Omega FSW-6000 Series User Manual Download Page 11

Calibration

To Start:

Calibration for Flow / No Flow:

Set Point Adjustment:

1 - Remove the enclosure lid (Note: the screws are self-retaining)
2 - Start the power supply and wait 5 minutes until the FSW is active and has reached a

stable point within the medium.

3 - Let the regular or desired flow reach its point of normal operation.

1 - Set the flow rate at the normal range of operation.
2 - Turn the potentiometer counter-clockwise until the central LED turns red.
3 - With the central LED red, turn the potentiometer clockwise until the central LED

changes to a blinking green state.

4 - Continue to turn the potentiometer clockwise until all green LEDs in the bar graph are

on.

5 - In order to be sure that the adjustment is not at a critical state give the potentiometer

an additional quarter turn clockwise.

The flow switch can be adjusted to indicate either increasing flow, or decreasing flow at a
specific set point within 3cm/s to 3m/s.
It is important to determine the specific set point at which the flow switch should activate
or de-activate.

0%

100%

BARGRAPH - Lights ON

Set Point

BARGRAPH - Lights ON

0%

100%

BARGRAPH - Lights OFF

Set Point

BARGRAPH - Lights OFF

Adjust

Adjust

11

www.omega.com e-mail: [email protected]

Summary of Contents for FSW-6000 Series

Page 1: ...m For latest product manuals www omegamanual info Shop online at omega comSM User sGuide FSW 6000 FSW 7000 Series Thermal Dispersion Flow Switches This datasheet has been downloaded from http www digc...

Page 2: ...ervice 1 800 872 9436 USA Canada only Tel 203 359 1660 Fax 203 359 7700 e mail info omega com For Other Locations Visit omega com worldwide omega com info omega com The information contained in this d...

Page 3: ...duction 4 Models Dimensions 5 Wiring Diagram 6 Pre Installation 9 FSW Relay Status Guide 8 Installation 10 Calibration 11 Handling 13 Technical Specifications 14 Trouble Shooting 16 www omega com e ma...

Page 4: ...e switch point status of the unit The sensing element and connection of the FSW are made with 316 S S and can be coated when necessary The enclosure is offered in either nylon or aluminum All models c...

Page 5: ...ocess Connections TC Connection ANSI 150 ANSI 300 Rubber Seal Process Connection NPT BSP FF RF 100mm 100mm 100mm 50mm 45mm 35mm 50mm 75mm 12mm 12mm 12mm 3 4 NPT 1 NPT 1 NPT NPT FSW w insertion length...

Page 6: ...mmon Green NC Black Power Supply Contacts Ground FSW6000 AC Powered 2000mm 1 2 Connector 12mm NO or NC contact 2000mm 1 2 Connector 12mm _ NO or NC contact Nylon Housing M12 Connector Optional M12 Con...

Page 7: ...er Supply NC Contact P1 Set Point Potentiometer Adjust B1 8 LED s Red LED Yellow LED Green LED L1 Central LED Green With flow Red No flow Bargraph 1 2 3 Ground 4 NO Contact 5 Common 6 Power Supply Pow...

Page 8: ...larm LED Status RED GREEN Set Point OFF ON FSW SPDT Status NO 4 NC 6 C 5 C 5 Application FSL Condition Normal Alarm LED Status GREEN RED Set Point ON OFF FSW SPDT Status NO 4 NO 4 NO 4 NC 6 NC 6 NC 6...

Page 9: ...e risk of air accumulating in the pipe Keep in mind that the ideal mounting location is where the pipe is always full This will ensure that the switch is always immersed in the flow Fig 2 correct fig...

Page 10: ...on the side as long as the tip of the probe sits within the middle of the pipe See Fig 2 When the pipe is in a vertical position the FSW should be installed only when the water flow is upward See Fig...

Page 11: ...ter clockwise until the central LED changes to a blinking green state 4 Continue to turn the potentiometer clockwise until all green LEDs in the bar graph are on 5 In order to be sure that the adjustm...

Page 12: ...for 2 minutes 2 Turn the potentiometer clockwise until the central LED is blinking green 3 Turn the potentiometer counter clockwise until the central LED turns red 4 Continue to turn the potentiometer...

Page 13: ...rosion or deposit build up If deposits are found clean the sensor to ensure optimum performance The FSW should not be dropped or suffer any impact or fall that could damage the electronics or the ther...

Page 14: ...ousing 2 SPDT Large Aluminum Housing Cable gland w 2000mm cable M12 connector or NPT Red led flow is below setpoint Yellow led flow is at setpoint Green led flow is above setpoint 1450 PSI 100 Bar 450...

Page 15: ...low is above setpoint Max Pressure 1450 PSI 100 Bar 4500 PSI 300 Bar upon request Accuracy Response Time Enclosure Material Glass filled nylon option Aluminum Wetted Material 316 Stainless Steel Class...

Page 16: ...stallation insertion length Verify the calibration Check power supply Cause Solution Radio frequency interference Sensor is potentialy defective Flow switch turns on or off suddenly Relay remains clos...