Special Instructions For Vacuum Ranges

On  vacuum  ranges,  the  C-NO  circuit  is  closed  at  sea  level
conditions.  Therefore,  increasing  vacuum  will  cause  the  C-
NC circuit to close while decreasing vacuum will cause the
C-NO  circuit  to  close.  Please  make  a  note  of  this  and
wire/adjust the unit accordingly. 

Tools Needed

Screwdriver

NOTE:

For  set  point  adjustments  and  re-calibration,  con-

nect control to a calibrated pressure gauge.

PSW-852, PSW-853

Remove  cover,  follow  same  procedure  as  paragraph  above.
Switches may be set together or apart, up to 100% of range
scales  (maximum  separation  on  models  PSW-852A*  is
defined in Table 1). On dual switch, either switch may be set
high. On triple switch models, the third (middle) switch has
no  over-travel  mechanism  and  must  always  be  set  to  the
highest  pressure  when  switches  are  set  apart.  Altering  the
setting  of  one  switch  will  usually  have  little  effect  on  the
other(s), however re-calibration may be desired at a critical
pressure setting and after changing switch(es) or sensor.

Table 1

Special Instructions for Models PSW-852A*

When  calibrating  the  Models  PSW-852A*,  Switch  2  (the
right switch as viewed from the front of the control) must be
set to the lower pressure value. Use a screwdriver to turn the
adjustment screw and obtain the desired actuation pressure
for Switch 2. Switch 1 can then be set following the proce-
dure  outlined  above  for  other  products.    Maximum  separa-
tion between Switch 1 and 2 is defined in Table 1.

PSW-855, 856

Controls are factory calibrated for maximum accuracy at the
dial  midpoint.  Switches  may  be  set  together  or  apart  up  to
100%  of  the  range  scale.  On  dual  switch  models  either
switch  may  be  set  high.  On  triple  switch  models,  the  third
(middle)  switch  has  no  over-travel  mechanism  and  must
always be set to the highest pressure  when the switches are
set apart. Altering the setting of one switch will usually have
little  effect  on  the  other(s),  however  re-calibration  may  be
desired at a critical setting or after changing switch(es) or sen-
sor. 

To  re-calibrate,  turn  pointer  to  desired  set  point  and  add
gauge pressure until switch transfers. If gauge pressure and
set  point  pressure  do  not  agree,  turn  zero  adjust  screw
clockwise to raise. Counter-clockwise to lower  setting. 

Tools Needed

Screwdriver

USE ONLY FACTORY AUTHORIZED REPLACEMENT PARTS
AND  PROCEDURES.    DISCONNECT  ALL  LIVE  CIRCUITS
BEFORE  PROCEEDING.  COMPONENTS  AVAILABLE  FOR
REPLACEMENT ARE THE SWITCHES. OTHER COMPONENTS
FACTORY REPLACEABLE ONLY.

REPLACEMENT OF SWITCH(ES)

1) Disconnect leadwires.

2) Remove the two mounting screws. On multi-switch 
controls, first remove switch bias springs (See Figure 1.)

3) Insert replacement switch and replace screws and bias
springs.

4) Check switch set point and re-calibrate per PART II if
necessary.

Part III - Replacements 

Part II - Adjustments 

Model & Range

Switch Separation
(% of Range Span)

PSW-852AA

(-300 to 0 ”wc VAC)

25%

PSW-852AB

(-10 to +10 ”wc)

35%

PSW-852AC

(-50 to +50 ”wc)

35%

PSW-852AD

(0.5 to 5 ”wc)

50%

PSW-852AE

(2.5 to 50” wc)

50%

PSW-852AF

(10 to 250 ”wc)

20%