Conductive Level Controller

 

61F-GPN-BT/-BC

E-15

Level 

Controllers

Conductive Level Controller

61F-GPN-BT/-BC

Battery (24 VDC) allows use in locations 
without AC power supply. AC sine-wave 
voltage between electrodes enables stable 
detection with no electric corrosion.

• Outputs can be set to self-hold at ON or OFF using special cir-

cuits.

• Adjustable sensitivity, with an operating resistance range of 0 to 

100 k

, allows use for a wide variety of liquids.

• Relay contact chattering conventionally caused by waves elimi-

nated using open collector output, reducing contact wear.

• Bears CE marking and is a UL recognized component.

Features

The 61F can now run on DC power to allow energy savings, greater safety, and use in 
emergency situations.

Ordering Information

Note:

A variety of Holders are available to suit different types of application. For details, refer to 

61F Floatless Level Controller 

(F030-E1-8)

.

Product name

Model number

Conductive Level Controller

61F-GPN-BT

61F-GPN-BC

Open collector (NPN)

Relay contact (SPST-NO)

Front Socket

PF113A-E

Electrode Holder

(See note.)

Upper limit

Mid-point

Lower limit

Valve

Short-circuit

Pump

Chattering

Load

Open Collector Output

Combines DC Power 
Supply with AC Sensing 
Method

AC sine-wave signals are 
sent to electrodes using a 
built-in DC-AC converter, 
preventing electric 
corrosion and ensuring 
safety.

Oscillator 
circuit

Detector 
circuit

Supports Multi-channel 
Sensing

Power supply circuits and 
detection circuits are 
isolated, allowing more 
than one Controller to be 
used in the same tank.

Control output 
is possible for 
upper limit, 
mid-point, and 
lower limit.

Signals can be used as 
direct input for a PLC. 
PNP output is also 
possible using the 
connection method.

Same Wiring for Supply 
and Drainage

Supply control and 
drainage control can be 
performed with the same 
wiring (short terminals 7 
and 8 for supply control). 
This makes it easy to 
perform wiring and 
confirm connection.

Drainage 
control

Supply 
control

Summary of Contents for 61F-GPN-BC

Page 1: ...vel Controller F030 E1 8 Product name Model number Conductive Level Controller 61F GPN BT 61F GPN BC Open collector NPN Relay contact SPST NO Front Socket PF113A E Electrode Holder See note Upper limit Mid point Lower limit Valve Short circuit Pump Chattering Load Open Collector Output Combines DC Power Supply with AC Sensing Method AC sine wave signals are sent to electrodes using a built in DC A...

Page 2: ... voltage Interelectrode voltage 5 VAC max Operation resistance See note 1 Variable 0 to 100 kΩ Error For scale of 0 10 kΩ For scale of 100 10 kΩ Release resistance 200 max of the operation resistance Switching between supply and drainage Terminals 7 and 8 open Automatic drainage operation Terminals 7 and 8 shorted Automatic supply operation Output specifications Open collector NPN 30 VDC 100 mA ma...

Page 3: ...s Therefore if the power supply connected across terminals 3 and 9 is interrupted the output from terminals 10 and 11 will turn OFF enabling detection of power interruptions Dimensions Application Examples 49 4 38 70 84 101 61F GPN BT 61F GPN B_ PF113A E ON OFF Battery Applications Liquid level control for solar power generation systems Drainage control for semiconductor wafer cleaning installatio...

Page 4: ...troller in locations subject to flammable gases or objects Insert the Socket until it securely clicks into place Do not short the load connected to the output terminals Do not connect the power supply in reverse Correct Use Mounting Mount to a panel of thickness 1 to 5 mm Do not mount the Controller in the following places Locations subject to strong vibrations or shocks Locations outside the spec...

Reviews: