4-89
4-2 Function Mode
4
Func
tions
Forced Operator Function
• This function forcibly enables operation via the Digital Operator by turning on/off the multi-function
terminal if the frequency reference/RUN command sources are not set to the Digital Operator.
• If the Forced Operator function is selected in the multi-function input selection, the Inverter is
operated with the signal from the frequency reference source and RUN command source selected
in A001 and A002, when the input signal is OFF. When the signal is ON, the Inverter is forced to
operate with the frequency reference or RUN command from the Digital Operator.
• If you switch on/off this function during operation, the RUN command is reset to stop the Inverter
output. Before resuming operation, turn off the RUN command from each command source to
avoid possible danger and then input it again.
P/PI Switching Function
• This function allows you to switch the control (compensation) method for the speed control system
between proportional integral compensation and proportional compensation, when "sensorless
vector control", "0-Hz sensorless vector control", or "sensor vector control" is selected as the
control method.
RUN command
(FW, RV)
UP
DWN
Output
frequency
Acceleration/Deceleration does
not occur if the UP and DWN
terminals turn on simultaneously.
Data
Symbol
Function name
Status
Description
31
OPE
Forced operator
ON
Prioritizes the command from the Digital Operator (A020,
A220 set values) over the A001 and A002 settings.
OFF
Operates according to the A001 and A002 settings.
Available input terminals
C001 to C008
Related codes
A001, A002
Parameter No.
Function name
Data
Default setting
Unit
A044/A244/A344
V/f characteristics
selection
03: SLV (A344 is blank.)
04: 0 Hz (A344 is blank.)
05: Sensor vector
00
⎯
C001 to C008
Multi-function inputs
1 to 8 selection
43: PPI (P/PI switching)
⎯
⎯
H005/H205
Speed response
0.001 to 80.000
1.590
⎯
H050/H250
PI proportional gain
0.0 to 999.9/1000
100.0
%
H051/H251
PI integral gain
0.0 to 999.9/1000
100.0
%
H052/H252
P proportional gain
0.001 to 10.00
1.00
⎯
Summary of Contents for 3G3RX Series
Page 1: ...Cat No I560 E1 03 USER S MANUAL SYSDRIVE RXSERIES High function General purpose Inverter ...
Page 2: ......
Page 17: ...Chapter 1 Overview 1 1 Functions 1 1 1 2 Appearance and Names of Parts 1 4 ...
Page 22: ......
Page 23: ...Chapter 2 Design 2 1 Installation 2 1 2 2 Wiring 2 6 ...
Page 48: ......
Page 108: ......
Page 324: ......
Page 337: ...Chapter 6 Inspection and Maintenance 6 1 Inspection and Maintenance 6 1 ...
Page 348: ......
Page 392: ......
Page 436: ......
Page 437: ...Index ...
Page 441: ......