Maxiflex T2 CPU User Manual
37
-© Omniflex
UMM124XBR04.pdf
DIT Number
Description
48
Power Supply Status (applies to M1152 Power Supply only)
Bit 0 – Mains supply DISCONNECTED (0) or CONNECTED (1)
Bit 1 – Temperature Sensor DISCONNECTED (0) or CONNECTED (1)
Bit 2 – Battery Level Alarm HEALTHY (0) or ALARM (1)
When the measured battery level falls below the Alarm level configured in the
Setup M1152 PSU module group, this status goes to ALARM. If the current
battery voltage is above the Alarm level, then the status is HEALTHY.
Bit 3 – Battery Level Critical NOT CRITICAL (0) or CRITICAL (1)
When this status indicates CRITICAL, then the battery voltage has fallen below
the Critical battery level configured in the Setup M1152 PSU group. This condition
means that the battery requires urgent replacement.
49
Battery Level (when M1152 Power Supplies are used) measured in tenths of a volt
50 – 65
I/O Module Status
50
I/O Manifest Status
This is a bit map of the current I/O module status. The bit structure is as follows:
0
15
1
2
3
4
5
6
7
8
9
10
11
12
13
14
I/O Slot 1
I/O Slot 2
I/O Slot 3
I/O Slot 4
I/O Slot 5
I/O Slot 6
I/O Slot 7
I/O Slot 8
I/O Slot 9
I/O Slot 10
I/O Slot 11
I/O Slot 12
I/O Slot 13
I/O Slot 14
I/O Slot 15
Global I/O Status BIT
If a bit is set for I/O Slot
n
then the module installed in that I/O Slot does not match
the module configured. Refer to DIT 64051 for configuration of I/O modules.
The Global Status BIT is set if any of the I/O Slot bits are set. It can be used as an
I/O System Integrity flag.