Sequence 4 - Momentary Alarm, Manual Reset, with Ringback, (Timer Option Off)
STATE 3
RESET
ABNORMAL
1 2 3 4 5 6 7 8
ON
SEQUENCE SWITCH
SETTING
SIL
ACK
WHILE
NORMAL
STATE 2
LAMP FAST
FLASH
HORN ON
STATE 5
STATE 1
LAMP OFF
HORN OFF
HORN OFF
STATE 4
LAMP FAST
FLASH
ACK WHILE
ABNORMAL
LAMP ON
HORN OFF
LAMP SLOW
FLASH
HORN OFF
RETURN
TO NORMAL
ABNORMAL
ACK WHILE NORMAL
Sequence 4 - Momentary (Fleeting) Alarm, Manual Reset, with Ringback, Timer Delay on inputs.
RESET
ABNORMAL
1 2 3 4 5 6 7 8
ON
SEQUENCE SWITCH
SETTING
STATE 1
STATE 6
RETURN TO
NORMAL
LAMP OFF
HORN OFF
TIMER OFF
LAMP OFF
HORN OFF
TIMER
RUNNING
TIME
OUT
SIL
ACK
WHILE
NORMAL
T
STATE 4
HORN OFF
TIMER OFF
STATE 2
LAMP FAST
FLASH
HORN ON
TIMER OFF
LAMP ON
HORN OFF
STATE 3
LAMP FAST
FLASH
HORN OFF
TIMER OFF
STATE 5
LAMP ON
HORN OFF
TIMER OFF
ACK WHILE ABNORMAL
RETURN TO
NORMAL
ACK WHILE
ABNORMAL
ABNORMAL
ACK WHILE NORMAL
LAMP SLOW
FLASH