Omega PSW-850 SERIES User Manual Download Page 3

GENERAL

Pressure variations are sensed by a bellows, diaphragm or piston
sensor which either actuates or de-actuates one, two or three snap-
acting switches at a pre-determined set point(s). Set point(s) is
adjusted by turning an internal knob and pointer or internal screw

Tools Needed

Screwdriver

Hammer

Adjustable wrench

MOUNTING

INSTALL  UNIT  WHERE  SHOCK,  VIBRATION  AND
TEMPERATURE  FLUCTUATIONS  ARE  MINIMAL.
ORIENT  UNIT  SO  THAT  MOISTURE  IS 

PREVENTED  FROM  ENTERING  THE  ENCLOSURE.  IF  UNIT
IS  BEING  INSTALLED  WHERE  HEAVY  CONDENSATION  IS
EXPECTED, 

VERTICAL 

MOUNTING 

(PRESSURE  CONNECTION  DOWN)  IS  REQUIRED.  DO  NOT
MOUNT  UNIT  IN  AMBIENT  TEMPERATURES  EXCEEDING
PUBLISHED LIMITS.

PSW-850  Series  pressure  controls  can  be  mounted  in  any
position, provided the electrical conduit is not facing up. The
preferred mounting position is vertical (pressure connection
down).

The cast-in knockouts for 3/4” electrical conduit are located on the
side and rear of the enclosure. These can easily be knocked out by
placing the blade of a screwdriver in the groove and rapping
sharply with a hammer.

Mount the unit via the (2) 1/4” screw clearance holes on the enclo-
sure. See Dimensions. Units may also be mounted via the NPT
pressure connection. 

ALWAYS HOLD A WRENCH ON THE PRESSURE HOUS-
ING HEX WHEN MOUNTING UNIT. DO NOT TIGHTEN BY
TURNING ENCLOSURE. THIS WILL DAMAGE SENSOR

AND WEAKEN SOLDER OR WELDED JOINTS.

Please read all instructional literature carefully and thoroughly before starting.

Pressure Controls

Part Numbers:
PSW-852, 853, 855,
856 Series

Part I - Installation

WIRING

DISCONNECT ALL SUPPLY CIRCUITS BEFORE WIRING.

ELECTRICAL RATINGS STATED IN LITERATURE AND ON
NAMEPLATE SHOULD NEVER BE EXCEEDED.  OVER-LOAD
ON A SWITCH CAN CAUSE FAILURE ON THE FIRST

CYCLE. 

WIRE UNITS ACCORDING TO LOCAL AND NATIONAL
ELECTRICAL CODES.  MAXIMUM RECOMMENDED WIRE
SIZE IS 14 AWG.

Connect conduit to the case and wire directly to the switch terminals
according to local and national electrical codes.  Bring the wires up to
terminals from the rear of the case. (See fig. 1.) If manual reset switch
or DPDT options are used, lead wires are supplied, color coded as
follows:

ALLOW ENOUGH SLACK SO AS NOT TO AFFECT SWITCH
MOVEMENT WHEN MAKING SETTING ADJUSTMENTS AND
ENSURE THAT THE WIRES ARE NOT TOUCHING THE

COVER WHEN INSTALLED.

NOTE:

For  larger  wire  gauges,  a  one  time  shift  may  be 

experienced or expected due to space limitations within the enclo-
sure. Verify setpoint after installation. 

NOTE: 

The middle switch assembly is omitted for dual switch con-

trollers.  The outer switch assemblies are omitted for single switch
controllers. Type PSW-852, 853 controls have internal screw adjust-
ments and type PSW-855, 856 have cam assemblies for internal cali-
brated adjustments. 

Switch 1

Switch 2

Common

Violet

Yellow

Normally Open

Blue

Orange

Normally Closed 

Black

Red

Figure 1

Reviews: