23
Configuration / Operation
10
Section 10.1 - General
settings which fit the application. For each menu there is a scrolling help text which is
automatically shown in line 3 on the display.
Configuration is carried out by using the 3 function keys:
will increase the numerical value or choose the next parameter
will decrease the numerical value or choose the previous parameter
will accept the chosen value and proceed to the next menu
When configuration is completed, the dispaly will return to the default state 1.0.
Pressing and holding will return to the previous menu or return to the default
state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state (1.0)
without saving the changed values or parameters.
ok
ok
Section 10.2 - Password protection
mitter in order to ensure a high degree of protection against unauthorised
modifications to the configuration. Default password 2008 allows acces to all
configuration menus
Section 10.3 - Signal and sensor error info (Display front
DRSL-DISPLAY
)
Sensor error (see limits in the table) is displayed as SE.BR (sensor break) or SE.SH
(sensor short). Signals outside the selected range (not sensor error, see table for limits)
are displayed as IN.LO indicating low input signal or IN.HI indicating high input
signal. The error indication is displayed in line 3 as text and at the same time the
backlight flashes. Line 4 of the display is a status line which displays COM (flashing
bullet) indicating correct functioning of DRSL-DISPLAY, and arrow up/down which
indicates tendency readout of the input signal.