Omni Instruments DFS2 Instruction Manual Download Page 4

 

Instruction Manual 2009  

Rev 3 

 

DFS2 Doppler Flow Switch 

   

 

 

 

 

 

 

 

Adjustments 
 
Range Selection  :  (refer JP1)

 

 

Range 1 (0 – 2 m/s) :- Jumper in position “1” 
Range 2 (0 – 6 m/s) :- Jumper in position “2” 
 

Setting Low Flow Trip Point :  

 

Move slide switch “S1” to “Lo” position.  Adjust the low trip potentiometer until the 
bar graph displays the required alarm setting as a percentage of the flow range 
selected. 
 
Example  :  Range 1 (0 – 2 m/s) 
 

 

Bar graph display – 50% 

 

 

Trip point setting – 1,0 m/s 

 

 

 

Setting High Flow Trip Point 

 

Move slide switch “S1” to “Hi” position and adjust high trip potentiometer to display 
the required alarm setting. 
 

NB

  Return slide switch to centre position for normal operation. 

 

Delay-Off Timer T1  : 

 

Under normal operating conditions the flow may fluctuate beyond the high or low trip 
settings momentarily.  The adjustable 0 – 60 sec. timer is adjusted with 
potentiometer “T1”.  Turn clockwise to increase the delay before the relay operates. 
 

Delay-On Timer T2 :

 

 
If the flow switch is used for pump control it is necessary to over-ride the trip settings 
during start-up, until the flow is established. 
The adjustable 0 – 60 sec. timer is adjusted with potentiometer “T2”.  Turn clockwise 
to increase the delay before the relay operates. 
 
 
 

Summary of Contents for DFS2

Page 1: ...ice Tel 44 0 845 9000 601 Fax 44 0 845 9000 602 info omniinstruments co uk www omniinstruments co uk Australia Asia Pacific Office Tel 61 0 282 442 363 Fax 61 0 294 751 278 info omniinstruments com au...

Page 2: ...ay on and delay off adjustable timers The DFS2 requires 24Vdc 115 or 230Vac power supply Two selectable flow ranges of 0 2 m s or 0 6 m s are available and the flow rate is displayed on a bar graph in...

Page 3: ...rate with or without latch Latch Selection JP2 Position 1 ON latch reset Relay energised in normal conditions i e between high and low limits giving a failsafe mode In alarm condition the relay will d...

Page 4: ...1 to Hi position and adjust high trip potentiometer to display the required alarm setting NB Return slide switch to centre position for normal operation Delay Off Timer T1 Under normal operating condi...

Page 5: ...must be cleaned to bare metal A small amount of pipe pitting even with spots of paint or rust will not cause problems e The transducer must be mounted accurately parallel to the pipe axis for correct...

Page 6: ...ting Relay Does Not Operate Possible Cause High trip point set below low trip point Unit faulty Corrective Action Adjust high trip point above low trip point Return unit to factory Signal Strength LED...

Page 7: ...1 Relay 1Amp SPDT Transducer Cable 3 metre length Temperature Sensor 20 to 90 C Electronics 10 to 50 C Electronics IP65 Polycarbonate Enclosure 120 x 120 x 55mm Power Input 115 230V ac 50Hz 24V dc 10...