Maxiflex T2 CPU User Manual
47
-© Omniflex
UMM124XBR04.pdf
DIT Number
Description
Set this register to 4000 to enable the User I/O Slot Address Table.
Set to this register to 0 to disable the User I/O Slot Address Table and revert to the full
addressing scheme.
64081
User Start Address for I/O Slot 2
64082
User Start Address for I/O Slot 3
64083
User Start Address for I/O Slot 4
64084
User Start Address for I/O Slot 5
64085
User Start Address for I/O Slot 6
64086
User Start Address for I/O Slot 7
64087
User Start Address for I/O Slot 8
64088
User Start Address for I/O Slot 9
64089
User Start Address for I/O Slot 10
64090
User Start Address for I/O Slot 11
64091
User Start Address for I/O Slot 12
64092
User Start Address for I/O Slot 13
64093
User Start Address for I/O Slot 14
64094
User Start Address for I/O Slot 15
64095
RESERVED
64096
RESERVED
64097
Programmer’s Global Address
This register sets the Global ID of the programmer PC or Laptop so that it is possible to
remotely program other devices connected to the network port of the local CPU via the
Programming Port. This value is usually set to 254 as a default but may be changed by
the user if desired.
64098
RESERVED
64099 – 64100
Serial Port Configuration
64099
RTS/CTS Timeout
If RTS/CTS handshaking is enabled, then the transmitter will assert RTS when it is
ready to transmit. If CTS is asserted before the timeout period in this register, then
transmission will commence. If CTS is not asserted, then the transmission will be
aborted. Handshaking is enabled by setting bit 12 of register 64100.