operation shown in parentheses in the diagram above.)

61F-GPN-BT

61F-GPN-BC

Rated voltage

24 VDC

Allowable voltage range

85% to 110% of the rated voltage

Interelectrode voltage

5 VAC max.

Operation resistance (See note 1.)

Variable (0 to 100 k

)

Error

For scale of 0: +10 k

; For scale of 100: 

±

10 k

Release resistance

200% max. of the operation resistance

Switching between supply and drainage

Terminals 7 and 8 open: Automatic drainage operation
Terminals 7 and 8 shorted: Automatic supply operation

Output specifications

Open collector (NPN)
30 VDC, 100 mA max.

SPST-NO
5 A, 240 VAC (Resistive load)
2 A, 240 VAC (Inductive load: cos

φ

=0.4)

Life expectancy

---

Electrical:

100,000 operations min.

Mechanical: 20,000,000 operations min.

Wiring distance (See note 2.)

100 m max.

Ambient operating temperature

10 to 55

°

C

Ambient operating humidity

25% to 85%

Insulation resistance

100 M

 min. (at 500 VDC)

Dielectric strength (See note.)

2,000 VAC, 50/60 Hz for 
1 minute

Power consumption

2 W max.

Response time

Operating: 1.5 s max.
Releasing: 3.0 s max.

7

8

4

E

2

E

3

E

1

11

10

3

9

5

6

11

10

24 VDC
Recommended power supply; eg. OMRON S8VS

OUT+

OUT

OUT+

OUT

Pump ON (OFF)

Pump OFF (ON)

61F-GPN-BT

(See note.)

Open collector 
output

Relay contact 
output

Supply/ 
drainage 
selection 
terminals

Summary of Contents for 61F-GPN-BC

Page 1: ...vel Controller F030 E1 8 Product name Model number Conductive Level Controller 61F GPN BT 61F GPN BC Open collector NPN Relay contact SPST NO Front Socket PF113A E Electrode Holder See note Upper limit Mid point Lower limit Valve Short circuit Pump Chattering Load Open Collector Output Combines DC Power Supply with AC Sensing Method AC sine wave signals are sent to electrodes using a built in DC A...

Page 2: ... voltage Interelectrode voltage 5 VAC max Operation resistance See note 1 Variable 0 to 100 kΩ Error For scale of 0 10 kΩ For scale of 100 10 kΩ Release resistance 200 max of the operation resistance Switching between supply and drainage Terminals 7 and 8 open Automatic drainage operation Terminals 7 and 8 shorted Automatic supply operation Output specifications Open collector NPN 30 VDC 100 mA ma...

Page 3: ...s Therefore if the power supply connected across terminals 3 and 9 is interrupted the output from terminals 10 and 11 will turn OFF enabling detection of power interruptions Dimensions Application Examples 49 4 38 70 84 101 61F GPN BT 61F GPN B_ PF113A E ON OFF Battery Applications Liquid level control for solar power generation systems Drainage control for semiconductor wafer cleaning installatio...

Page 4: ...troller in locations subject to flammable gases or objects Insert the Socket until it securely clicks into place Do not short the load connected to the output terminals Do not connect the power supply in reverse Correct Use Mounting Mount to a panel of thickness 1 to 5 mm Do not mount the Controller in the following places Locations subject to strong vibrations or shocks Locations outside the spec...

Reviews: