Safety Accessories Supplementary Sheet
46
OMICRON
WARNING
Death or severe injury caused by high voltage or current possible.
Contact OMICRON technical support if the
CP Strobe
Warning Lamp is not
flashing during the test.
7.5
Disconnection
To disconnect the
CP Strobe
Warning Lamp from the main device:
1. Make sure that the main device used with the
CP Strobe
Warning Lamp is switched off.
2. Press the
Emergency Stop
button on the main device.
3. Disconnect the
CP Strobe
connection cable from the
CP Strobe
Warning Lamp and the main device.
4. Disconnect the
Safety Connector Dongle
from the CP Strobe connection cable.
5. Connect the
Safety Connector Dongle
to the
SAFETY
output connector of the main device.
6. The
CP Strobe
has now been removed and the main device has the required
Safety Accessory
Dongle
installed on the
SAFETY
output connector.
7.6
Cleaning
To clean the
CP Strobe
Warning Lamp, use a cloth dampened with isopropanol alcohol.
WARNING
Death or severe injury caused by high voltage or current possible.
Before cleaning the
CP Strobe
, always disconnect it from the main device.