Main circuit
24
■
Applicable Breakers
200V class
• When inverter ND rating setting
• When inverter LD/VLD rating setting
Note
1.
The models described in the table are examples of selection. When using the device, choose a model that has appropriate
breaking capacity and sensitive current by taking short circuit current and relevant laws and regulations into consideration
based on the rated current shown in the table.
2.
The applicable motor capacity is a selection example when standard motors 4-pole motor model 60HZ 200VAC (200V class)
is used.
3.
The electric durability ensured when the magnetic contactor is used in AC-1 class is 500,000 times, while emergency stop
during motor operation is 25 times.
4.
If there is emergency stop during motor drive or commercial operation is performed, choose the magnetic contactor on the
motor side in AC-3 class against the rated current of motor.
5.
If the rated capacity of inverter is larger than the motor capacity, choose instruments based on the inverter model.
Model
3G3RX2
Applicable
motor
(kW)
Applicable instrument (input voltage 200 to 220V)
Without power factor improvement reactor
With power factor improvement reactor
(3G3AX-AL or 3G3AX-DL)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Example
of model
Rated
current
AC-1
AC-3
Example
of model
Rated
current
AC-1
AC-3
A2004
0.4
EB-30E
5
HS8
HS8
EB-30E
5
HS8
HS8
A2007
0.75
EB-30E
10
HS8
HS8
EB-30E
5
HS8
HS8
A2015
1.5
EB-30E
15
HS8
HS8
EB-30E
10
HS8
HS8
A2022
2.2
EB-30E
20
HS8
HS8
EB-30E
15
HS8
HS8
A2037
3.7
EB-30E
30
HS8
HS20
EB-30E
20
HS8
HS20
A2055
5.5
EB-50E
40
HS20
HS25
EB-30E
30
HS8
HS20
A2075
7.5
EB-50E
50
HS35
HS35
EB-50E
40
HS20
HS25
A2110
11
EB-100E
75
HS50
H65C
EB-100E
60
HS35
HS50
A2150
15
RXK125-S
125
H65C
H80C
EB-100E
100
HS50
H65C
A2185
18.5
RXK125-S
125
H80C
H100C
EB-100E
100
HS50
H65C
A2220
22
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
A2300
30
EXK225
200
H125C
H150C
EXK225
150
H80C
H125C
A2370
37
RXK250-S
250
H150C
H200C
EXK225
200
H100C
H125C
A2450
45
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
A2550
55
EX400
400
H200C
H300C
EX400
300
H150C
H250C
Model
3G3RX2
Applicable
motor
(kW)
Applicable instrument (input voltage 200 to 220V)
Without power factor improvement reactor
With power factor improvement reactor
(3G3AX-AL or 3G3AX-DL)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Earth-leakage breaker
(ELB)
Magnetic contactor
(MC)
Example
of model
Rated
current
AC-1
AC-3
Example
of model
Rated
current
AC-1
AC-3
A2004
0.75
EB-30E
10
HS8
HS8
EB-30E
5
HS8
HS8
A2007
1.5
EB-30E
15
HS8
HS8
EB-30E
10
HS8
HS8
A2015
2.2
EB-30E
20
HS8
HS8
EB-30E
15
HS8
HS8
A2022
3.7
EB-30E
30
HS8
HS20
EB-30E
20
HS8
HS20
A2037
5.5
EB-50E
40
HS20
HS25
EB-30E
30
HS8
HS20
A2055
7.5
EB-50E
50
HS35
HS35
EB-50E
40
HS20
HS25
A2075
11
EB-100E
75
HS50
H65C
EB-100E
60
HS35
HS50
A2110
15
RXK125-S
125
H65C
H80C
EB-100E
100
HS50
H65C
A2150
18.5
RXK125-S
125
H80C
H100C
EB-100E
100
HS50
H65C
A2185
22
EXK225
150
H80C
H125C
RXK125-S
125
H65C
H80C
A2220
30
EXK225
200
H125C
H150C
EXK225
150
H80C
H125C
A2300
37
RXK250-S
250
H150C
H200C
EXK225
200
H100C
H125C
A2370
45
EX400
300
H200C
H250C
EXK225
225
H125C
H150C
A2450
55
EX400
400
H200C
H300C
EX400
300
H150C
H250C
A2550
75
EX600B
500
H300C
H400C
EX400
400
H200C
H300C