DFS2 Doppler Flow Switch 

   

 

 

 

 

 

 

 

Connections 

 
 

Sensor 

Connect the sensor to the 4-way terminal 
plug as indicated in Figure 1 Terminal No’s 9 
to 12.

 

 

 

 

Power Input 

:

 

Check that the operating voltage of the flow 
switch is correct,  (i.e. 24Vdc, 115Vac or 
230Vac) before connecting the power supply.

 

 

 

 

Relay 

 

:

 

The relay has a changeover contact, which 
can be used for pump control, or simply to 
initiate an alarm condition. The single control 
relay will operate when the flow measured is 
outside the high or low trip settings and can 
be configured to operate with or without 
“latch”.

 

 

 

 

Latch Selection 

:

 

JP2 Position 1 – ON (latch/reset) 

  Relay energised in normal conditions 

i.e. between high and low limits giving 
a failsafe mode. 

  In alarm condition the relay will 

deenergise and latch in the 
deenergised position. 

  Close reset contact (7 & 8) to reset 

relay to energised position. Resetting 
will also reset timer T2. 

  If alarm condition remains after T2 

timer times out the relay will again 
deenergise and latch. 

  If used for pump protect either power 

the DFS2 from the pump circuit or 
close reset contact allowing normal 
flow conditions to be established 
before T2 timer times out. 

 
Position 2 – OFF (No latch/reset) 

  Relay is deenergised in normal 

conditions i.e. between high and low 
limits. 

  In alarm conditions the relay will 

energise. 

 

Summary of Contents for DFS2

Page 1: ...ice Tel 44 0 845 9000 601 Fax 44 0 845 9000 602 info omniinstruments co uk www omniinstruments co uk Australia Asia Pacific Office Tel 61 0 282 442 363 Fax 61 0 294 751 278 info omniinstruments com au...

Page 2: ...ay on and delay off adjustable timers The DFS2 requires 24Vdc 115 or 230Vac power supply Two selectable flow ranges of 0 2 m s or 0 6 m s are available and the flow rate is displayed on a bar graph in...

Page 3: ...rate with or without latch Latch Selection JP2 Position 1 ON latch reset Relay energised in normal conditions i e between high and low limits giving a failsafe mode In alarm condition the relay will d...

Page 4: ...1 to Hi position and adjust high trip potentiometer to display the required alarm setting NB Return slide switch to centre position for normal operation Delay Off Timer T1 Under normal operating condi...

Page 5: ...must be cleaned to bare metal A small amount of pipe pitting even with spots of paint or rust will not cause problems e The transducer must be mounted accurately parallel to the pipe axis for correct...

Page 6: ...ting Relay Does Not Operate Possible Cause High trip point set below low trip point Unit faulty Corrective Action Adjust high trip point above low trip point Return unit to factory Signal Strength LED...

Page 7: ...1 Relay 1Amp SPDT Transducer Cable 3 metre length Temperature Sensor 20 to 90 C Electronics 10 to 50 C Electronics IP65 Polycarbonate Enclosure 120 x 120 x 55mm Power Input 115 230V ac 50Hz 24V dc 10...

Reviews: