requirements of the product (including reliable grounding, power leakage, and wire-diameter electrical load).
Do not install the product before the modification if the electrical installation requirements of the product are
not met.
◼
Air conditioners must use a dedicated power supply. The power voltage must conform to the rated voltage.
◼
The external power supply circuit of the air conditioner must include a grounding line, and the grounding line
of the power cable connecting to the indoor unit must be securely connected to the grounding line of the
external power supply.
◼
Electrical wiring work must be carried out by a professional technician, and must comply with the labels stated
in the circuit diagram.
◼
The fixed wiring connected must be equipped with an all-pole disconnection device with a minimum 3mm of
contact separation.
◼
Leakage protection devices must be configured according to national standards for electrical equipment.
◼
The power cord and signal cables must be neatly and properly arranged without interfering with one another
or contacting with any connecting pipes or valves.
◼
When multiple air conditioners are installed in a centralized manner, ensure load balance of the three-phase
power supply, and avoid installing multiple units at the same phase of the three-phase power supply.
◼
In general, two wires cannot be connected unless the joint is securely welded and wrapped with insulation
tape.
Power the system on only after all the completed wiring operations have been carefully
checked.
8.2 Power Supply Specifications
Four-way Cassette
:
IECS018(24,31,36,42,48)J3A-DWG053(71,90,105,120,140)
Model
Power supply
Switch capacity of the
main power supply(A)
power cable includes
grounded wire
(mm
2
)
Indoor/Outdoor
unit power
cable includes
grounded wire(mm
2
)
Voltage and
frequency
53
220V-240V~50Hz
20
2X2.5+1X2.5
4×2.5
71
220V-240V~50Hz
25
2X4.0+1X4.0
4×2.5
Model
Power supply
Switch capacity of
the main power
supply(A)
power cable includes
grounded wire
(mm
2
)
Connective
wire(mm
2
)
Voltage and
frequency
90
IDU
220V-240V~50Hz
6
2X1.0+1X1.0
3X0.75
ODU
25
2X2.5+1X2.5
105
IDU
220V-240V~50Hz
6
2X1.0+1X1.0
3X0.75
ODU
32
2X4.0+1X4.0
120
IDU
220V-240V~50Hz
6
2X1.0+1X1.0
3X0.75
O
DU
32
2X4.0+1X4.0
140
IDU
220V-240V~50Hz
6
2X1.0+1X1.0
3X0.75
O
DU
40
2X6.0+1X6.0
Summary of Contents for OTEC ICHD009J0A-DMG026
Page 1: ...IECS D Series Round Flow Ceiling Cassette Technical Manual ...
Page 4: ...2 Part 1 General information 1 Model Names of Indoor Outdoor Units 3 2 External Appearance 4 ...
Page 33: ...109 2 Installation of Four way Cassette 2 1 Installating space ...
Page 61: ...17 ICHD031J0A DMG090 ...
Page 62: ...18 ICHD036J0A DMG105 ICHD042J0A DMG120 ICHD048J0A DMG140 ...
Page 63: ...19 ICHD060J0A DMG160 ...