Omniflex Omni8m C1477B Series User Manual Download Page 2

 

 

C1477B User Manual (UMC1477BR06) 

- 2 - 

© Omniflex 

 

SCOPE 

This is a User Manual supplied with your product and provides information 
necessary to install, set-up and operate the product. 

This manual covers the following product Model Numbers: 

 

Model 

Description 

C1477B-1 

Omni8

 with 10-15Vdc Power Supply 

C1477B-2 

Omni8

 with 20-60Vdc Power Supply 

C1477B-3 

Omni8

 with 85-264Vac/dc Power Supply 

 

 

 

 

 

 

D

ATE

 

R

EVISION

 

C

OMMENTS

 

Sep 1999 

Initial revision 

Nov 1999 

General Corrections during development. 

Feb 2000 

Released to Production 

Apr 2016 

Updated for B release 

May 2016 

Added humidity specifications and IP rating 

May 2018 

Updated mechanical drawing and photo due to new bracket 

 

 

COPYRIGHT AND PROTECTIVE NOTICES 

1.  The Copyright of this document and the associated drawings, is the property of Omniflex and 

is issued on condition that it is not copied, reprinted or reproduced or transmitted in any form 
or by any means, electronically, photocopying, mechanical or otherwise, nor its contents 
disclosed, either wholly or in part, without the consent in writing of, or in accordance with the 
conditions of a contract with Omniflex. 

2.  The publication of information in the document does not imply freedom from patent or other 

protective rights of Omniflex or others. 

3.  Although every intention is made to ensure that performance figures and data are accurate the 

company reserves the right to alter without notice any product or specification.  Performance 
figures and data must therefore be specifically confirmed by the company before they become 
applicable to any tender, order or contract. 

4.  In the case of electrical components, enough data is included in the drawings to allow 

maintenance of the equipment.  However, if component availability or substitution information 
is required please consult the factory for assistance, as it is impossible to include data on 
every component in this document. 

5.  This product is sold without liability for consequential loss of any description. 

 

 

Summary of Contents for Omni8m C1477B Series

Page 1: ...Omni8 Alarm Annunciator C1477B x...

Page 2: ...in any form or by any means electronically photocopying mechanical or otherwise nor its contents disclosed either wholly or in part without the consent in writing of or in accordance with the conditi...

Page 3: ...m annunciator systems Available in a range of power supply options the rugged Omni8 is designed to fit directly into local electrical panels without the need for external power conditioning or interfa...

Page 4: ...ATION 11 3 1 Installing the Omni8 in a panel 11 4 ELECTRICAL INSTALLATION 12 4 1 Introduction 12 4 2 Connection Table 12 4 3 Connecting the alarm inputs 12 4 4 Connecting the Relay 13 4 5 Connecting t...

Page 5: ...nt monitoring Integral audible device and control pushbuttons for ease of installation and use Relay output for common group alarm or external audible device control Removable terminals for easy insta...

Page 6: ...ction Figure 1 3 Side View showing 8 way Set up Switches 1 5 Installation and Set up Procedure The following steps should be implemented in the order shown to configure and install an Omni8 alarm annu...

Page 7: ...witch of SW2 e g SW2 1 sets the contact sense for input 1 and SW2 8 sets the contact sense for input 8 When the switch is OFF up then the input is set to NORMALLY OPEN i e the input will enter the ala...

Page 8: ...12 0 0 1 1 0 MOMENTARY ALARM AUTO RESET TIME DELAY ON RETURN TO NORMAL 16 60 seconds 13 1 0 1 1 0 PULSE MONITORING ALARM MANUAL RESET 17 17 1 1 1 1 0 INPUTS 1 4 SEQUENCE 1 INPUTS 5 8 SEQUENCE 27 FOR...

Page 9: ...d normally by pressing the Silence or Acknowledge Pushbutton This is useful in environments where the local internal audible will not be heard 4 Relay acts in Multiple Reflash Mode The relay is normal...

Page 10: ...C1477B User Manual UMC1477BR04 10 Copyright Omniflex...

Page 11: ...CKNESS 8mm MAXIMUM PANEL 42 44 92 180 48 Location of DIP switches Mounting bracket Figure 3 1 Mounting an Omni8 3 1 Installing the Omni8 in a panel Remove the metal bracket from the unit by removing t...

Page 12: ...wetting 10 Relay Change over Contact Normally Open Connection 11 Relay Change over Contact Common Connection 12 Relay Change over Contact Normally Closed Connection 13 No Connection 14 Earth 15 dc Pow...

Page 13: ...ported by all operating systems There is also a README TXT file on this disk Run this first to see which version of program you must run to use the supplied templates 5 2 Creating the Legend Film To c...

Page 14: ...sequence When the Omni8 is put into its test routine by depressing the TEST pushbutton any existing alarm states are remembered and the alarm annunciator will revert to its previous state when it ret...

Page 15: ...this procedure of marching sequence followed by the brief blank display period will be repeated continuously until the ACKNOWLEDGE pushbutton is depressed or until an input changes state This marchin...

Page 16: ...C selectable by DIP switch Max open cct voltage 15V dc between Common positive and all input terminals Max closed cct current 2 mA per input Max loop resistance to detect closed circuit 200 ohms Min...

Page 17: ...haracters 2 5mm Fast Flash Rate 140 flashes per minute Slow Flash Rate 35 flashes per minute TEMPERATURE RANGE Operating Relative Humidity 0 C to 60 C 32 F to 140 F Up to 90 RH non condensing Storage...

Page 18: ...nts IEC 61000 4 4 1995 2 kV DC power port 1 kV input output lines Supply Variations IEC 61000 4 7 1991 24 V dc 15 10 RoHS Compliance 2011 65 EU RoHS2 ORDERING INFORMATION C1477B 1 Omni8 with PSU 10 15...

Page 19: ...P ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 LAMP OFF HORN OFF HORN OFF Sequence 2 Momentary Fleeting Alarm Manual Reset Timer option off STATE 4 STATE 3 RESET WHILE NORMAL ABNORMAL LAMP ON...

Page 20: ...Only No Lock in Auto Reset Timer option off STATE 4 STATE 3 RETURN TO NORMAL ABNORMAL LAMP ON HORN OFF 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 2 STATE 1 LAMP OFF HORN OFF SIL ACK LAMP FAST FL...

Page 21: ...RETURN TO NORMAL ABNORMAL ACK WHILE NORMAL Sequence 4 Momentary Fleeting Alarm Manual Reset with Ringback Timer Delay on inputs RESET ABNORMAL 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE...

Page 22: ...FAST FLASH HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL Sequence 5 Momentary Fleeting Alarm First Out Manual Reset Auto Reset on subsequent Alarms RETURN TO NORMAL ABNORMAL S...

Page 23: ...TIVE FIRST OUT INACTIVE FIRST OUT INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RESET WHILE NORMAL ACK ACK WHILE ABNORMAL LAMP SLOW FLASH FIRST OUT ACTIVE LAMP ON LAMP ON LAMP FAST FLAS...

Page 24: ...et Re alarm after time out if still abnormal RESET WHILE NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH H...

Page 25: ...TIMER RUNNING TIME OUT LAMP FAST FLASH HORN ON TIMER OFF SIL LAMP FAST FLASH HORN OFF TIMER OFF ACK HORN OFF TIMER OFF T ACK LAMP SLOW FLASH Sequence 12 Momentary Fleeting Alarm Auto Reset with Time D...

Page 26: ...TIMER OFF TIMER OFF LAMP OFF HORN OFF TIMER OFF TIMER OFF ABNORMAL RETURN TO NORMAL ABNORMAL RETURN TO NORMAL TIME OUT TIME OUT ACK WHILE ABNORMAL SIL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NOR...

Page 27: ...L LAMP ON Sequence 21 Momentary Fleeting Alarm First Out Multiple Groups Auto Reset RETURN TO NORMAL ABNORMAL SUBSEQUENT 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN OFF SI...

Page 28: ...INACTIVE HORN ON FIRST OUT ACTIVE LAMP ON FIRST OUT INACTIVE RETURN TO NORMAL ACK WHILE NORMAL ACK WHILE NORMAL ACK WHILE ABNORMAL ACK WHILE NORMAL LAMP ON LAMP ON LAMP FAST FLASH LAMP FAST FLASH LAM...

Page 29: ...larm after time out if still abnormal RETURN TO NORMAL ABNORMAL LAMP ON 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING HORN OFF STATE 1 STATE 2 STATE 3 STATE 4 LAMP OFF HORN OFF LAMP FAST FLASH HORN ON SI...

Page 30: ...OFF ACK HORN OFF TIMER OFF T ACK WHILE ABNORMAL LAMP SLOW FLASH ACK WHILE NORMAL Sequence 29 Pulse Monitoring Alarm Auto Reset 1 2 3 4 5 6 7 8 ON SEQUENCE SWITCH SETTING STATE 1 STATE 2 LAMP OFF HORN...