TROUBLESHOOTING

Note:

If you experience an unusual problem that is not described in this section, or if troubleshooting procedures will not

restore the unit to normal operation, please contact Omega.

SYMPTOM

CAUSE

SOLUTION

1)  Plugged or blocked orifice.

1)  Remove orifice screw and clean

orifice with wire or pin <0.009"
diameter

2)  Supply pressure too low. 

2)  Supply pressure must be at least 5

PSIG above the 100% output.

1)  Zero set too low.

1)  Turn zero adjustment counter-

clockwise until output pressure
increases then follow calibration
procedure.

2)  Electrical connection has opened or

wrong type of signal applied.

2)  Check electrical connections to

insure that there is a correct input
signal reaching the transducer.

Wires connected in reverse

Insure wiring is connected per Electrical
Connection section.

Pneumatic connections reversed or
supply and output both connected to
“IN” ports.

Insure supply is connected to port
marked “IN” and output is connected to
port marked “OUT”.

Sluggish Performance or Reduced
Range

matter the input signal3.

Transducer remains at start up no

signal goes up.)

(Pressure goes down when input

Transducer works in reverse.

Output Pressure same as supply
Pressure with no signal effect.

IP210A Unit shown without female 43650A connector.

Figure 3

Summary of Contents for IP210A Series

Page 1: ...e mail info omega com For latest product manuals www omegamanual info Shop online at omega com User sGuide IP210A SERIES ELECTROPNEUMATIC CONVERTERS...

Page 2: ...h America U S A Omega Engineering Inc Headquarters Toll Free 1 800 826 6342 USA Canada only Customer Service 1 800 622 2378 USA Canada only Engineering Service 1 800 872 9436 USA Canada only Tel 203 3...

Page 3: ...o rear of panel Attach transducer See Fig 3 to panel using two 10 32 screws and two threaded mountingholesonthebackoftheunit Panel with no access to rear of panel Attach bracket See Fig 1 and 3 to tra...

Page 4: ...the input wires entering the transducer is recommended should installationnexttohighelectromagneticinterferencebenecessary ToolsRequired Solder SolderingIron WireCutter Stripper Includedwiththeunit In...

Page 5: ...tivethattheoutputpressurebecloselymonitoredasturningthezeroscrewexcessivelycoulddamagetheflexure Note inputpercentagereferstothefollowingexamples Once the transducer has been mounted and air supply co...

Page 6: ...ow calibration procedure 2 Electrical connection has opened or wrong type of signal applied 2 Check electrical connections to insure that there is a correct input signal reaching the transducer Wires...

Page 7: ...moisture or vibration improper specification misapplication misuse or other operating conditions outside of OMEGA s control Components in which wear is not warranted include but are not limited to co...

Page 8: ...Air Velocity Indicators Turbine Paddlewheel Systems Totalizers Batch Controllers pH CONDUCTIVITY pH Electrodes Testers Accessories Benchtop Laboratory Meters Controllers Calibrators Simulators Pumps I...

Reviews: