21
2.5
Powering Down the Loads and UPS
Follow these steps to turn off the power of the UPS:
1. Turn off the power to loads connected to the UPS. Refer to the operating instructions for each load.
2. Turn the UPS switch to the “ ” position.
2.6 Cleaning
!
Before cleaning, turn off the switch of the UPS. Unplug the UPS from the power outlet.
!
Also unplug the battery cable for the Long Back up Time model.
!
Clean all surfaces with a soft, lint-free cloth that you have dampened in a mild solution of detergent and water. The
cloth must not be too wet.
WARNING-
1. Never spill water or cleaning fluid inside the unit. Should this happen accidentally, call immediately your
maintenance authority.
2.Do not use scouring pads, steel wool, harsh chemical agents, or anything that can damage the surface of
the unit
2.7 Storage
If you plan to store the UPS, there is a risk that the battery might discharge to the point where it is permanently
discharged. To prevent this from happening, follow these steps before storing the unit:
1. Fully charge the battery before storing the unit.
2. Recharge the battery for 24 hours at intervals not greater than 3 months.
2.8 Battery
Maintenance
The battery should be serviced only by the qualified technicians.
OMEGA 1000
Standard model: Use SEALED LEAD ACID 12V 7(or 7.2)Ah×4 (CSB GP1270-F2 CSB GP1272-F2,
GS PE12V7.2) battery for replacement.
OMEGA 2000
Standard model: Use SEALED LEAD ACID 12V 7(or 7.2)Ah×6 (CSB GP1270-F2,CSB GP1272-F2,
GS PE12V72) battery for replacement
OMEGA 3000
Standard model: Use SEALED LEAD ACID 12V 7(or 7.2)Ah×10 (CSB GP1270-F2,
CSB GP1272-F2, GS PE12V72) battery for replacement.
3 Troubleshooting
This chapter describes problems you may encounter when using the UPS and the possible solution to these problems.
Also by the different LEDs display and buzzer beeping to let the user easily communicate with service people.
3.1
Indicators of LEDs and Buzzer
LEDs
"
:
On
×
:
Off
Buzzer
BP:
Continuous
×
:
Off
----:
Every 4 seconds
-|-:
Every 15 seconds
====:
Every second
**-**:
2 times every second
?
:
Depends on the Alarm condition
LEDs Display
LINE BYPASS INV ALARM
OVER
LOAD
Buzzer
Main mode operating
N/A
"
×
"
×
×
×
Main mode operating
N/A
"
"
"
×
×
×
Transferring from
Bypass to Inverter
N/A
×
×
"
×
×
----
Battery mode
operating
Check the ac utility or the
fuse on the rear panel
×
×
"
×
×
-|-
Battery discharges
over 30 minutes
N/A
×
×
"
×
×
====
Battery low warning
N/A
"
×
"
×
×
×
Full load condition
Unplug the least critical
equipment
N/A
×
"
×
"
**-**
Over load condition
Unplug the least critical
equipment
N/A
"
×
"
×
BP
Fault
Refer to 3.2 description and
call the service people
22
3.2
Indicators of LED in Alarm Status
When the “Alarm” LED is on, please write down the LEDs bar display (from bottom to top) and contact to the service
people.
LED 1,2 On
Inverter over voltage
LED 1,3 On
Inverter under voltage
LED 1,4 On
Over temperature
LED 1,5 On
Charging over voltage
LED 1,2,4 On
Output short circuit
LED 1,2,5 On
BUS over voltage
LED 1,3,5 On
PFC or Charger malfunction
LED 1,4,5 On
Over load occurred in battery mode operating
Specifications
Model OMEGA
1000
OMEGA 2000
OMEGA 3000
Rated Power
1000VA/700W
2000 VA / 1400 W
3000VA/2100W
Operation
True On-Line High Frequency UPS
Voltage 160-270VAC
Current
6A max
12A max
16A max
Frequency 50(60)Hz+/-5%
Power Factor
>0.95 (Full load)
Input
Phase
Single Phase / H+N+GND
Voltage 220/230//-2%
Frequency 50(60)Hz+/-0.5%
Waveform True
Sinewave
Stable
110-140% for 20 seconds
Overload
Peak current
>140% for 10 cycles
Line Mode
#$
Battery Mode : 0mS
Output
Transfer Time
Inverter Mode
#$
Bypass Mode : <4mS
DC Voltage
48VDC
72 VDC
120VDC
Quantity
12VDC/7AH×4pcs 12VDC/7AH×6pcs 12VDC/7AH×10pcs
Charging Current
1A
Back-Up Time
10~15 Minutes (Depends on the Load Size)
Battery
Recharging Time
8~10 Hours (Recovery to 90% Capacity)
Battery Discharge
Sounding every 4 seconds
Discharge over 30 minutes
Sounding every 15 seconds
Battery Low
Sounding every second
Overload Rush
beeping
Audible
alarm
Fault Continuously
beeping
Acoustic Noise
<45dBA(1 meter)
<50dBA(1 meter)
Temperature 0-40°C
0-40°C
0-40°C
Relative Humidity
<95%(Non-condensing)
Environment
Altitude <3000
meter
Dimension
(D)467mm
×
(W)190mm
×
(H)255mm
(D)532mm
×
(W)190mm
×
(H)255mm
(D)470mm
×
(W)225mm
×
(H)480mm
Weight (Net)
22Kgs
29Kgs
49Kgs
Summary of Contents for Juicer 1000
Page 12: ...23 www unitek europe com...